Intelligent display control instrument
l Compatible input21Signal types: thermistor, thermocouple, standard voltage, standard current, Haofu, remote pressure gauge resistance, etc
l The zero point display value, slow point display value, transmission output ratio range, and decimal point position of the sensor can be freely set
l Multi level digital filtering selection effectively filters out interference and eliminates non critical skip words
l Realize alarm, control output, loose output, peak hold display, peak transmission output
1 Main technical indicators:
u Measurement of North Korea shows: “1----”Or“-1---”
u Measurement speed:3order/second
u Measurement accuracy: (25℃)±0.5%FS≤150ppm
u Transmission output progress: (25℃)0.5%FS IRL≤250ΩVRL≥500K
u Distribution voltage of transmitter:DC22V~28V(Maximum short-circuit current ≤35mA)
u Relay contact capacity:AC 220V/3A
u Relay contact life:100000order
u Working environment: Temperature0~+50Celsius relative humidity ≤85%RH
u Working power supply: (5W)AC220V 50Hz
u Appearance and installation hole dimensions (see table below)
model |
Digital tube size |
External dimensions(mm) |
Dimension(mm) |
|
Upper |
Bottom row |
|||
48*48 |
0.36” |
0.36” |
48x48x108square |
45x45 |
48*96 |
0.39” |
0.36” |
48x96x80vertical |
45x91 |
96*48 |
0.52” |
0.36” |
96x48x80horizontal |
91x45 |
72*72 |
0.52” |
0.36” |
72x72x104square |
68x68 |
96*96 |
0.80” |
0.56” |
96x96x80square |
91x91 |
80*160 |
0.52” |
0.40” |
80x160x93vertical |
76x152 |
160*80 |
0.80” |
0.40” |
160x80x93horizontal |
152x76 |
2、 Model Description
III Instrument terminal diagram

4 Panel description (to96*48Taking the panel as an example)
① indicator light:AL1Relay indicator light (lit when there is output)
AL2Relay indicator light (lit when there is output)
OUTThe indicator light is on,SVwindow displayAL1ALARM VALUE
AT/MThe indicator light is on,SVwindow displayAL2ALARM VALUE
AT/M+OUTThe indicator lights are on simultaneously,SVwindow displayAL2ALARM VALUE
② Add key: set the status to modify the numerical value by adding one, hold down to scroll by adding one
③ Minus button: Set the state to modify the value by subtracting one, press and hold to scroll by subtracting one
②+③ Please press and hold the shift key for three seconds to eliminate the previous peak value, and use the current measurement value as the peak value
④ Shift key: set the status to blink, move the cursor to the right by one position, or select the parameter with the measurement status leftSVWindow switching display content usage
⑤ Set button: Set the status to save data or parameters. Select button for measurement status. Press to enter password input status
⑥ Measurement value(PV)Display Window
⑦ (SV)Display window:
5 Parameter Setting Instructions
(1) Parameter setting; flow chart
E
Set key points
pressSET Enter the setting state
use>、︿and﹀ Enter password and parameter value settings
pressSET confirm
Use the parameter down selection keySETOr parameter up selection key>Select new parameters
(outside1)Sensor input signal type and(Sn)Code correspondence table
code |
Sensor type and measurement range |
code |
Sensor type and measurement range |
0 |
SType thermocouple0~1600℃ |
12 |
DC 0~10VStandard signal (ordering) |
1 |
RType thermocouple0~1600℃ |
13 |
DC 0~10mAstandard signal |
2 |
BType thermocouple200~1800℃ |
14 |
DC 0~20mAstandard signal |
3 |
KType thermocouple0~1300℃ |
15 |
DC 4~20mAstandard signal |
4 |
NType thermocouple0~1300℃ |
16 |
DCMillivolt signal0~100mV |
5 |
EType thermocouple-200~+850℃ |
17 |
Resistance signal0~400Ω |
6 |
JType thermocouple0~650℃ |
18 |
|
7 |
TType thermocouple-200~+400℃ |
19 |
DC 0~5VSignal open |
8 |
Pt100thermal resistance-199~+600℃ |
20 |
DC 1~5VSignal open |
9 |
Cu50thermal resistance-50~+150℃ |
21 |
DC 0~10mASignal open |
10 |
DC 0~5Vstandard signal |
22 |
DC 4~10mASignal open |
11 |
DC 1~5Vstandard signal |
23 |
|
(2) Sensor parameters (entry method, press)SET Afterwards, enter the password555)
Parameter prompt |
Parameter |
Parameter function |
Options or Setting Range |
Factory value |
notes |
SN |
SN |
Input signal selection |
0~22 |
3 |
pour1 |
DOT |
DOT |
decimal place |
0~3 |
1 |
pour2 |
PVL |
PVL |
Zero point display value |
-1999~9999 |
0.0 |
pour3 |
PVH |
PVH |
Full point display value |
-1999~9999 |
500.0 |
pour4 |
PV |
PV |
Zero point correction value |
-100~100 |
0.0 |
pour5 |
K1 |
K1 |
Display magnification factor |
0.100~9.999 |
1.000 |
pour6 |
INPL |
INPL |
Non standard signal zero point |
0~400 |
0 |
pour7 |
INPH |
INPH |
Non standard signal full point |
0~400 |
100 |
pour8 |
FILT |
FILT |
Digital filtering coefficient |
0.100~9.999 |
0.100 |
pour9 |
DISP |
DISP |
SVWindow controller |
0000~1113 |
1113 |
pour10 |
u Sensor parameter function description
pour1.(Sn)Set the corresponding code based on the sensor model. See (Table)1)↑
pour2.(dot)Set the decimal point position of the measured value, and the parameters that change with the decimal point are as followsPVL、PVH、OBL、OBH、PbIA、AL1、HAL1、AL2、HAL2
pour3.(PvL)Set the corresponding display value when the sensor has zero input
pour4.(PvH)Set the corresponding display value when the sensor is fully input
pour5.(Pb)Used to correct the zero point error of the sensor, the relationship with the displayed value is as follows: current measurement current value=Actual measured display value*K1+Pb
pour6.(K1)Resignation is used to correct the slow point error of the sensor, and its relationship with the displayed value is as follows: the current measured display value=Actual measured display value*K1+Pb
pour7.(InPL)Set the minimum value of the input signal only whenSn=16perhaps17It needs to be set only when a millivolt signal or resistance signal is input.
pour8.(InPH)Set the maximum value of the input signal only whenSn=16perhaps17It needs to be set only when a millivolt signal or resistance signal is input. Peijie's remote transmission pressure gauge0~375Set Ω input as an example:InPH=375,InPL=0
pour9.(FILT)The larger the filtering coefficient, the more stable the display, and then it becomes larger.
pour10.(DISP)Set the instrument to display in the measuring state againSVshow contents
Thousand positions:0Prohibit displaying measurement peak values 1Allow display of measurement peak values
Hundreds of people:0Prohibit displayAL2ALARM VALUE1Allow displayAL2ALARM VALUE 2Allow and modifyAL2ALARM VALUE
Ten people:0Prohibit displayAL1ALARM VALUE1Allow displayAL1ALARM VALUE2Allow and modifyAL1ALARM VALUE
everybody:3Power on display measurement peak value 2Power on displayAL2set value1Power on displayAL1set value
(3) Transmission parameters (entry method, pressSET Afterwards, enter the password800)
Parameter prompt |
Parameter |
Parameter function |
Options or Setting Range |
Factory value |
notes |
Outy |
Outy |
Transmission output type |
0~3 |
2 |
pour11 |
Obl |
obL |
Zero point of transmission output |
-1999~9999 |
0.0 |
pour12 |
Obh |
obH |
Transmission output full point |
-1999~9999 |
500.0 |
pour13 |
Peak |
PEAK |
Peak transmission |
0~1 |
0 |
pour14 |
u Explanation of Transmission Parameter Function
pour11(outy):1do0~10mAOutput;2do4~20mA;3do0~20mA.
pour12(obL)Set the measurement value corresponding to the zero point of the transmission output.
When settingobLgreater thanobH, can display inverse ratio transmission20~4mA.
pour13(obH):Set the measurement value corresponding to the output slow point for a hundred years.
pour14(PEAK):PEAK=0When, use the measured value as the transmission output.
PEAK=1At this time, the peak value is used as the transmission output.
(4) Alarm parameters (entry method, press)SET input100)
Parameter prompt |
Parameter |
Parameter function |
Options or Setting Range |
Factory value |
notes |
PAL1 |
PAL1 |
Alarm function selection |
0~2 |
1 |
picture1 |
Al1 |
AL1 |
call the police1set value |
-1999~9999 |
90.0 |
|
HAL1 |
HAL1 |
return difference1set value |
0~9999 |
0.5 |
|
Pal2 |
PAL2 |
Alarm function selection |
0~2 |
2 |
|
AL2 |
AL2 |
call the police2set value |
-1999~9999 |
70.0 |
|
HAL2 |
HAL2 |
return difference2set value |
0~9999 |
0.5 |
|
D1 |
D1 |
First alarm delay |
0~100S |
0 |
|
D2 |
D2 |
Second alarm delay |
0~100S |
0 |
u Alarm Function Description
PAL1/PAL2Alarm function, functionality2In the middle, set as00The detailed instructions for canceling the alarm are shown in the following figure:
Over the line alarm |
Offline alarm |
equalPV≥AL1Time alarm |
equalPV≤AL2Time alarm |
equalPV<(AL1-HAL1)When the alarm is lifted |
equalPV>(AL2+HAL2)Instant alarm contact |
(AL1=300,HAL1=1) |
(AL1=200,HAL2=1) |
|
|
PAL1=1:Over limit police |
PAL2=2:Lower limit alarm |
VI Application examples
Example: The user needs to detect the temperature of the heating furnace and requires a temperature measurement range of0℃~500℃, when the furnace temperature is higher than300When the temperature is below ℃, an alarm will be triggered online200At ℃, the lower limit alarm will be triggered and will be activated0~500℃ becomes4~20mALoose output, the system power supply isAC220VThe size of the instrument opening is91x45(mm).
1. Sensor selection: SelectKType thermocouple
2. Instrument selection: Instrument selectionXMT112B-AIntelligent digital display control
3. Sensor wiring:KType thermocouple input terminal connection1Number and2name
4. Parameter setting:
1) Sensor parameters (entry method, press)SET Afterwards, enter the password555)
Input signal selectionSn=3(K:0~1300℃)
decimal placedot=0(Set the display resolution to1℃)
Zero point correction valuePb=0
Display magnification factorK1=1.000(1compare1Display)
Digital filtering coefficientFILtCan be set according to on-site interference as appropriate
Press and hold after setting upSET key3Second, return to measurement status
2) Loosening parameters (entry method, pressSTE Afterwards, enter the password800)
Loose output selectionOuty=2(4~20mALoose output)
Loosening output zero pointobL=0(Set temperature to loosen output zero point)
Loose output full pointobH=500(Set temperature to loosen and output at full point)
Peak looseningPEAK=0(Using measured values as loose output)
Press and hold after setting upSET key3Second, return to measurement status
3) Alarm parameters (entry method, press)SETAfterwards, enter the password100)
call the police1Function selectionPAL1=1(Online alarm)
call the police1set valueAL1=300(Set online alarm value)
call the police1set valueHAL1=1(Setting)1℃ hysteresis)
call the police2Function selectionPAL2=2(Offline alarm)
call the police2set valueAL2=200(Set lower limit alarm value)
call the police2set valueHAL2=1(Setting)1℃ hysteresis)
Press and hold after setting upSET key3Second, return to measurement status