Jiangsu Zhengsheng Automation Instrument Co., Ltd
Home>Products>High temperature radar level gauge
High temperature radar level gauge
High temperature radar level gauge
Product details
1. Overview of High Temperature Radar Level Gauge Products:
High temperature radar level gauge is an advanced radar type level measuring instrument with a maximum measurement distance of 30 meters. It can be used for measuring the level of blast furnace materials, thick tank tops, and installation of short pipes. It outputs 4... 20mA analog signals.
2. Technical parameters of high-temperature radar level gauge:
Application: Suitable for measuring the material level of blast furnaces, storage tanks with thick tank tops, and installation of short pipes.
Measurement range: 30 meters
Process connection: flange
Medium temperature:- 40-500℃
Process pressure: atmospheric pressure
Accuracy: ± 15mm
Repeatability: ± 2mm
Frequency range: 6.8GHz
Explosion proof/protection level: Exib IIC T6 Gb
Protection level: IP67
Signal output: 4-20mA/HART
3. Precautions for Installation of High Temperature Radar Level Gauge:
Due to incorrect installation, significant false echoes may occur
The sensor should not be too close to the container wall.
If the sensor is too close to the container, it will generate strong false echoes. Adhesive media, rivets, screws, or welds can cause false reflections. So the sensor must maintain a certain distance from the container wall.
The sensor should be perpendicular to the surface of the medium.
If the sensor is not aligned with the surface of the medium during installation, the measurement signal will weaken. The axis of the radar sensor must be aligned vertically with the surface of the medium.
If there is a ladder, bracket or stirring blade inside the tank during measurement, the instrument will produce false backlash, which will affect the measurement. Therefore, in practical applications, these obstacles should be avoided or a refractive plate should be used to refract the false signal away.
Devices inside the container, such as ladders, can cause false echoes. When designing the installation location, no device should obstruct the operation of radar signals.
The bracket inside the container can cause strong false echoes. The use of refractive plates can effectively prevent false reflections.