FG-ZRB type composite resistive capacitive absorber
Product Introduction
FG-ZRBType CompositeResistance capacitance absorptionThe device is a specialized equipment that effectively protects against operating overvoltage and atmospheric overvoltage. It has the dual functions of a resistance capacitance absorber and a lightning arrester, and can be widely used in vacuum circuit breakersOperation of vacuum contactors, etcGeneratorIn electric motors, transformers, reactors, and distribution lines.
Technical Parameter
FG-ZRBType CompositeResistance capacitance absorptionThe technical data of the device is shown in the following table:
PRODUCT MODEL |
System standard callvoltage (Effective value) kV |
devicehighest operating voltage (Effective value) kV |
Resistance capacitance branch |
Lightning protection branch |
product height H mm |
protect scope of application |
||||
rated capacitance µF ±10% |
Automatic accesspower gridPower frequency voltage (Effective value) kV±10% |
DC withstand voltage of capacitor 10S kV |
Power frequency amplifier Electric voltage (Effective value)kV±10%
|
1.2/50µS Impact release Electric voltage kV |
8/20µS 5kAthunder and lightning Impact residual pressure kV |
|||||
(Peak value) not greater than | ||||||||||
FG-ZRB-6Z(F) |
6 |
6.9 |
0.1 |
8 |
34.5 |
16 |
30 |
24 |
223 |
generator、motor |
FG-ZRB -6P(F) |
11 |
35 |
27 |
252 |
Transformers, reactors, and power lines |
|||||
FG-ZRB -10Z(F) |
10 |
11.5 |
0.1 |
15 |
45 |
26 |
45 |
41 |
276 |
generator、motor |
FG-ZRB -10P(F) |
19 |
50 |
45 |
315 |
Transformers, reactors, and power lines |
|||||
FG-ZRB -35(F) |
35 |
40.5 |
0.1 |
51 |
120 |
80 |
134 |
124 |
575 |
Transformers, reactors, and power lines |
pour:
1. (F) is an optional item with an action counter;
2. be directed against35kVWeak insulation equipment in the system, such as electric furnace transformers, can be specially designed with a capacity of0.2µFProducts to enhance protection;
3. Various non-standard models can be customized with parameters according to specific customer requirements;
During the capacitor acceptance test, the DC withstand voltage value of the capacitor is taken as 0.75 times the withstand voltage in the technical data sheet, and the time is 10 seconds.
Conditions of Use
1. Suitable for indoor use.
2. Environmental temperature: not lower than -40℃, not higher than+40℃; Relative humidity: not greater than95%(25℃).
3. Altitude not exceeding3000m,exceed3000mIt can be customized according to the actual situation.
4. earthquake intensity7Areas of degree and below; Maximum wind speed not exceeding35m/S.
5. Grid frequency:58~62Hz(60HzSystem),48~52Hz(50HzSystem).
6. The air in the installation site should not contain chemical corrosive gases and vapors, and there should be no explosive dust.
7. The minimum nominal creepage distance of the jacket shall not be less than20mm/kVSuitable for use in moderately polluted areas.
Instructions for use
1. FG-ZRBThe composite resistance capacitance absorber should be connected to the outlet current of the vacuum circuit breaker (vacuum contactor)mutual inductanceimplementBetween the lower side and the protected equipment (such as electric motors or transformers), as shown in the figure1As shown.
2. FG-ZRBType CompositeRX-ZRBDivided intoZType (suitable for protecting generators and motors) andPType(Suitable for protecting distribution transformers, reactors, and lines, appropriate products should be selected for ordering and installation according to the protected objects.3. FG-ZRBWhen the type of composite resistance capacitance absorber is taken out of operation and checked, it should beO-NDischarge the resistance capacitance circuit between them.
Transportation and Storage
1. FG-ZRBThe composite resistance capacitance absorber should be packed and transported in a rainproof, light, upright, and anti-collision manner during transportation.
2. When stored, it should be kept in an upright position, and the storage location should have an ambient temperature of -40℃~+40Flammable and explosive gases and chemicals are not allowed within the temperature range of ℃.
If you need detailed information or the latest product information, please send your name, contact information, and company name tosale@foago.comOr call -8002 to request, thank you for your attention and support to our company!