Shanghai Jiaquan Pump Industry Co., Ltd
Home>Products>Fully automatic diesel engine fire protection complete set
Fully automatic diesel engine fire protection complete set
Brief description: The XBC series diesel engine fire pump set produced by Shanghai Jiaquan Pump Industry Manufacturing Co., Ltd. is strictly developed
Product details

XBCThe fire pump used for the diesel engine fire pump set of the series drilling platform can be produced by our companyISSeries single-stageSSOWSeries of new single-stage and two-stageTSWADType series multi-stage segment. The diesel engines used in this series of equipment are all domestic or imported products, which have the characteristics of good starting characteristics, strong overload capacity, compact structure, easy maintenance, simple use, and high degree of automation. They are a reliable firefighting equipment.

XBCThe working range of the series diesel engine fire pump set:

Flow range:10-800L/S

Pressure Range: 0.2-2.2MPA

rotational speed: 1500r/min 1800 min 2400 min 3000 min

XBCThe working range of the series diesel engine fire pump set:

ambient atmosphere pressure:> 90KPa

ambient temperature: five0C-400C

Relative air temperature:80

Power of diesel engine under abnormal conditions,To ensure normal operation,A high-power diesel engine should be selected to match the water pump.

Performance characteristics:

1It has three complete starting functions:

1Manual start function: Manual and automatic interlocking can be achieved through the conversion switch, and manual start function can be realized

2Automatic manual function: allows three starts, if three attempts are unsuccessful, a "start failure alarm" will be issued and the starting state will be automatically exited; After a successful start, the time from starting to rated load is5-10-15S(varies according to the size of the unit capacity);

3Emergency manual direct start function: When the automatic control device fails, the emergency manual direct start function can be achieved.

IIAutomatic operation: When the water pump unit receives a valid fire signal, if the power supply system of the electric motor fire pump is cut off, there is a phase loss, or the electric pump fails and cannot start normally, the diesel engine fire pump unit will automatically start and operate. Once the power supply system is restored to normal or the electric pump can operate normally, it can automatically switch to the electric pump.

IIIAutomatic shutdown: When the fire signal disappears, the diesel engine fire pump will automatically delay shutdown.

4Self charging and voltage stabilization function of the battery: The battery can be automatically charged by the diesel engine charging motor using mains power, ensuring smooth start-up of the unit.

5Equipped with a comprehensive indication system: ready to start, manual start, automatic start, unit operation, unit shutdown, battery charging, overspeed, low diesel engine lubricating oil pressure, low turbocharger oil pressure, low diesel engine lubricating oil temperature, high diesel engine cooling water temperature, low battery voltage, low (or missing) fuel level, low diesel engine cooling water temperature preheating, scheduled inspections.

VIEquipped with a comprehensive alarm or protection system: alarm or protection for three failed starts, overspeed alarm or protection, low lubricating oil pressure alarm or protection, low turbocharger oil pressure alarm or protection, high cooling water temperature alarm or protection, low lubricating oil temperature alarm or protection, automatic charging device fault alarm, low battery voltage alarm, high battery voltage alarm, low oil level alarm or protection.

7Equipped with a comprehensive display system: diesel engine lubricating oil pressure, diesel engine speed, battery charging current, battery charging voltage.

8Direct coupling type: The diesel engine and water pump are directly connected by a coupling, using a common channel steel base. The structure is compact, the overall performance is good, the faults are few, the vibration is small, and the on-site construction and installation are convenient.

9Wide range of equipment pressure and flow: Unit selectionISSeries single-stage single suctionS\\SOWSeries of new single-stage double suctionTSWA\\DThe Type series multi-stage water pump can meet the fire protection needs of water in the same situation.

10Adjustable flow rate and pressure: The diesel engine water pump is equipped with a mechanical or electronic regulator. When the flow rate and head of the water pump do not match the actual situation, the speed of the diesel engine can be adjusted and changed.

11Equipped with a water heating and preheating device: the unit is equipped withAC220VCooling water preheating device can ensure that the unit operates below50CNormal operation in the environment.

TwelveDual battery circuit: When one set of batteries fails, the other set of batteries can be automatically switched in.

ThirteenMaintenance free battery: No need to frequently add supplementary fluid.

14Automatic scheduled inspection test: The fire protection system is usually in standby mode, and the equipment of the unit can automatically complete the test of the unit's standby state and alarm in a timely manner.

Note: The above functions can be selected according to user needs. It can also be customized according to special needs.

to configure:

1Water pump:ISSeries single-stage single suctionSSOWSeries of new single-stage dual suctionTSWADType series multi-stage segment.

IIDiesel engine: equipped with single cylinder, double cylinder, three cylinder, four cylinder, six cylinder, eight cylinder, and twelve cylinder diesel engines.

IIISpeed:1500r/min 1800r/min 2400r/min 3000r/minclass

4Other accessories: filtration system, silencing system, cooling system, fuel tank, common base, radiator, battery, charger. (Preheating system can be added)

5Control cabinet: microcontrollerPLCProgrammer, sensor, fully automatic control cabinet.

Model Description:

Structure and Control System Diagram

Function Description:

The diesel engine fire pump can be combined with electric pumps, stabilizing pumps, etc. to form an automatic water fire water supply system, and can be linked with the fire control center.

When the diesel engine fire pump unit receives a start command, if the mains power is cut off, the diesel engine automatic control cabinet immediately sends a start signal to the pump unit starting motor, starts the motor, and causes the diesel engine to idle and start. Then gradually adjust the throttle to accelerate the diesel engine until it reaches the rated speed. The control system will automatically monitor the operation of the diesel engine, such as the oil pressure, oil temperature, speed, and outlet pressure of the water pump, and determine whether the diesel engine starts normally through automatic monitoring. If the startup fails, the control system will issue a restart signal. If all three startups fail, the self-control system will issue a failure alarm. When the diesel engine fire pump unit receives a signal that the pipeline pressure is restored or the mains power is restored to normal, the pump unit will quickly slow down and automatically stop after monitoring the idle position for a period of time.

XBC
model
Rated flow rate
m3/h
rated head
m
rated speed
r/min
Water pump model
Diesel engine model
XBC8.0/13.9
30-50-60
84-80-75
2900
IS80-50-250
4L22B-SB
XBC7.0/13.0
47
70
2900
IS80-50-250A
4L22B-SB
XBC6.0/12.2
44
60
2900
IS80-50-250B
4L22B-SB
XBC8.5/11.7
42
85
2900
IS80-50-315B
4L22B-SB
XBC11.0/13.
47
110
2900
IS80-50-315A
KM496-SB
XBC12.5/13.9
30-50-60
128-125-123
2900
IS80-50-315
KM496-SB
XBC5.0/27.8
60-100-120
54-50-47
2900
IS100-65-200
4L22B-SB
XBC6.0/23.9
86
60
2900
IS100-65-250B
4L22B-SB
XBC7.0/25.8
93
70
2900
IS100-65-250A
4L22B-SB
XBC8.0/27.8
60-100-120
87-80-75
2900
IS100-65-250
KM496-SB
XBC10.0/25.0
90
100
2900
IS100-65-315B
KM496-SB
XBC5.0/55.6
120-200-240
58-50-45
2900
IS125-100-200
KM496-SB
XBC6.0/48.1
173
60
2900
IS125-100-250B
KM496-SB
XBC12.5/27.8
60-100-120
133-125-118
2900
IS100-65-315
X6135JD
XBC8.0/55.6
120-200-20
87-80-72
2900
IS125-100-250
X6135JD
XBC12.5/55.6
120-200-240
133-125-120
2900
IS125-100-315
X6135JZD
XBC11.0/52.8
190
110
2900
IS125-100-315A
X6135JZD
XBC9.2/48.1
173
92
2900
IS125-100-315B
X6135JD
XBC5.0/111
240-400-460
55-50-45
1450
IS200-150-400
X6135JZD
XBC5.0/28
100
50
1450
IS125-100-400
495AD
XBC5.0/28
200
50
1450
IS150-125-400
TL4110ZD
XBC4.6/10
30-36-42
50-46-40
1450
75TSWA×4
4L22B-SB1
XBC5.7/10
30-36-42
62-57-50
1450
75TSWA×5
4L22B-SB1
XBC6.9/10
30-36-42
75-69-60
1450
75TSWA×6
4L22B-SB1
XBC8.0/10
30-36-42
87-80-70
1450
75TSWA×7
4L22B-SB1
XBC9.2/10
30-36-42
100-92-80
1450
75TSWA×8
4L22B-SB1
XBC10.3/10
30-36-42
112-103-90
1450
75TSWA×9
4L22B-SB1
XBC6.2/19.2
62-69-80
64-62-56
1450
100TSWA×4
495AD
XBC7.8/19.2
62-69-80
81-78-70
1450
100TSWA×5
495AD
XBC9.3/19.2
62-69-80
97-93-84
1450
100TSWA×6
495AZD
XBC10.9/19.2
62-69-80
113-109-98
1450
100TSWA×7
495AZD
XBC6.4/25
72-90-108
69-64-60
1450
125TSWA×3
495AD
XBC8.6/25
72-90-108
92-86-80
1450
125TSWA×4
TL4110D
XBC10.8/25
72-90-108
115-108-100
1450
125TSWA×5
TL4110ZD
XBC6.0/43
119-155-191
65-60-55
1480
150TSWA×2
TL4110D
XBC9.0/43
119-155-191
97-90-82
1480
150TSWA×3
TL4110ZD
XBC12.0/43
119-155-191
129-120-109
1480
150TSWA×4
X6135JD
XBC8.6/77.8
190-280-346
95-86-77
1480
200D1-43×2
X6135JD
XBC12.9/77.8
190-280-346
142-129-115
1480
200D1-43×3
X6135JZD
XBC12.0/125
400-450-500
123-120-114
1480
D450-60Ⅲ×2
WX6135JD
XBC11.4/139
450-500-550
120-114-108
1480
D500-57×2
12V135JZD
XBC12.0/200
550-720-850
132-120-108
1480
D720-62×2
W12V138A
XBC5.0/60
150-216-260
59-50-45
1480
D216-25×2
TL4110ZD
XBC7.5/60
150-216-260
88-75-67
1480
D216-25×3
X6135JD
XBC10.0/60
150-216-260
118-100-90
1480
D216-25×4
X6135JD
XBC12.5/60
150-216-260
147-125-112
1480
D216-25×5
X6135JZD
XBC6.5/134
360-485-612
71-65-56
1450
250S65
X6135JZD
XBC9.0/219
590-790-936
93-90-82
1450
300S90
W12V135AZD
XBC7.8/210
576-756-918
86-78-70
150
300S90A
12V135AJZD
XBC6.7/200
540-720-900
72-67-57
1450
300S90B
12V135JZD
XBC5.8/219
576-790-972
65-58-50
1450
300S58
X6135JD
XBC5.0/204
529-735-893
55-50-42
1450
300S58A
X6135JZD
XBC12.5/351
850-1260-1660
140-125-100
1450
350S125
KTA38-G2
XBC11.2/328
787-1181-1538
120-112-86
1450
350S125A
KTA38-G
XBC9.6/305
697-1098-1363
106-96-77
1450
350S125B
KTA19-G4
XBC7.5/351
972-1260-1440
80-75-65
1450
350S75
W12V138A-3
XBC6.5/325
900-1170-1332
70-65-56
1450
350S75A
W12V135AD
XBC5.5/300
813-1080-1202
59-55-46
1450
350S75B
12V135JZD

If the above spectrogram and spectrogram do not meet your requirements, please let us know the flow rate and head, and we will help you select the appropriate one.
Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!