model | HX-20 | HX-25 | HX-20H | HX-25H | HX-35H | 2)HX-45H | 2)HX-55H | ||
---|---|---|---|---|---|---|---|---|---|
Temperature1)(Bath solution: water) | Working temperature(℃ / ℉) | +3 ~ 40 / +37.4 ~ 104 | |||||||
Temperature stability at 15 ℃(±℃ / ℉) | 1 / 1.8 | ||||||||
Cooling power(Bath solution: water) | At 20 ℃(kW) | 1.9 | 2.4 | 1.9 | 2.4 | 3.6 | 4.7 | 7.1 | |
At 10 ℃(kW) | 1.4 | 1.7 | 1.4 | 1.7 | 3.1 | 3.6 | 5.1 | ||
At 5 ℃(kW) | 1 | 1.4 | 1 | 1.4 | 2.4 | 2.9 | 4.2 | ||
pump | Maximum flow rate(L / min, gal / min) | 40 / 10.6 | 28 / 7.39 | ||||||
Maximum pressure(bar / psi) | 1.43 / 20.74 | 4.3 / 62.37 | |||||||
size | Maximum filling volume(L / cu ft) | 35 / 1.24 | 45 / 1.59 | ||||||
Pipe diameter(mm / inch) | 20 / 3/4 | ||||||||
Infusion import(Ø, mm / inch) | 50 / 1.9 | ||||||||
External dimensions(W×L×H, mm / inch) | 620×785×990 / 24.4×30.9×39 | 745×800×1095 / 29.3×31.5×43.1 | |||||||
Net weight(kg / lbs) | 93 / 205 | 101 / 223 | 97 / 214 | 105 / 231 | 120 / 265 | 130 / 287 | 140 / 309 | ||
Power requirements(230V, 60Hz) | 8.5A | 9A | 9.3A | 9.8A | 15A | 19A | |||
Item number | AAH64011K | AAH64021K | AAH64111K | AAH64121K | AAH64131K | AAH64141K | - | ||
Power requirements(230V, 50Hz) | 7A | 7.6A | 7.9A | 8.8A | 14A | ||||
Item number | AAH64012K | AAH64022K | AAH64112K | AAH64122K | AAH64132K | - | - | ||
Power requirements(120V, 60Hz) | 17A | 22A | |||||||
Item number | AAH64013U | AAH64023U | - | - | - | - | - | ||
Power requirements(380V, 60Hz) | 10A | 11.5A | |||||||
Item number | - | - | - | - | - | AAH64149K | AAH64159K | ||
Power requirements(380V, 50Hz) | 7A | 8.5A | |||||||
Item number | - | - | - | - | - | AAH64148K | AAH64158K |
1) The technical parameters comply with DIN 12876 standard.
2) Only HX-45H and 55H are 380V and 60Hz.
The above parameters were measured at 50Hz.
※ Room temperature may affect product parameters
Cooling water circulation device (low-temperature type)
The HL series has a strong and powerful cooling circulation device, which has the characteristics of stable temperature and a wide range of cooling capacity.
model: HL-05/10/15/15H/20/20H/25H/35H/45H/55H cooling water circulation device (low-temperature type)
The HL series has a strong and powerful cooling circulation device, which has the characteristics of stable temperature and a wide range of cooling capacity.
model: HL-05/10/15/15H/20/20H/25H/35H/45H/55H
Performance characteristics
- Temperature range:- 20℃~40℃
- The maximum cooling power is 7.1 kW at 20 ℃.
- The maximum flow rate of the circulating pump is 70L/min. and the pressure is 6.0 bar.
- The cooling system can reduce energy waste and achieve maximum cooling effect.
easy to operate
- Simplified VFD touch screen for operation.
-Interactive touch buttons make it easy to read VFD displays.
-Set the resolution to 0.1 ℃/℉
-Quick keyboard lock function to prevent unauthorized operations.
-The signal indicator light displays the operational status. - The LED liquid level indicator can also be seen from a distance.
- Built in pressure gauge, which can clearly show the pressure of the pump at a glance.
- The high/low pressure gauge can clearly check the status of the refrigeration system at a glance.(for H type)
- The spacious inlet allows for easy and safe pouring of solution into the system
- Two backup valves can prevent coolant leakage.
- Mobile grid vents can reduce contamination of the condenser.
- Standard casters for easy installation and movement.
safety features
- Automatic diagnostic function, automatically identifying errors.
- Safety protection function with signal alarm.
-Low liquid level and no bath protection, there will be an alarm sound to remind when there is an error signal on the display.
-Over temperature protection, if the device experiences over temperature due to external environment, an audible and visual alarm reminder signal will appear.
-Current overload protection - The environmentally friendly R-404A/R-507 coolant can prevent environmental pollution.
- The keyboard can prevent being splashed by shower gel.