Introduction to Puhui 200X Adjustable Pilot Pressure Reducing Valve
200X pilot operated pressure reducing valveThe structure diagram and working principle of the adjustable pilot operated pressure reducing valve are provided by Hebei Puhui. The representative product of Puhui brand YSA416 fire pressure reducing and stabilizing valve, which can both reduce pressure and stabilize pressure. There is a need to make a call. The supplied caliber includes small DN40 and large DN600; There are three pressure levels: 1.0MPa, 1.6MPa, and 2.5MPa; Main body material: cast iron: HT200 and QT450; Main accessory brass. Ready stock all year round.
Main parameters of 200X pilot operated pressure reducing valve
Nominal pressure: 1.0MPa-1.6MPa-2.5MPa;
Low action pressure: ≥ 0.02MPa;
Specification caliber: 50 to 600mm;
Medium temperature: 0 to 80 degrees;
Applicable medium: clear water;
Connection form: flange;
Shell material: cast iron or brass.
Working principle of 200X pilot operated pressure reducing valve
YSA416 pressure reducing and stabilizing valveIt is a representative product of the 200X pilot operated pressure reducing valve. The YSA416 fire pressure reducing and stabilizing valve controls the flow rate of the main valve by regulating the required pressure through the pilot valve. When the pressure behind the pilot operated pressure reducing valve is lower than the set value, the pilot valve immediately releases the pressure in the main valve control chamber, causing the valve disc to open moderately. When the pressure behind the pilot operated pressure reducing valve reaches the set value, the pressure in the main valve control chamber increases, causing the valve disc opening to decrease until it closes. YSA416 pressure reducing and stabilizing valve can set the pressure behind the valve according to on-site needs, and the pressure behind the valve will not change due to changes in the pressure before the valve, nor will it change due to changes in the flow rate behind the valve.
Structure diagram of 200X pilot operated pressure reducing valve
The image in the following picture isStructure of 200X Pilot operated Pressure Reducing ValveThe schematic diagram shows that the main components of this pilot operated pressure reducing valve include: 1. Valve body, internal valve disc, and spring. The interception port in the picture is in a fully closed state, located at the valve disc next to the lower part of the valve shaft. From the figure, it can be seen that this valve has three main parts. The upper valve chamber has a spring, which is located in the upper valve chamber, and the middle part is the valve's internal organ; Below the interception port is the lower valve chamber.
2. The main valve is equipped with external components, including a pilot pressure reducing head, two copper pipes, and one needle valve. Copper ball valves are equipped on finished copper pipes with larger diameters above DN200. And pressure gauges can also be requested to be configured.
![]() |
Please refer to the installation requirements for YSA416 fire pressure reducing and stabilizing valve and 200X pilot operated pressure reducing valve, as well as the installation requirements for Y series adjustable pressure reducing valve and the following requirements:
200X pilot operated pressure reducing and stabilizing valveOccasional problems encountered on site and troubleshooting methods
phenomenon
|
reason
|
Exclusion method: 200X pilot operated pressure reducing valve
|
No pressure reduction and stabilization
|
A. Direction of inlet and outlet
B. The main valve diaphragm is damaged
C. Needle valve not open
D. The ball valve is not open
E. The adjustable pressure reducing diaphragm is damaged
F. There are foreign objects inside the valve body
|
A. Adjust to 200X pilot operated pressure reducing valve
B. Replace the main valve diaphragm
C. Open the needle valve
D. Open the ball valve
E. Replace the adjustable pressure reducing valve diaphragm
F. Cleaning up
|
There is a constant voice
|
A. There are foreign objects inside the valve body
B. Closing speed too fast 200X pilot operated pressure reducing valve
|
A. Impurities
B. Adjust needle valve opening 200X pilot operated pressure reducing valve
|
Installation, commissioning and maintenance instructions for 200X pilot operated pressure reducing valve
When installing in the pipeline network, attention should be paid to the direction of water flow being consistent with the arrow on the valve body.
2. Install a Y-shaped filter in front of the valve to prevent dirt from entering the valve and affecting the static pressure effect.
3. Gate valves should be installed before and after the valve for maintenance purposes.
4. The opening degree of the needle valve is 1/4 turn, and the control valve is in the fully open position.
During the initial operation of the 5.200X pilot operated pressure reducing valve, the gate valve in front of the pressure reducing valve should be slowly opened and not fully opened at once. If it is found that the pressure is not reduced. Close the gate valve in front of the valve, drain the rear water, and then slowly reduce the pressure from the water supply.
The pressure adjustment of the 6.200X adjustable pilot operated pressure reducing valve should be carried out under static pressure, that is, when the gate valve behind the valve is closed. Rotate the adjusting screw of the pilot valve clockwise to increase the pressure behind the valve. Rotate the valve counterclockwise to decrease the pressure behind the valve. Adjust the required pressure to lock the nut. If the pressure exceeds the required value during pressure regulation, the pressure behind the valve should be reduced and then adjusted from low to high again.
If there is a "hunting vibration" phenomenon (periodic opening or closing) during the operation of the 7.200X adjustable pilot pressure reducing valve, the needle valve should be slightly closed in a clockwise direction to reduce the closing speed of the shut-off port and prevent the "hunting vibration" phenomenon.