Product Overview:
Modern scientific experiments require indoor air cleanliness to meet the requirements of precision machining, product miniaturization, high purity, and high reliability of products. Obviously, if particles enter the product, it may cause obstacles, short circuits, impurity sources, and potential defects. Therefore, clean technology has become one of the symbols of modernization in scientific experiments and production activities.
ZH. instrument direct expansion purification constant temperature and humidity air conditioner is particularly suitable for places that require air cleanliness and air conditioning, such as research laboratories, biotechnology, pharmaceuticals, chemical industry, food, electronics, precision machinery, etc., such as temperature 18-28 ℃ accuracy ± 2 ℃, humidity 45-70% accuracy ± 5% RH, purification level 10000 to 100.
Characteristics of the product.
Applied to cleaning engineering, carefully designed according to EN1886 and VDI6022 standards.
VDI6022 standard.
◎ Applicable occasions: clean constant temperature and humidity room | |
◎ Temperature range and accuracy:8~28℃±2℃ | |
◎ Humidity range and accuracy:45~70%±5% | |
◎ Filtration efficiency:G4+F7 |
Regarding the following points, requirements are proposed for air conditioning units that meet cleaning requirements.
◎ Plan.
Design of air conditioning unit.
◎ Operation.
◎ Service.
◎ Maintenance.
According to the highest technical standards.
... represents high-quality cleaning standards and provides a safe plan.
It can prevent the occurrence of problems.
The ZH. instrument air conditioning cabinet fully meets these requirements.
Technical Specifications and Parameters of Direct Expansion Purification Constant Temperature and Humidity Air Conditioner |
Technical parameters of air-cooled direct expansion type
type nameMode |
AC-FP8 |
AC-FP10 |
AC-FP12 |
AC-FP16 |
AC-FP20 |
AC-F30 |
AC-FP40 |
AC-FP50 |
||||
Refrigeration capacity |
KW |
21.4 |
27.2 |
33.2 |
42.8 |
54.4 |
83.6 |
116.2 |
138 |
|||
sensible cooling capacity |
KW |
18.8 |
23.9 |
29.1 |
37.6 |
47.8 |
73.4 |
102 |
122.9 |
|||
Heating capacity |
KW |
9 |
12 |
12 |
15 |
18 |
30 |
36 |
48 |
|||
wind measure |
m3/h |
4700 |
6000 |
7200 |
9500 |
12000 |
18000 |
25000 |
30000 |
|||
empty gas place texture machine |
Mixed air initial effect filtration section |
air filter |
type |
Plate type initial efficiency filter |
||||||||
new/Return air valve |
type |
electric/hand movement |
||||||||||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
700 |
700 |
750 |
850 |
||
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
|||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
|||
weight |
kg |
150 |
180 |
180 |
200 |
250 |
250 |
320 |
350 |
|||
Cooling and reheating section |
evaporator |
type |
Copper tube with aluminum sheet, flat sheet |
|||||||||
heater |
type |
electrical heating/hot water/steam |
||||||||||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
800 |
800 |
800 |
800 |
||
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
|||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
|||
weight |
kg |
250 |
300 |
300 |
350 |
400 |
450 |
500 |
600 |
|||
Humidifier section |
type |
Electrode type |
||||||||||
Humidification amount |
Kg/h |
5 |
5 |
13 |
13 |
13 |
13 |
13 |
13 |
|||
Input power |
KW |
3.4 |
3.4 |
9.8 |
9.8 |
9.8 |
9.8 |
9.8 |
9.8 |
|||
Medium efficiency filtration section |
air filter |
type |
Bag type medium efficiency filter |
|||||||||
External dimensions |
long |
mm |
600 |
600 |
600 |
600 |
600 |
600 |
600 |
600 |
||
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
|||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
|||
weight |
kg |
120 |
130 |
130 |
160 |
180 |
180 |
250 |
250 |
|||
Air supply section |
fan |
type |
Belt dragging type |
|||||||||
External residual pressure |
pa |
400~900 |
||||||||||
fan power |
kW |
3 |
4.5 |
4.5 |
7.5 |
11 |
11 |
15 |
18.5 |
|||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
900 |
900 |
1200 |
1500 |
||
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
|||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
|||
weight |
kg |
250 |
300 |
320 |
350 |
400 |
400 |
500 |
700 |
|||
Host segment |
compressor |
type |
Fully enclosed vortex type |
|||||||||
Motor Power |
KW |
6.2 |
7.8 |
9.4 |
12.4 |
15.6 |
23.6 |
32.3 |
49.2 |
|||
energy regulation |
% |
0-50%-100% |
||||||||||
Safety Control |
tall/Low voltage protection,compressor/Fan overcurrent protection,Reverse phase protection |
|||||||||||
refrigerant |
type |
R22/R134a/R407c |
||||||||||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
700 |
750 |
750 |
850 |
||
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
|||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
|||
weight |
kg |
300 |
400 |
450 |
500 |
700 |
800 |
1000 |
1100 |
|||
Outdoor |
fan |
Air volume |
m3/h |
8500 |
13500 |
13500 |
17000 |
21500 |
41000 |
50000 |
60000 |
|
Motor Power |
KW |
0.4 |
0.6 |
0.6 |
0.8 |
1.4 |
2.9 |
6 |
8.8 |
|||
heat exchanger |
type |
Copper tube with aluminum sheet, flat sheet |
||||||||||
Windward area |
m2 |
1.04 |
1.64 |
2.1 |
2.66 |
3.37 |
5.06 |
5.4 |
8.42 |
|||
Row number |
arrange |
4 |
3 |
3 |
3 |
3 |
3 |
4 |
3 |
|||
size |
long |
mm |
1200 |
1760 |
1760 |
1760 |
1760 |
2280 |
2280 |
3500 |
||
wide |
mm |
450 |
930 |
930 |
930 |
930 |
1200 |
1200 |
1200 |
|||
tall |
mm |
1100 |
700 |
850 |
1050 |
1250 |
1430 |
1430 |
1430 |
|||
weight |
Kg |
80 |
120 |
140 |
160 |
210 |
320 |
410 |
500 |
|||
Electrical parameters |
power supply |
380V/3P/50HzThree-phase four-wire |
||||||||||
Operating power |
KW |
18.6 |
24.9 |
26.5 |
35.7 |
46.0 |
67.5 |
89.3 |
124.5 |
|||
wiring(Copper core) |
mm2 |
10 |
10 |
10 |
16 |
25 |
25 |
35 |
50 |
|||
Unit takeover size |
Outer diameter of trachea |
mm |
16 |
19 |
19 |
22 |
22 |
28 |
28 |
35 |
||
Outer diameter of liquid tube |
mm |
12 |
12 |
12 |
16 |
16 |
19 |
19 |
22 |
|||
Humidifier water replenishment pipe |
DN |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
|||
Condensate drainage pipe |
DN |
25 |
25 |
25 |
32 |
32 |
40 |
40 |
40 |
Note: The customized cooling capacity is based on an indoor dry wet bulb temperature of 24 ℃, relative humidity of 50%, and an outdoor inlet dry wet bulb temperature of 32 ℃.
Water cooled direct expansion technical parameters
modelMode |
AC-SP8 |
AC-SP10 |
AC-SP12 |
AC-SP16 |
AC-SP20 |
AC-SP30 |
AC-SP40 |
AC-SP50 |
|||
Refrigeration capacity |
KW |
21.4 |
27.2 |
33.2 |
42.8 |
54.4 |
83.6 |
116.2 |
138 |
||
sensible cooling capacity |
KW |
18.8 |
23.9 |
29.1 |
37.6 |
47.8 |
73.4 |
102 |
122.9 |
||
Heating capacity |
KW |
9 |
12 |
12 |
15 |
18 |
30 |
36 |
48 |
||
wind measure |
m3/h |
4700 |
6000 |
7200 |
9500 |
12000 |
18000 |
25000 |
30000 |
||
Mixed air initial effect filtration section |
air filter |
type |
Plate type initial efficiency filter |
||||||||
new/Return air valve |
type |
electric/hand movement |
|||||||||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
700 |
700 |
750 |
850 |
|
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
||
weight |
kg |
150 |
180 |
180 |
200 |
250 |
250 |
320 |
350 |
||
Cooling and reheating section |
evaporator |
type |
Copper tube with aluminum sheet, flat sheet |
||||||||
heater |
type |
electrical heating/hot water/steam |
|||||||||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
800 |
800 |
800 |
800 |
|
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
||
weight |
kg |
250 |
300 |
300 |
350 |
400 |
450 |
500 |
600 |
||
Humidifier section |
type |
Electrode type |
|||||||||
Humidification amount |
Kg/h |
5 |
5 |
13 |
13 |
13 |
13 |
13 |
13 |
||
Input power |
KW |
3.4 |
3.4 |
9.8 |
9.8 |
9.8 |
9.8 |
9.8 |
9.8 |
||
Medium efficiency filtration section |
air filter |
type |
Bag type medium efficiency filter |
||||||||
External dimensions |
long |
mm |
600 |
600 |
600 |
600 |
600 |
600 |
600 |
600 |
|
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
||
weight |
kg |
120 |
130 |
130 |
160 |
180 |
180 |
250 |
250 |
||
Air supply section |
fan |
type |
Belt dragging type |
||||||||
External residual pressure |
pa |
400~900 |
|||||||||
fan power |
kW |
3 |
4.5 |
4.5 |
7.5 |
11 |
11 |
15 |
18.5 |
||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
900 |
900 |
1200 |
1500 |
|
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
||
weight |
kg |
250 |
300 |
320 |
350 |
400 |
400 |
500 |
700 |
||
Host segment |
compressor |
type |
Fully enclosed vortex type |
||||||||
Motor Power |
KW |
6.2 |
7.8 |
9.4 |
12.4 |
15.6 |
23.6 |
32.3 |
49.2 |
||
energy regulation |
% |
0-50%-100% |
|||||||||
water-cooled condenser |
form |
Shell and tube type/telescopic/plate heat exchanger |
|||||||||
discharge |
m3/h |
4.28 |
5.44 |
6.64 |
8.56 |
10.88 |
16.72 |
23.24 |
27.60 |
||
Water pressure drop |
Kpa |
59 |
62 |
48 |
59 |
45 |
60 |
58 |
50 |
||
Safety Control |
tall/Low voltage protection,compressor/Fan overcurrent protection,Reverse phase protection,Cut off water protection |
||||||||||
refrigerant |
type |
R22/R134a/R407c |
|||||||||
External dimensions |
long |
mm |
700 |
700 |
700 |
700 |
700 |
750 |
750 |
850 |
|
wide |
mm |
1100 |
1300 |
1300 |
1500 |
1800 |
1800 |
2200 |
2200 |
||
tall |
mm |
1100 |
1300 |
1300 |
1300 |
1500 |
1500 |
1700 |
1700 |
||
weight |
kg |
300 |
400 |
450 |
500 |
700 |
800 |
1000 |
1100 |
||
Electrical parameters |
power supply |
380V/3P/50HzThree-phase four-wire |
|||||||||
Operating power |
KW |
18.2 |
24.3 |
25.9 |
34.9 |
44.6 |
64.6 |
83.3 |
115.7 |
||
wiring(Copper core) |
mm2 |
10 |
10 |
10 |
16 |
25 |
25 |
35 |
50 |
||
Unit takeover size |
Cooling water inlet and outlet pipe |
DN |
40 |
40 |
50 |
50 |
50 |
65 |
80 |
80 |
|
Humidifier water replenishment pipe |
DN |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
15 |
||
Condensate drainage pipe |
DN |
25 |
25 |
25 |
32 |
32 |
40 |
40 |
40 |
Note:Customized cooling capacity based on:Indoor dry wet bulb temperature 24 ℃, relative humidity 50%, condenserInlet temperature 30 ℃, outlet temperature 35 ℃.
Unit external structure
Note: The unit can be designed in two types according to customer needs: roof integrated and split type;
describe:
1. The operating power in the table refers to the maximum operating load;
2、The total input power is determined based on the quantity and method of heating and humidification;
3、Heating methods are optional, including electric heating, hot water heating, steam heating, and the heating amount can be selected;
4Humidification mode is optional, wet film humidification, dry steam humidification, electrode humidification, high-pressure spray humidification, and humidification amount is optional;
5The functional sections of the direct expansion purified air handling unit can be selected, including mixing section, return air section, primary filtration section, cooling section, heating section, humidification section, fan section, intermediate flow equalization section, noise reduction section, and medium efficiency filtration section(inferior)Efficient filtration section, heat recovery section, air supply section, etc;
6Due to continuous technological innovation and improvement by the manufacturer, changes in size and materials are subject to change without prior notice. Special models and the latest technical data are available upon request.
A. Controller.
◎ Touchscreen PLC controller, easy to operate and manage
The working status of all systems is displayed in text and graphic form on the control panel, which is clear at a glance and easy to understand
The controller can operate independently or form an integrated centralized management online
The controller can be built on the surface of the air conditioning unit or set up nearby indoors to monitor the unit on site.
B. Compressor.
Copeland Valley Wheel's efficient and reliable fully enclosed eddy current refrigeration compressor from the United States
◎ It has the advantages of high volumetric efficiency (more than 10% higher than traditional piston compressors), fewer moving parts, low vibration, low noise, and strong hydraulic resistance
Efficiency: According to ARI standards, the coefficient of performance (COP) exceeds 3.35W/W
◎ Low noise: The new design eliminates vibration of the intake and exhaust valves, significantly reducing noise
Safe and reliable: operates continuously, tolerates liquid reflux, and has an extremely low failure rate.
C. Humidifier.
◎ Italian Carl efficient humidification system
Fuzzy control technology: Control the humidification amount through humidification current and automatically monitor the water conductivity
◎ AFS control technology: mesh humidification electrode, large contact surface, foam prevention, automatic drainage, automatic cleaning
◎ Convenient maintenance technology: detachable humidifying body, tank made of fireproof material, reusable
The immersion electrode humidification system can automatically and accurately control various functions through a microprocessor, and automatically adapt to the water quality in different regions.
ventilator.
Efficient and low-noise centrifugal fans, available in various forms such as forward multi wing, backward circular arc, and backward wing
Select computer software based on air volume, air pressure, noise, and power, and correctly combine high-quality motors
◎ Use a fan with drive or a direct drive fan
◎ Design for low RPM and high torque
Minimize operating noise to the greatest extent possible
◎ It has a minimum lifespan of 100000 hours of operation.
D. Filter.
The filtering material should not contribute to the growth of microorganisms
◎ Only fully sealed gaskets can be used
Even in humid environments, the mechanical properties of materials must be sufficiently stable
◎ Filter differential pressure control is equipped with visual inspection or electronic control as standard configuration.
E. Evaporator.
The direct expansion refrigeration coil adopts high-purity seamless copper pipes and aluminum interference plates, which are tightly combined with the copper pipes and aluminum plates through mechanical expansion pipes to achieve the best heat transfer effect
The dual advantages of dual sine wave honeycomb fins and window fins ensure high heat exchange coefficient while having low air resistance
Honeycomb fins enhance airflow interference through intermittent concave convex stretching processing structures. The fins have smaller cut cross-sections, reducing the accumulation and retention of dust in the air on the fins
After long-term operation, the refrigeration coil still has high heat transfer efficiency.
F. The structure of the box.
◎ Patent box structure, making the inner surface completely smooth, without cutting edges or grooves
The box is not prone to condensation (the insulation performance of the box reaches the European EN1886-1997T2/TB2 level)
◎ Low air leakage rate (the air leakage rate of the box meets the A-level requirement of EN1886-1997 standard, which is equivalent to a clean air conditioning air leakage rate of less than 1% according to GB/T14294-93 standard)
◎ High quality galvanized steel plate, stainless steel plate and cold formed steel are used, with strong aging resistance
To avoid surface corrosion of the panel, galvanized panels with unprotected cutting edges are not used
The door and panel seals are made of high-density, non aging materials
All parts should be easy to inspect, equipped with necessary lighting equipment, inspection doors, and observation windows.