ECA430A pressure transmitter
Summary: The ECA430A pressure transmitter is used to measure the pressure of gases, liquids, and vapors, and then convert it into a 4-20mADC current s
Product details

summary
ECA430APressure transmitters are used to measure the pressure of gases, liquids, and vapors, and then convert it into a 4-20mADC current signal output. The ECA430A can also communicate with the HART275 handheld device for setting, monitoring, and other purposes.
Functional specifications
output
2-wire system, 4-20mA DC output, digital communication, programmable linear or square root output mode, HART protocol loaded on 4-20mA DC signal.
supply voltage
10.5~42V DC (working state)
(10.5-30V DC intrinsic safety type)
16.4~42V DC (digital communication)
(16.4~30V DC intrinsic safety type)
9.0-32VDC (FF fieldbus communication)
load
0-1335 Ω working state
250-600 Ω digital communication
HART
Communication Distance
Using multi-core twisted pair cables, the maximum communication distance can reach 1.5km, and the communication distance varies depending on the cable type.
Damping time constant
The sum of damping time constants for amplifier components and membrane enclosures. The damping time constant of amplifier components can be adjusted within the range of 0.2 to 64 seconds
ambient temperature
-40~85℃(-40~185°F)
-30-80 ℃ (-22-176 ° F) [with LCD meter head]
Liquid contact temperature
-40~120℃(-40~248°F)
Performance specifications
Reference accuracy for range adjustment (including linearity, hysteresis, and repeatability from zero) ± 0.1%
ECA430APressure transmitters are used to measure the pressure of gases, liquids, and vapors, and then convert it into a 4-20mADC current signal output. The ECA430A can also communicate with the HART275 handheld device for setting, monitoring, and other purposes.
Functional specifications
output
2-wire system, 4-20mA DC output, digital communication, programmable linear or square root output mode, HART protocol loaded on 4-20mA DC signal.
supply voltage
10.5~42V DC (working state)
(10.5-30V DC intrinsic safety type)
16.4~42V DC (digital communication)
(16.4~30V DC intrinsic safety type)
9.0-32VDC (FF fieldbus communication)
load
0-1335 Ω working state
250-600 Ω digital communication
HART
Communication Distance
Using multi-core twisted pair cables, the maximum communication distance can reach 1.5km, and the communication distance varies depending on the cable type.
Damping time constant
The sum of damping time constants for amplifier components and membrane enclosures. The damping time constant of amplifier components can be adjusted within the range of 0.2 to 64 seconds
ambient temperature
-40~85℃(-40~185°F)
-30-80 ℃ (-22-176 ° F) [with LCD meter head]
Liquid contact temperature
-40~120℃(-40~248°F)
Performance specifications
Reference accuracy for range adjustment (including linearity, hysteresis, and repeatability from zero) ± 0.1%
Pressure transmitter 430A series model and specification code table
model
|
specifications
code
|
Explanation
|
reference price
|
notes
|
||
ECA430A
|
|
pressure transmitter
|
|
|
||
Conveying signals
|
E
D |
4~20mA, HART protocol digital communication
4~20mA |
|
|
||
Measurement range
(Capsule) |
A
B |
0.03~3Mpa
0.14~14Mpa |
|
|
||
Material of the liquid receiving part
|
|
essence
|
Capsule
|
Exhaust screw
|
|
|
S
|
SCS14A
|
SUS316L
|
SUS316
|
|||
pipe connection
|
2
1 0 |
With M20×1.5Process connector
belt½NPTInternal thread process joint No process joint (on capacitive flange)¼NPTInternal thread) |
|
|
||
Material of bolts and nuts
|
A
B C |
SCM435
SUS630 SUH660 |
LMaximum working pressure of membrane box
3MPa(30kgf/cm2) |
M、 H membrane box
Maximum working pressure 14MPa(140kgf/cm2) |
|
|
Installation method
|
2
|
Vertical installation, high voltage on the right, process connected to the top
|
|
|
||
3
|
Vertical installation, high voltage on the right, process connected at the bottom
|
|||||
6
|
Vertical installation, high voltage on the left, process connected to the top
|
|||||
7
|
Vertical installation, high pressure on the left side, process connected at the bottom
|
|||||
8
|
Horizontal installation, high voltage on the right side
|
|||||
9
|
Horizontal installation, high voltage on the left side
|
|||||
electrical interface
|
5
|
G½Internal screw, 2 wiring ports with blind plugs
|
|
|
||
Display header
|
D
E N |
Digital header
Pointer header (No header) |
|
|
||
2inchPipe installation bracket
|
A
|
SECCFlat bracket
|
|
|
||
B
|
SUC304Flat bracket
|
|||||
C
|
SECC LType bracket
|
|||||
D
|
SUS304 LType bracket
|
|||||
N
|
No installation bracket
|
|||||
Additional selection code
|
|
/Additional specifications
|
|
|
External dimensions
Vertical piping installation method (installation code 2. For codes 3, 6, or 7, see comments)
Horizontal piping installation method (installation code 8, see comments for code 9)
Note: 1. When selected for installation as 6, 7, or 9, the high and low voltage sides are opposite to the above figure;
2. When selecting installation as 3 or 7, the process of installing the bracket is opposite to the one shown in the above figure.
Terminal side wiring diagram
Wiring terminals
SUPPLY± | Power supply and output terminal |
CHECK± | External indicator (ammeter) terminal |
╧ | Grounding terminal |
Note: The impedance when using an external indicator or measuring timer should be less than 10Ω