XBCThe fire pump used for the diesel engine fire pump set of the series drilling platform can be produced by our companyISSeries single-stageS、SOWSeries of new single-stage and two-stageTSWA、DType series multi-stage segment. The diesel engines used in this series of equipment are all domestic or imported products, which have the characteristics of good starting characteristics, strong overload capacity, compact structure, easy maintenance, simple use, and high degree of automation. They are a reliable firefighting equipment.
XBCThe working range of the series diesel engine fire pump set:
Flow range:10-800L/S
Pressure Range: 0.2-2.2MPA
rotational speed: 1500r/min 1800 min 2400 min 3000 min
XBCThe working range of the series diesel engine fire pump set:
ambient atmosphere pressure:> 90KPa
ambient temperature: five0C-400C
Relative air temperature:≤80%
Power of diesel engine under abnormal conditions,To ensure normal operation,A high-power diesel engine should be selected to match the water pump.
Performance characteristics:
1It has three complete starting functions:
1Manual start function: Manual and automatic interlocking can be achieved through the conversion switch, and manual start function can be realized
2Automatic manual function: allows three starts, if three attempts are unsuccessful, a "start failure alarm" will be issued and the starting state will be automatically exited; After a successful start, the time from starting to rated load is5-10-15S(varies according to the size of the unit capacity);
3Emergency manual direct start function: When the automatic control device fails, the emergency manual direct start function can be achieved.
IIAutomatic operation: When the water pump unit receives a valid fire signal, if the power supply system of the electric motor fire pump is cut off, there is a phase loss, or the electric pump fails and cannot start normally, the diesel engine fire pump unit will automatically start and operate. Once the power supply system is restored to normal or the electric pump can operate normally, it can automatically switch to the electric pump.
IIIAutomatic shutdown: When the fire signal disappears, the diesel engine fire pump will automatically delay shutdown.
4Self charging and voltage stabilization function of the battery: The battery can be automatically charged by the diesel engine charging motor using mains power, ensuring smooth start-up of the unit.
5Equipped with a comprehensive indication system: ready to start, manual start, automatic start, unit operation, unit shutdown, battery charging, overspeed, low diesel engine lubricating oil pressure, low turbocharger oil pressure, low diesel engine lubricating oil temperature, high diesel engine cooling water temperature, low battery voltage, low (or missing) fuel level, low diesel engine cooling water temperature preheating, scheduled inspections.
VIEquipped with a comprehensive alarm or protection system: alarm or protection for three failed starts, overspeed alarm or protection, low lubricating oil pressure alarm or protection, low turbocharger oil pressure alarm or protection, high cooling water temperature alarm or protection, low lubricating oil temperature alarm or protection, automatic charging device fault alarm, low battery voltage alarm, high battery voltage alarm, low oil level alarm or protection.
7Equipped with a comprehensive display system: diesel engine lubricating oil pressure, diesel engine speed, battery charging current, battery charging voltage.
8Direct coupling type: The diesel engine and water pump are directly connected by a coupling, using a common channel steel base. The structure is compact, the overall performance is good, the faults are few, the vibration is small, and the on-site construction and installation are convenient.
9Wide range of equipment pressure and flow: Unit selectionISSeries single-stage single suctionS\\SOWSeries of new single-stage double suctionTSWA\\DThe Type series multi-stage water pump can meet the fire protection needs of water in the same situation.
10Adjustable flow rate and pressure: The diesel engine water pump is equipped with a mechanical or electronic regulator. When the flow rate and head of the water pump do not match the actual situation, the speed of the diesel engine can be adjusted and changed.
11Equipped with a water heating and preheating device: the unit is equipped withAC220VCooling water preheating device can ensure that the unit operates below50CNormal operation in the environment.
TwelveDual battery circuit: When one set of batteries fails, the other set of batteries can be automatically switched in.
ThirteenMaintenance free battery: No need to frequently add supplementary fluid.
14Automatic scheduled inspection test: The fire protection system is usually in standby mode, and the equipment of the unit can automatically complete the test of the unit's standby state and alarm in a timely manner.
Note: The above functions can be selected according to user needs. It can also be customized according to special needs.
to configure:
1Water pump:ISSeries single-stage single suctionS、SOWSeries of new single-stage dual suctionTSWA、DType series multi-stage segment.
IIDiesel engine: equipped with single cylinder, double cylinder, three cylinder, four cylinder, six cylinder, eight cylinder, and twelve cylinder diesel engines.
IIISpeed:1500r/min 1800r/min 2400r/min 3000r/minclass
4Other accessories: filtration system, silencing system, cooling system, fuel tank, common base, radiator, battery, charger. (Preheating system can be added)
5Control cabinet: microcontrollerPLCProgrammer, sensor, fully automatic control cabinet.
Model Description:
Structure and Control System Diagram
Function Description:
The diesel engine fire pump can be combined with electric pumps, stabilizing pumps, etc. to form an automatic water fire water supply system, and can be linked with the fire control center.
When the diesel engine fire pump unit receives a start command, if the mains power is cut off, the diesel engine automatic control cabinet immediately sends a start signal to the pump unit starting motor, starts the motor, and causes the diesel engine to idle and start. Then gradually adjust the throttle to accelerate the diesel engine until it reaches the rated speed. The control system will automatically monitor the operation of the diesel engine, such as the oil pressure, oil temperature, speed, and outlet pressure of the water pump, and determine whether the diesel engine starts normally through automatic monitoring. If the startup fails, the control system will issue a restart signal. If all three startups fail, the self-control system will issue a failure alarm. When the diesel engine fire pump unit receives a signal that the pipeline pressure is restored or the mains power is restored to normal, the pump unit will quickly slow down and automatically stop after monitoring the idle position for a period of time.
XBC
model
|
Rated flow rate
m3/h
|
rated head
m
|
rated speed
r/min
|
Water pump model
|
Diesel engine model
|
XBC8.0/13.9
|
30-50-60
|
84-80-75
|
2900
|
IS80-50-250
|
4L22B-SB
|
XBC7.0/13.0
|
47
|
70
|
2900
|
IS80-50-250A
|
4L22B-SB
|
XBC6.0/12.2
|
44
|
60
|
2900
|
IS80-50-250B
|
4L22B-SB
|
XBC8.5/11.7
|
42
|
85
|
2900
|
IS80-50-315B
|
4L22B-SB
|
XBC11.0/13.
|
47
|
110
|
2900
|
IS80-50-315A
|
KM496-SB
|
XBC12.5/13.9
|
30-50-60
|
128-125-123
|
2900
|
IS80-50-315
|
KM496-SB
|
XBC5.0/27.8
|
60-100-120
|
54-50-47
|
2900
|
IS100-65-200
|
4L22B-SB
|
XBC6.0/23.9
|
86
|
60
|
2900
|
IS100-65-250B
|
4L22B-SB
|
XBC7.0/25.8
|
93
|
70
|
2900
|
IS100-65-250A
|
4L22B-SB
|
XBC8.0/27.8
|
60-100-120
|
87-80-75
|
2900
|
IS100-65-250
|
KM496-SB
|
XBC10.0/25.0
|
90
|
100
|
2900
|
IS100-65-315B
|
KM496-SB
|
XBC5.0/55.6
|
120-200-240
|
58-50-45
|
2900
|
IS125-100-200
|
KM496-SB
|
XBC6.0/48.1
|
173
|
60
|
2900
|
IS125-100-250B
|
KM496-SB
|
XBC12.5/27.8
|
60-100-120
|
133-125-118
|
2900
|
IS100-65-315
|
X6135JD
|
XBC8.0/55.6
|
120-200-20
|
87-80-72
|
2900
|
IS125-100-250
|
X6135JD
|
XBC12.5/55.6
|
120-200-240
|
133-125-120
|
2900
|
IS125-100-315
|
X6135JZD
|
XBC11.0/52.8
|
190
|
110
|
2900
|
IS125-100-315A
|
X6135JZD
|
XBC9.2/48.1
|
173
|
92
|
2900
|
IS125-100-315B
|
X6135JD
|
XBC5.0/111
|
240-400-460
|
55-50-45
|
1450
|
IS200-150-400
|
X6135JZD
|
XBC5.0/28
|
100
|
50
|
1450
|
IS125-100-400
|
495AD
|
XBC5.0/28
|
200
|
50
|
1450
|
IS150-125-400
|
TL4110ZD
|
XBC4.6/10
|
30-36-42
|
50-46-40
|
1450
|
75TSWA×4
|
4L22B-SB1
|
XBC5.7/10
|
30-36-42
|
62-57-50
|
1450
|
75TSWA×5
|
4L22B-SB1
|
XBC6.9/10
|
30-36-42
|
75-69-60
|
1450
|
75TSWA×6
|
4L22B-SB1
|
XBC8.0/10
|
30-36-42
|
87-80-70
|
1450
|
75TSWA×7
|
4L22B-SB1
|
XBC9.2/10
|
30-36-42
|
100-92-80
|
1450
|
75TSWA×8
|
4L22B-SB1
|
XBC10.3/10
|
30-36-42
|
112-103-90
|
1450
|
75TSWA×9
|
4L22B-SB1
|
XBC6.2/19.2
|
62-69-80
|
64-62-56
|
1450
|
100TSWA×4
|
495AD
|
XBC7.8/19.2
|
62-69-80
|
81-78-70
|
1450
|
100TSWA×5
|
495AD
|
XBC9.3/19.2
|
62-69-80
|
97-93-84
|
1450
|
100TSWA×6
|
495AZD
|
XBC10.9/19.2
|
62-69-80
|
113-109-98
|
1450
|
100TSWA×7
|
495AZD
|
XBC6.4/25
|
72-90-108
|
69-64-60
|
1450
|
125TSWA×3
|
495AD
|
XBC8.6/25
|
72-90-108
|
92-86-80
|
1450
|
125TSWA×4
|
TL4110D
|
XBC10.8/25
|
72-90-108
|
115-108-100
|
1450
|
125TSWA×5
|
TL4110ZD
|
XBC6.0/43
|
119-155-191
|
65-60-55
|
1480
|
150TSWA×2
|
TL4110D
|
XBC9.0/43
|
119-155-191
|
97-90-82
|
1480
|
150TSWA×3
|
TL4110ZD
|
XBC12.0/43
|
119-155-191
|
129-120-109
|
1480
|
150TSWA×4
|
X6135JD
|
XBC8.6/77.8
|
190-280-346
|
95-86-77
|
1480
|
200D1-43×2
|
X6135JD
|
XBC12.9/77.8
|
190-280-346
|
142-129-115
|
1480
|
200D1-43×3
|
X6135JZD
|
XBC12.0/125
|
400-450-500
|
123-120-114
|
1480
|
D450-60Ⅲ×2
|
WX6135JD
|
XBC11.4/139
|
450-500-550
|
120-114-108
|
1480
|
D500-57×2
|
12V135JZD
|
XBC12.0/200
|
550-720-850
|
132-120-108
|
1480
|
D720-62×2
|
W12V138A
|
XBC5.0/60
|
150-216-260
|
59-50-45
|
1480
|
D216-25×2
|
TL4110ZD
|
XBC7.5/60
|
150-216-260
|
88-75-67
|
1480
|
D216-25×3
|
X6135JD
|
XBC10.0/60
|
150-216-260
|
118-100-90
|
1480
|
D216-25×4
|
X6135JD
|
XBC12.5/60
|
150-216-260
|
147-125-112
|
1480
|
D216-25×5
|
X6135JZD
|
XBC6.5/134
|
360-485-612
|
71-65-56
|
1450
|
250S65
|
X6135JZD
|
XBC9.0/219
|
590-790-936
|
93-90-82
|
1450
|
300S90
|
W12V135AZD
|
XBC7.8/210
|
576-756-918
|
86-78-70
|
150
|
300S90A
|
12V135AJZD
|
XBC6.7/200
|
540-720-900
|
72-67-57
|
1450
|
300S90B
|
12V135JZD
|
XBC5.8/219
|
576-790-972
|
65-58-50
|
1450
|
300S58
|
X6135JD
|
XBC5.0/204
|
529-735-893
|
55-50-42
|
1450
|
300S58A
|
X6135JZD
|
XBC12.5/351
|
850-1260-1660
|
140-125-100
|
1450
|
350S125
|
KTA38-G2
|
XBC11.2/328
|
787-1181-1538
|
120-112-86
|
1450
|
350S125A
|
KTA38-G
|
XBC9.6/305
|
697-1098-1363
|
106-96-77
|
1450
|
350S125B
|
KTA19-G4
|
XBC7.5/351
|
972-1260-1440
|
80-75-65
|
1450
|
350S75
|
W12V138A-3
|
XBC6.5/325
|
900-1170-1332
|
70-65-56
|
1450
|
350S75A
|
W12V135AD
|
XBC5.5/300
|
813-1080-1202
|
59-55-46
|
1450
|
350S75B
|
12V135JZD
|