The HD series capacitor switching switch is designed specifically for reactive power compensation of 0.4KV power capacitors. This switch is mainly used for switching capacitors for power compensation in 400V voltage systems. And by combining power electronic switch thyristors with high-power bistable magnetic holding relays, voltage zero crossing input and current zero crossing cutoff can be achieved. It has the advantages of low contact resistance, impact resistance, reliable operation, low energy consumption, and long mechanical life. Mainly applicable for low-voltage reactive power compensation in factories, residential areas, transformer substations, urban and rural power grid renovation.
1、 Product Model and Definition
HD □K-□-□-□
Note: HDFK-0.45-60A composite switch, 450V, 60A, three-phase
HDFK-0.25-60A-Y composite switch, 250V, 60A, phase separated
2、 Product functional parameters
a. This switch is mainly used for switching capacitors for power compensation in 400V voltage systems.
b. Combining power electronic switch thyristors with high-power bistable magnetic holding relays to achieve voltage zero crossing input and current zero crossing cutoff. It has the advantages of low contact resistance, impact resistance, reliable operation, low energy consumption, and long mechanical life.
c. Mainly applicable for low-voltage reactive power compensation in factories, residential areas, transformer substations, urban and rural power grid renovation.
Technical parameters
Working environment conditions
Environmental temperature:- 25℃~+60℃
Relative humidity: 20% to 90% at 40 ℃
Rated working voltage and current
Voltage: taken from internal A and C phases 380V
Frequency: 50Hz/60Hz
Current: ≤ 60A
Specification
Service life: ≥ 400000 times
Control capacity: Three phase co compensation ≤ 40Kvar
Single phase compensation ≤ 20Kvar
Control voltage: DC 12V ± 5V
Control terminal current: ≤ 3mA
Response time: ≤ 40ms
Re investment delay: ≤ 1000ms
Whole machine power consumption: ≤ 3VA
Continuous connection interval: ≥ 100ms
Contact pressure drop: ≤ 100mV
Contact withstand voltage: ≥ 1600V AC
Altitude: ≤ 3500M
Insulation level: ≥ 10M under normal atmospheric conditions
Product appearance and installation dimensions (specific installation dimensions are subject to the user manual)
Dimensions: 160 × 96 × 90.5 (in millimeters);
Installation size: 142 × 80 (unit: mm);