Jinhu Ouwang Technology Co., Ltd
Home>Products>ECA430A pressure transmitter
ECA430A pressure transmitter
Summary: The ECA430A pressure transmitter is used to measure the pressure of gases, liquids, and vapors, and then convert it into a 4-20mADC current s
Product details
summary
ECA430APressure transmitters are used to measure the pressure of gases, liquids, and vapors, and then convert it into a 4-20mADC current signal output. The ECA430A can also communicate with the HART275 handheld device for setting, monitoring, and other purposes.
Functional specifications
output
2-wire system, 4-20mA DC output, digital communication, programmable linear or square root output mode, HART protocol loaded on 4-20mA DC signal.
supply voltage
10.5~42V DC (working state)
(10.5-30V DC intrinsic safety type)
16.4~42V DC (digital communication)
(16.4~30V DC intrinsic safety type)
9.0-32VDC (FF fieldbus communication)
load
0-1335 Ω working state
250-600 Ω digital communication
HART
Communication Distance
Using multi-core twisted pair cables, the maximum communication distance can reach 1.5km, and the communication distance varies depending on the cable type.
Damping time constant
The sum of damping time constants for amplifier components and membrane enclosures. The damping time constant of amplifier components can be adjusted within the range of 0.2 to 64 seconds
ambient temperature
-40~85℃(-40~185°F)
-30-80 ℃ (-22-176 ° F) [with LCD meter head]
Liquid contact temperature
-40~120℃(-40~248°F)

Performance specifications
Reference accuracy for range adjustment (including linearity, hysteresis, and repeatability from zero) ± 0.1%
Pressure transmitter 430A series model and specification code table
 
model
specifications
code
Explanation
reference price
notes
ECA430A
 
pressure transmitter
 
 
Conveying signals
E
D
4~20mA, HART protocol digital communication
4~20mA
 
 
Measurement range
(Capsule)
A
B
0.03~3Mpa
0.14~14Mpa
 
 
Material of the liquid receiving part
 
essence
Capsule
Exhaust screw
 
 
S
SCS14A
SUS316L
SUS316
pipe connection
2
1
0
With M20×1.5Process connector
belt
½NPTInternal thread process joint
No process joint (on capacitive flange)
¼NPTInternal thread)
 
 
Material of bolts and nuts
A
B
C
SCM435
SUS630
SUH660
LMaximum working pressure of membrane box
3MPa(30kgf/cm2)
M、 H membrane box
Maximum working pressure
14MPa(140kgf/cm2)
 
 
Installation method
2
Vertical installation, high voltage on the right, process connected to the top
 
 
3
Vertical installation, high voltage on the right, process connected at the bottom
6
Vertical installation, high voltage on the left, process connected to the top
7
Vertical installation, high pressure on the left side, process connected at the bottom
8
Horizontal installation, high voltage on the right side
9
Horizontal installation, high voltage on the left side
electrical interface
5
G½Internal screw, 2 wiring ports with blind plugs
 
 
Display header
D
E
N
Digital header
Pointer header
(No header)
 
 
2inchPipe installation bracket
A
SECCFlat bracket
 
 
B
SUC304Flat bracket
C
SECC LType bracket
D
SUS304 LType bracket
N
No installation bracket
Additional selection code
 
/Additional specifications
 
 

External dimensions

Vertical piping installation method (installation code 2. For codes 3, 6, or 7, see comments)

Horizontal piping installation method (installation code 8, see comments for code 9)

Note: 1. When selected for installation as 6, 7, or 9, the high and low voltage sides are opposite to the above figure;
2. When selecting installation as 3 or 7, the process of installing the bracket is opposite to the one shown in the above figure.

Terminal side wiring diagram

Wiring terminals

SUPPLY± Power supply and output terminal
CHECK± External indicator (ammeter) terminal
Grounding terminal

Note: The impedance when using an external indicator or measuring timer should be less than 10Ω