Introduction to Industrial Humidification Solution for Electronic Workshop: A company in Hangzhou that produces electronic appliances requires a humidity of 55% in the production process of the new workshop. Due to the unsatisfactory humidification effect of the old workshop using air conditioning units, in early 2018, the new workshop first tested a workshop and installed a dry mist humidification system, which solved the problems of insufficient humidity and condensation of humidification water for the manufacturer. Due to the installation effect meeting customer expectations, all remaining production workshops have installed the "Fog King" dry mist humidification system.
The basic information of the electronic factory is as follows:
Area (m2) |
Quantity (room) |
Height (m) |
Temperature (℃) |
Original humidity |
Humidity requirements |
Fresh air volume (m3/h) |
3000 |
5 |
4.5 |
22-25℃ |
30% |
55% |
44000 |
After calculation, the required humidification amount for the workshop is as follows:
Area (m2) |
Height (m) |
Volume (m3) |
Ventilation rate (m3/h) |
Humidification rate (L/h) |
15000 |
4.5 |
675000 |
220000 |
1270 |
According to the humidification capacity, the installation quantity is as follows:
Area (m2) |
Humidification rate (L/h) |
Humidity requirements |
Dry mist humidification capacity (L/h) |
Quantity (set) |
15000 |
1270 |
55% |
11 |
116 |
Case study of installing a dry mist humidification system in an electrical workshop in Hangzhou:
Detailed introduction of dry mist humidifier products:
Customers can configure the above components according to their actual needs
The dry mist humidification system of Wuwang has become a hot new humidification equipment due to its non wetting humidification performance, energy-saving performance, high cost-effectiveness, and easy maintenance advantages.
Mist King JY-WW-QS8 dry fog humidification system is mixed by air water two fluids, and then subjected to three times of gasification shearing, it is again micronized by the air ejected from the nozzle, and is hit by the same micronized gas fog from the other nozzle. At the same time of repeated shearing, 33000-40000 Hz ultrasonic waves are generated to further micronize the liquid droplets. The principle of an even atomization system realizes real multistage atomization to obtain good spray effect, and the diameter of spray particles is 5-7.5um.
Water pressure (bar) |
Air pressure (bar) |
Water flow rate (L/h) |
Gas consumption (L/min) |
Unilateral spray distance (mm) |
Shao Te average value (um) |
Droplet reaching area (m²) |
0 |
3 |
10 |
116 |
5800 |
5.5 |
100 |
0 |
2 |
8 |
110 |
4500 |
7.5 |
80 |
0 |
1 |
6 |
90 |
3800 |
10 |
60 |
specifications
material |
main housing |
polypropylene |
Anti corrosion, long service life |
spray nozzle |
plastics |
Anti corrosion, long service life |
|
retainer |
silicone rubber |
─ |
|
weight |
Single nozzle |
220g |
─ |
4 nozzles |
350g |
─ |
|
Connection method |
Gas path |
Rc1/4 |
Diameter Φ 10mm |
waterway |
Rc1/8 |
Diameter Φ 8mm |