Technical parameters: KAM series pneumatic quick installation angle regulating valve adopts a top guide structure, with a simple and dead angle flow p
Product details

brief introduction


KAM series pneumatic quick installation angle regulating valveAdopting a top guide structure, the flow path inside the valve body is simple and free of dead corners, which can avoid phenomena such as medium coking, bonding, and blockage, and has a certain self-cleaning ability. This product is suitable for regulating high viscosity media containing suspended solids.


KAM series pneumatic quick installation angle regulating valveProduct Specification

canonical name

Industrial Control Valve

Structure length

Flange standard

pneumatic control valve

Pressure and temperature rating

international standard

IEC 60534-1

IEC 60534-3-1

ASME B16.5

IEC 60534-4

ASME B16.34

national standard

GB/T17213

GB/T17213.3

JB/T79, HG/T20592, etc

GB/T4213

GB/T9131


pneumatic control valveMain parameters of valve body

Form

Angular shape

Nominal Diameter

DN25~DN300

nominal pressure

PN16、40、63,ANSI CL150、300、600

Valve body and valve cover material

WCB, WC6, WC9, CF8, CF8M, HC276, Ti alloy, etc

Material of valve internals

304, 316, HC276, Ti alloy, etc

Packing material

PTFE V-shaped, flexible graphite, PTFE packing, flexible graphite with nickel wire

actuator

Pneumatic and electric

Connect with the actuator

Bolt compression type, round nut locking type

Valve cover type

Standard type, high temperature type (heat sink), corrugated tube type

Connection method

Flange type (RF, MFM, RJ), welded type (SW, BW)

flange distance

See the table below

operation temperature

-29~+230 (standard),+230~+560 (medium high temperature)

Leakage level

ANSI B16.104 IV、VI、 Zero Leakage

Traffic characteristics

Equal percentage, linear ratio

Inherent adjustable ratio

50:1



KAM series pneumatic quick installation angle regulating valveValve structure length (flange distance)

Nominal Diameter

20

25

32

40

50

65

80

100

125

150

200

250

300

Flange distance L1, L2

PN16、25

95

95

105

111

127

138

149

176

200

225

271

325

375

PN40

99

99

107

117

133

146

159

184

210

237

284

-

-

PN63、100

105

105

115

125

143

156

168

197

230

254

305

-

-


KAM series pneumatic quick installation angle regulating valveRated flow coefficient and stroke

Nominal Diameter

20

25

32

40

50

65

80

100

125

150

200

250

300

Valve seat diameter

20

25

32

40

50

65

80

100

125

150

200

250

300

Rated Cv

linear

7

8.5

13

21

34

53

85

135

210

340

535

800

1280

Equal percentage

6.3

10

17

25

40

63

99

160

250

360

640

900

1440

rated travel

16

25

40

60

100

Note: For nominal diameters above DN300, please refer to large-diameter control valves





KAM series pneumatic quick installation angle regulating valveInstallation precautions


In order to ensure the normal operation of the regulating valve during start-up and ensure the safe operation of the system for the newly designed and installed control system, the nameplate markings on the valve should be checked for compliance with the design requirements before installation. At the same time, the following items should also be debugged: basic error limit; Full journey deviation; Return difference; Dead zone; Leakage rate (when strictly required).

If the control valve in the original system is overhauled, in addition to the calibration of the above items, the sealing inspection shall also be carried out on the stuffing box and connection of the old valve.

In the use of regulating valves, many of them are often not caused by the quality of the regulating valve itself, but by improper installation and use of the regulating valve, such as improper installation environment, installation position and direction, or unclean pipelines. Therefore, attention should be paid to the following aspects when installing and using regulating valves:

(1) The regulating valve is a field instrument, and it is required that the ambient temperature should be within the range of -25 to 60 ℃ and the relative humidity should be ≤ 95%. If installed outdoors or in high-temperature environments, waterproof and cooling measures should be taken. In areas with seismic sources, it is necessary to stay away from the source or increase anti vibration measures.

(2) Regulating valves should generally be installed vertically, and in special cases, they can be tilted. For example, if the tilt angle is too large or the valve itself weighs too much, supporting components should be added to protect the valve.

(3) The pipeline for installing regulating valves should generally not be too high above the ground or floor. When the pipeline height is greater than 2 meters, a platform should be set up as much as possible to facilitate the operation of the handwheel and maintenance.

(4) Before installing the regulating valve, the pipeline should be cleaned to remove dirt and welding slag. After installation, in order to ensure that impurities do not remain in the valve body, the valves should be cleaned again. That is, when introducing the medium, all valves should be opened to prevent impurities from getting stuck. After using the handwheel mechanism, it should be restored to its original neutral position.

(5) In order to enable the production process to continue in case of malfunction or maintenance of the regulating valve, a bypass pipeline should be added to the regulating valve, and special attention should be paid to whether the installation position of the regulating valve meets the requirements of the process.

(6) The installation of the electrical part of the regulating valve should be carried out according to the relevant electrical equipment construction requirements. If it is a flameproof product, it should be installed according to the requirements of the "Installation Specification for Electrical Equipment in Explosive Hazardous Areas". During use and maintenance, it is strictly prohibited to use electricity to open the cover for repair and to strike the explosion-proof surface in explosive areas. At the same time, do not damage or scratch the explosion-proof surface during disassembly and assembly, and restore it to its original explosion-proof state after maintenance.

(7) After disassembling and repairing the actuator, attention should be paid to oiling and lubrication. Generally, low-speed motors should not be disassembled, washed, or oiled. After assembly, it is also necessary to check whether the valve position matches the valve opening indication.