Beiying Electronic Technology (Shanghai) Co., Ltd
Home>Products>Pipeline air leakage detector PAN341
Pipeline air leakage detector PAN341
The PAN341 positive and negative pressure system air duct and equipment leakage evaluation system (PANDA) and PAN300 series positive and negative pres
Product details

Pipeline air leakage detector PAN341

Positive and negative pressure system air duct and equipment leakage evaluation system(PANDA)

PAN300 series


Positive and negative pressure pipeline evaluation system(PANDA can effectively assist contractors, engineering technicians, and R&D personnel in evaluating the leakage rate of ventilation ducts and equipment. PANDA provides a fast, accurate, and automated pipeline system air leakage testing solution, which is widely used for building energy efficiency.

Complies with international standards

BS EN12237:2003

BS EN1507:2006

DW/143 EUROVENT。


Characteristics and advantages

1. Can complete pipeline air leakage testing under positive and negative pressure conditions
-High air leakage rate: 10-200L/S
-Low air leakage rate: 1-13L/S

2. Accuracy: ± 2.5% of the reading

3. PAN321 model includes TA460-P multifunctional ventilation tester and PVM620 micro pressure gauge
-Automatically calculate and display air leakage in real-time
-Simultaneously display the air leakage factor and static pressure value
-Provide Pass/Tail judgment based on the selected airtightness level
-Automatically convert the actual flow leakage rate to the leakage rate under standard conditions (STP)
-Real time monitoring of changes in atmospheric pressure and temperature
-Data can be stored and easily downloaded, and reports can be generated
-Optional 8934 portable printer

倍迎电子


TA460-P measurement interface




TECHNICAL INDEX

model:PAN300 series

Pressure measurement(PVM620)

Range: ± 3735 Pa (± 15 in. W.G.)

Resolution: 0.1 Pa (0.001 in. W.G)

Accuracy:Reading of1% ± 1 Pa(± 0.005 in. W.G.)

Pipeline static pressure range: ± 2500 Pa (± 10 in. W.G), when the air flow is zero

Airflow measurement(TA460-P)

Wilson radiation flow probe:High leakage range10-200l/s (36-720 m3/hr, 21-424 cfm)

15mm conical nozzle:

Low leakage range: 1-13 l/s

(3.6-46.9 m3/hr, 2-27.5 cfm)

Resolution: 0.01 l/s (0.01 m3/hr, 0.01 cfm)

Accuracy:Reading of± 2.5% ± 0.01 l/s

(± 0.04 m3/hr, ± 0.02 cfm)

temperature measurement(TA460-P)

K-type thermocouple EN60584 (IEC 584)

Atmospheric pressure test(TA460-P)

Range: 690 to 1241 hPa (517.5 to 930.87)mm Hg, 20.36 to 36.648 in. Hg)

Accuracy:Reading of± 2%

Power requirements

Model numberPAN321 * 220-240V, single-phase, 50/60 Hz, 10A

Model numberPAN311 * * 220-240V, single-phase, 50/60 Hz, 10A

Weight:71Kg(157lbs.)

Size (length)X width x height):1,130mmx660mmx510mm

*Model: Includes instruments

**Model: Instrument not included


倍迎电子TA460-P



Pipeline Classification Table

Air tightness

grade

Static pressure limit (Ps)

Limit value of air leakage factor (f)max)

m3 .s-1 m-2


positive pressure

negative pressure


A

500

500

0.027 × pt0.65× 10-3

B

1,000

750

0.009 × pt0.65× 10-3

C

2,000

750

0.003 × pt0.65× 10-3

D

2,000

750

0.001 × pt0.65× 10-3



Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!