Suzhou Zhenghe Testing Equipment Co., Ltd
Home>Products>Dust free purification type constant temperature and humidity air conditioner
Product Groups
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    15950088616
  • Address
    No. 82 Qingsha Road, Luzhi Town, Wuzhong District, Suzhou City, Jiangsu Province
Contact Now
Dust free purification type constant temperature and humidity air conditioner
Dust free purification type constant temperature and humidity air conditioner
Product details

Product Overview:

Modern scientific experiments require indoor air cleanliness to meet the requirements of precision machining, product miniaturization, high purity, and high reliability of products. Obviously, if particles enter the product, it may cause obstacles, short circuits, impurity sources, and potential defects. Therefore, clean technology has become one of the symbols of modernization in scientific experiments and production activities.

ZH. instrument direct expansion purification constant temperature and humidity air conditioner is particularly suitable for places that require air cleanliness and air conditioning, such as research laboratories, biotechnology, pharmaceuticals, chemical industry, food, electronics, precision machinery, etc., such as temperature 18-28 ℃ accuracy ± 2 ℃, humidity 45-70% accuracy ± 5% RH, purification level 10000 to 100.

恒温恒湿机使用地.png

Characteristics of the product.

Applied to cleaning engineering, carefully designed according to EN1886 and VDI6022 standards.

VDI6022 standard.


◎ Applicable occasions: clean constant temperature and humidity room

◎ Temperature range and accuracy:8~28℃±2℃

◎ Humidity range and accuracy:45~70%±5%

◎ Filtration efficiency:G4+F7


Regarding the following points, requirements are proposed for air conditioning units that meet cleaning requirements.

◎ Plan.

Design of air conditioning unit.

◎ Operation.

◎ Service.

◎ Maintenance.

According to the highest technical standards.

... represents high-quality cleaning standards and provides a safe plan.

It can prevent the occurrence of problems.

The ZH. instrument air conditioning cabinet fully meets these requirements.

Technical Specifications and Parameters of Direct Expansion Purification Constant Temperature and Humidity Air Conditioner

Technical parameters of air-cooled direct expansion type

type nameMode

AC-FP8

AC-FP10

AC-FP12

AC-FP16

AC-FP20

AC-F30

AC-FP40

AC-FP50

Refrigeration capacity

KW

21.4

27.2

33.2

42.8

54.4

83.6

116.2

138

sensible cooling capacity

KW

18.8

23.9

29.1

37.6

47.8

73.4

102

122.9

Heating capacity

KW

9

12

12

15

18

30

36

48

wind measure

m3/h

4700

6000

7200

9500

12000

18000

25000

30000

empty

gas

place

texture

machine

Mixed air initial effect filtration section

air filter

type

Plate type initial efficiency filter

new/Return air valve

type

electric/hand movement

External dimensions

long

mm

700

700

700

700

700

700

750

850

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

150

180

180

200

250

250

320

350

Cooling and reheating section

evaporator

type

Copper tube with aluminum sheet, flat sheet

heater

type

electrical heating/hot water/steam

External dimensions

long

mm

700

700

700

700

800

800

800

800

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

250

300

300

350

400

450

500

600

Humidifier section

type


Electrode type

Humidification amount

Kg/h


5

5

13

13

13

13

13

13

Input power

KW


3.4

3.4

9.8

9.8

9.8

9.8

9.8

9.8

Medium efficiency filtration section

air filter

type

Bag type medium efficiency filter

External dimensions

long

mm

600

600

600

600

600

600

600

600

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

120

130

130

160

180

180

250

250

Air supply section

fan

type

Belt dragging type

External residual pressure

pa

400~900

fan power

kW

3

4.5

4.5

7.5

11

11

15

18.5

External dimensions

long

mm

700

700

700

700

900

900

1200

1500

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

250

300

320

350

400

400

500

700

Host segment

compressor

type


Fully enclosed vortex type

Motor Power

KW

6.2

7.8

9.4

12.4

15.6

23.6

32.3

49.2

energy regulation

%

0-50%-100%

Safety Control

tall/Low voltage protection,compressor/Fan overcurrent protection,Reverse phase protection

refrigerant

type

R22/R134a/R407c

External dimensions

long

mm

700

700

700

700

700

750

750

850

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

300

400

450

500

700

800

1000

1100

Outdoor

fan

Air volume

m3/h

8500

13500

13500

17000

21500

41000

50000

60000

Motor Power

KW

0.4

0.6

0.6

0.8

1.4

2.9

6

8.8

heat exchanger

type

Copper tube with aluminum sheet, flat sheet

Windward area

m2

1.04

1.64

2.1

2.66

3.37

5.06

5.4

8.42

Row number

arrange

4

3

3

3

3

3

4

3

size

long

mm

1200

1760

1760

1760

1760

2280

2280

3500

wide

mm

450

930

930

930

930

1200

1200

1200

tall

mm

1100

700

850

1050

1250

1430

1430

1430

weight

Kg

80

120

140

160

210

320

410

500

Electrical parameters

power supply


380V/3P/50HzThree-phase four-wire

Operating power

KW

18.6

24.9

26.5

35.7

46.0

67.5

89.3

124.5

wiring(Copper core)

mm2

10

10

10

16

25

25

35

50

Unit takeover size

Outer diameter of trachea

mm

16

19

19

22

22

28

28

35

Outer diameter of liquid tube

mm

12

12

12

16

16

19

19

22

Humidifier water replenishment pipe

DN

15

15

15

15

15

15

15

15

Condensate drainage pipe

DN

25

25

25

32

32

40

40

40

Note: The customized cooling capacity is based on an indoor dry wet bulb temperature of 24 ℃, relative humidity of 50%, and an outdoor inlet dry wet bulb temperature of 32 ℃.

 

Water cooled direct expansion technical parameters

modelMode

AC-SP8

AC-SP10

AC-SP12

AC-SP16

AC-SP20

AC-SP30

AC-SP40

AC-SP50

Refrigeration capacity

KW

21.4

27.2

33.2

42.8

54.4

83.6

116.2

138

sensible cooling capacity

KW

18.8

23.9

29.1

37.6

47.8

73.4

102

122.9

Heating capacity

KW

9

12

12

15

18

30

36

48

wind measure

m3/h

4700

6000

7200

9500

12000

18000

25000

30000

Mixed air initial effect filtration section

air filter

type

Plate type initial efficiency filter

new/Return air valve

type

electric/hand movement

External dimensions

long

mm

700

700

700

700

700

700

750

850

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

150

180

180

200

250

250

320

350

Cooling and reheating section

evaporator

type

Copper tube with aluminum sheet, flat sheet

heater

type

electrical heating/hot water/steam

External dimensions

long

mm

700

700

700

700

800

800

800

800

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

250

300

300

350

400

450

500

600

Humidifier section

type


Electrode type

Humidification amount

Kg/h


5

5

13

13

13

13

13

13

Input power

KW


3.4

3.4

9.8

9.8

9.8

9.8

9.8

9.8

Medium efficiency filtration section

air filter

type

Bag type medium efficiency filter

External dimensions

long

mm

600

600

600

600

600

600

600

600

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

120

130

130

160

180

180

250

250

Air supply section

fan

type

Belt dragging type

External residual pressure

pa

400~900

fan power

kW

3

4.5

4.5

7.5

11

11

15

18.5

External dimensions

long

mm

700

700

700

700

900

900

1200

1500

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

250

300

320

350

400

400

500

700

Host segment

compressor

type


Fully enclosed vortex type

Motor Power

KW

6.2

7.8

9.4

12.4

15.6

23.6

32.3

49.2

energy regulation

%

0-50%-100%

water-cooled condenser

form

Shell and tube type/telescopic/plate heat exchanger

discharge

m3/h

4.28

5.44

6.64

8.56

10.88

16.72

23.24

27.60

Water pressure drop

Kpa

59

62

48

59

45

60

58

50

Safety Control

tall/Low voltage protection,compressor/Fan overcurrent protection,Reverse phase protection,Cut off water protection

refrigerant

type

R22/R134a/R407c

External dimensions

long

mm

700

700

700

700

700

750

750

850

wide

mm

1100

1300

1300

1500

1800

1800

2200

2200

tall

mm

1100

1300

1300

1300

1500

1500

1700

1700

weight

kg

300

400

450

500

700

800

1000

1100

Electrical parameters

power supply


380V/3P/50HzThree-phase four-wire

Operating power

KW

18.2

24.3

25.9

34.9

44.6

64.6

83.3

115.7

wiring(Copper core)

mm2

10

10

10

16

25

25

35

50

Unit takeover size

Cooling water inlet and outlet pipe

DN

40

40

50

50

50

65

80

80

Humidifier water replenishment pipe

DN

15

15

15

15

15

15

15

15

Condensate drainage pipe

DN

25

25

25

32

32

40

40

40

Note:Customized cooling capacity based onIndoor dry wet bulb temperature 24 ℃, relative humidity 50%, condenserInlet temperature 30 ℃, outlet temperature 35 ℃.

 

Unit external structure

Note: The unit can be designed in two types according to customer needs: roof integrated and split type;

 

describe
1. The operating power in the table refers to the maximum operating load;
2The total input power is determined based on the quantity and method of heating and humidification;
3Heating methods are optional, including electric heating, hot water heating, steam heating, and the heating amount can be selected;
4Humidification mode is optional, wet film humidification, dry steam humidification, electrode humidification, high-pressure spray humidification, and humidification amount is optional;
5The functional sections of the direct expansion purified air handling unit can be selected, including mixing section, return air section, primary filtration section, cooling section, heating section, humidification section, fan section, intermediate flow equalization section, noise reduction section, and medium efficiency filtration section(inferior)Efficient filtration section, heat recovery section, air supply section, etc;
6Due to continuous technological innovation and improvement by the manufacturer, changes in size and materials are subject to change without prior notice. Special models and the latest technical data are available upon request.




A. Controller.

◎ Touchscreen PLC controller, easy to operate and manage

The working status of all systems is displayed in text and graphic form on the control panel, which is clear at a glance and easy to understand

The controller can operate independently or form an integrated centralized management online

The controller can be built on the surface of the air conditioning unit or set up nearby indoors to monitor the unit on site.

B. Compressor.

Copeland Valley Wheel's efficient and reliable fully enclosed eddy current refrigeration compressor from the United States

◎ It has the advantages of high volumetric efficiency (more than 10% higher than traditional piston compressors), fewer moving parts, low vibration, low noise, and strong hydraulic resistance

Efficiency: According to ARI standards, the coefficient of performance (COP) exceeds 3.35W/W

◎ Low noise: The new design eliminates vibration of the intake and exhaust valves, significantly reducing noise

Safe and reliable: operates continuously, tolerates liquid reflux, and has an extremely low failure rate.

C. Humidifier.

◎ Italian Carl efficient humidification system

Fuzzy control technology: Control the humidification amount through humidification current and automatically monitor the water conductivity

◎ AFS control technology: mesh humidification electrode, large contact surface, foam prevention, automatic drainage, automatic cleaning

◎ Convenient maintenance technology: detachable humidifying body, tank made of fireproof material, reusable

The immersion electrode humidification system can automatically and accurately control various functions through a microprocessor, and automatically adapt to the water quality in different regions.

ventilator.

Efficient and low-noise centrifugal fans, available in various forms such as forward multi wing, backward circular arc, and backward wing

Select computer software based on air volume, air pressure, noise, and power, and correctly combine high-quality motors

◎ Use a fan with drive or a direct drive fan

◎ Design for low RPM and high torque

Minimize operating noise to the greatest extent possible

◎ It has a minimum lifespan of 100000 hours of operation.

D. Filter.

The filtering material should not contribute to the growth of microorganisms

◎ Only fully sealed gaskets can be used

Even in humid environments, the mechanical properties of materials must be sufficiently stable

◎ Filter differential pressure control is equipped with visual inspection or electronic control as standard configuration.

E. Evaporator.

The direct expansion refrigeration coil adopts high-purity seamless copper pipes and aluminum interference plates, which are tightly combined with the copper pipes and aluminum plates through mechanical expansion pipes to achieve the best heat transfer effect

The dual advantages of dual sine wave honeycomb fins and window fins ensure high heat exchange coefficient while having low air resistance

Honeycomb fins enhance airflow interference through intermittent concave convex stretching processing structures. The fins have smaller cut cross-sections, reducing the accumulation and retention of dust in the air on the fins

After long-term operation, the refrigeration coil still has high heat transfer efficiency.

F. The structure of the box.

◎ Patent box structure, making the inner surface completely smooth, without cutting edges or grooves

The box is not prone to condensation (the insulation performance of the box reaches the European EN1886-1997T2/TB2 level)

◎ Low air leakage rate (the air leakage rate of the box meets the A-level requirement of EN1886-1997 standard, which is equivalent to a clean air conditioning air leakage rate of less than 1% according to GB/T14294-93 standard)

◎ High quality galvanized steel plate, stainless steel plate and cold formed steel are used, with strong aging resistance

To avoid surface corrosion of the panel, galvanized panels with unprotected cutting edges are not used

The door and panel seals are made of high-density, non aging materials

All parts should be easy to inspect, equipped with necessary lighting equipment, inspection doors, and observation windows.


Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!