Shanghai Yiqing Trading Co., Ltd
Home>Products>Gulde 3800SA Valve Positioner
Gulde 3800SA Valve Positioner
Product details introduction
Product details

Product details introduction

Product Introduction

undefined

Gulde 3800SAIntelligent Locator
    • Gulde 3800SAThe intelligent locator is simple to use, compact in size, and easy to install. It will4-20 mAThe input signal is converted into a pneumatic output signal to drive the control valve actuator. Parameter settings are made through buttons and LCD screens(LCD)Interface to proceed. The LCD screen is located inside the protective cover, so it is not affected by the environment.Gulde3800SASupport Chinese interface.
    • Gulde 3800SAAdopting a two-stage locator design. The preamplifier provides a high static gain to respond to small changes in the input signal. The pneumatic amplifier delivers sufficient compressed air to the actuator, enabling the equipment to achieve optimal dynamic performance with minimal steady-state air consumption.
    • The high-performance non connecting rod valve position feedback system avoids actual contact between the valve stem and the positioner. This way, there will be no wear on the parts, thus achieving the maximum cycle life. Due to the absence of connecting rods and pins, the number of installation parts and the complexity of installation are reduced, and the feedback components are retained on the actuator push rod, greatly simplifying the replacement and maintenance of the locator.
Product specifications
Installation method Gulde 5100
Direct travel actuator
Angular travel actuator
Input signal Analog input signal:4-20 mA DC, standards; Divisible journey
Minimum voltage:The available voltage at the instrument terminal must be8.5 VFor analog control) or9.0 V(For)HARTCommunication)
Maximum voltage:30 VDC Voltage
Minimum control current:4.0 mA(Below)3.5 mAMay cause microprocessor restart)
Overcurrent protection:Input circuit limits current to avoid internal damage
Reverse polarity protection:Reverse loop current will not cause instrument damage
output signal The pneumatic signal required by the executing agency can reach the maximum pressure of the gas source95%
Minimum range:0.5 bar (7 psig)
Maximum range:7 bar (101 psig)
Mode of action:Single acting, positive acting
Mpa Recommended value:Greater than the maximum value required by the executing agency0.5 bar (7 psig)
Maximum value:7 bar (101 psig)
operation temperature -40to85°CThe temperature is below-20°CWhen,LCDThe LCD screen may not be able to read the information.
Gas consumption Mpa1.5 bar (22 psig)Time:0.06 Nm3/h (2.3 scfh)
Mpa4 bar (58 psig)Time:0.12 Nm3/h (4.4 scfh)
Gas capacity Mpa1.5 bar (22 psig)Time:4.48 Nm3/h (167 scfh)
Mpa4 bar (58 psig)Time:9.06 Nm3/h (338 scfh)
Independent Linearity Output range0.5%
electromagnetic compatibility conform toEN 6132-1The first edition of the standard
Immunity - compliantEN 6132-1Standard table2The industrial scenario shown in.
Emissions - GradeA ISMClass device level:Aclass1group
Tested to be compliantNAMUR NE21require
Vibration test method Tested to be compliantANSI/ISA-75.13.01auxiliary word for ordinal numbers5.3.5.ASection requirements. Perform resonant frequency search in three-dimensional direction. This device is tested by the American Instrumentation Society at each resonant frequency(ISA)required1/2Hour durability test, in addition to200Ten thousand cycles of action testing.
Input impedance Gulde 3800SAThe input impedance of charged electronic circuits is not pure resistance. To compare with the specifications of resistive loads, you can use450 ohmEquivalent impedance. This value is equivalent to a current of20 mAChronous9 VVoltage.
Structural materials Shell and lid:A03600Low copper aluminum alloy
Elastic components:Nitrile rubber
weight

1.5Kilogram(3.3Pound)