Water cooled chiller unit at room temperature(7℃)
model |
Refrigeration capacity(kW) |
compressor(kW) |
Chilled water pump(kW) |
Whole machine power(kW) |
External dimensions(mm) |
weight |
LSX-10 |
9.8 |
1/2.1 |
0.37 |
2.5 |
1150*750*900 |
150 |
LSX-16 |
15.9 |
1/3.5 |
0.55 |
4.1 |
1150*750*900 |
220 |
LSX-29 |
28.6 |
1/5.7 |
0.75 |
6.4 |
1350*850*1200 |
310 |
LSX-32 |
31.7 |
1/6.4 |
0.75 |
7.2 |
1350*850*1200 |
360 |
LSX-36 |
36.3 |
1/7.3 |
1.10 |
8.4 |
1350*850*1200 |
450 |
LSX-46 |
46.0 |
1/10.2 |
1.10 |
11.3 |
1600*900*1200 |
650 |
LSX-62 |
61.5 |
1/13.8 |
1.50 |
15.3 |
1900*900*1200 |
850 |
LSX-64 |
63.4 |
2/12.8 |
1.50 |
14.3 |
1900*900*1200 |
850 |
LSX-73 |
72.6 |
2/14.6 |
1.50 |
16.1 |
1900*900*1200 |
1050 |
LSX-91 |
91.0 |
2/20.3 |
2.20 |
22.5 |
2150*1000*1200 |
1250 |
LSX-123 |
123 |
2/27.7 |
2.20 |
29.9 |
2300*1100*1300 |
1350 |
explain:1.Inlet temperature of chilled water12℃, effluent7℃; ambient temperature35℃;
2.This series of units adopts fully sealed compressors imported from Europe and America, with superior performance and strong resistance to liquid hammer;
3.Safe working range of the unit: inlet temperature of chilled water9~20℃;
4.Power supply system:3P-380V-50HZIt is recommended to use a three-phase four system, allowing for voltage fluctuations of ±5%Frequency fluctuation ±2%;
5.The actual head of the host is the pump head minus the internal head loss of the host. (1mH20=9.8kPa)
6.In addition to the above specifications and requirements, the company can provide non-standard products according to customer requirements. If necessary, please contact our sales team
Department contact.