1、 Product Overview
As the name suggests, high and low voltage distribution cabinets are distribution equipment used in power supply systems for energy distribution, control, metering, and cable connection. Generally, power supply bureaus and substations use high voltage switchgear,
Then, the low-voltage side of the transformer is stepped down and led out to the low-voltage distribution cabinet. The low-voltage distribution cabinet is connected to various power distribution panels, control boxes, and switch boxes. Inside, some switches, circuit breakers, fuses
A power distribution device that integrates protective devices such as buttons, indicator lights, instruments, and wires to meet the design functional requirements. Commonly known as high and low voltage switchgear or complete sets of high and low voltage electrical equipment.
2、 Model and meaning
3、 Normal usage conditions
1. Surrounding air temperature:- 15C~+40C.
2. Altitude: 1000m and below.
3. Humidity conditions:
The daily average value shall not exceed 95%, and the daily average value of water vapor pressure shall not exceed 2.2KPa.
The monthly average value shall not exceed 90%, and the monthly average value of water vapor pressure shall not exceed 1.8KPa.
4. Seismic intensity: not exceeding 8 degrees.
5. Places without obvious pollution such as corrosive or flammable gases.
Note: When the above normal usage conditions are exceeded, users can negotiate with our company.
4、 Characteristics of container structure
1. The transformer adopts a split box structure:
The transformer body, high-voltage load switch, plug-in fuse, backup current limiting fuse and other high-voltage components are placed in sealed oil tanks, arranged horizontally on both sides of the two boxes, completely separated by partitions. The partitions have insulated through wall sleeves for the connection between the transformer and the load switch, which can be easily removed and replaced without affecting the use of the other box.
2. Advantages of arranging two boxes left and right:
(1) Two boxes do not affect each other:
To prevent the upper oil from flowing into the bottom oil tank due to leakage, resulting in a shortage of oil in the upper oil tank (shortage or lack of oil can cause the operation load switch to arc, posing a danger to equipment and personnel);
Another advantage is that the left and right layout is convenient for maintenance. When the transformer room and load switch room are under maintenance, the two boxes do not affect each other, which is convenient and fast (the transformer oil tank needs to be completely removed before the transformer oil tank can be opened for maintenance, which is extremely inconvenient).
(2) The split box structure solves the pollution problem of transformer oil caused by load switch operation and fuse melting.
5、 Technical parameters
Serial Number | name | unit | Technical Parameter |
1 | rated voltage | kV | 10/0.4 (high/low voltage) |
2 | maximum working voltage | kV | 12 (High Voltage Side) |
3 | Rated frequency | Hz | 50 |
4 | rated capacity | KVA | 150-1600 |
5 | 1-minute power frequency withstand voltage | kV | 35 |
6 | lightning impulse voltage | kV | 75 |
7 | Cooling method |
|
ONAN |
8 | High voltage backup fuse breaking current | kA | 50 |
9 | Plug in fuse for breaking current | kA | 2.5 |
10 | ambient temperature | ℃ | -35~+40 |
11 | Coil allows temperature rise | K | 65 |
12 | No load voltage regulation |
|
+50% or 2×2,5% |
13 | noise level | db | 20 |
14 | protection grade |
|
IP43 |
6、 Load switch
The load switch is oil immersed, three-phase linkage switch, and spring operated mechanism; It can be operated with load for opening and closing, and its opening and closing speed is independent of the magnitude of the operating force. There are two station and four station T-switches availableV-shaped workstations are available for selection.Project/Name | unit | 315A | 630A | |
rated voltage | KV | 12 | 12 | |
Maximum current | A | 315 | 630 | |
Rated frequency | Hz | 50 | 50 | |
Rated short-circuit closing current | kA | 31.5 | 50 | |
Rated short-time withstand current | kA | 12.5 | 50 | |
Rated short-time endurance time | S | 2 | 2 | |
mechanical life | order | 2000 | 2000 | |
lightning impulse test | Alternating pairsgrounds |
KV |
75 | 75 |
isolating fracture | 85 | 85 | ||
1-minute power frequency withstand voltage |
Alternating to ground |
KV |
42 | 42 |
isolating fracture | 48 | 48 | ||
Rated peak withstand current | KA | 31.5 | 50 |
seven、Structure and operational sequence
The appearance and structure of the 10kV prefabricated substation are shown in Figure 2 and Figure 3. The oil tank is divided into two parts: the upper part is the high-voltage oil tank, and the lower part is the transformer oil tank. The two are only electrically connected, and the oil tank is divided into two partsNo way. The schematic diagram is shown in Figure 1“I”“II”The line is a ring network feeder, branch "II" is a transformer branch, and branch "IV" is a low-voltage output. Substations can be used for bothRing power supply system, also availableUsed in terminal systems, conversion is very convenient. “Ⅰ”The line and“Ⅱ”Switching is carried out between the branch precious electricity and the ring network load switch, and at the same time, a backup protection fuse is installed at the high-voltage side incoming end of the transformerAnd plug-in fuses are used to protect the branch from short-circuit faults and overload and over temperature protection. High voltage display devices and lightning arresters can also be installed. The low voltage end of the transformer is measured by a meterOutput after low-voltage circuit breaker.
2. Transformer
New S9 and S11 series three-phase oil immersed transformers with airLow load loss and temperature riseAdvantages such as low noise, low height, etc. The no-load and load losses of the transformer are lower than those of the original S9 type transformerThe compressor has reached the current advanced level in China. The transformer is a fully sealed structure that effectively isolates insulation degradation caused by atmospheric pollution and moisture. Leave 40-90mm of air at the top of the fuel tankThe cushion, along with the ripples on the fuel tank shell, can simultaneously provide heat dissipation and cooling effects, and effectively reduce internal pressure.
8、 Schematic diagram of prefabricated substation
Serial Number |
rated capacity (kVA) |
rated voltage |
pressure regulating range (%) |
Connection group label |
no-load current | Loss (W) |
impedance voltage (%) |
noise (dB) |
temperature rise (k) |
|||||
high pressure (kV) |
low pressure (kV) |
S9 S10/S11 | no-load loss | load loss | ||||||||||
S9 | S10 | S11 | S9/S10/S11 | |||||||||||
1 | 30 |
6
6.3
10 |
0.4
0.69 |
±5
±2×2.5 |
Yyn0
Dyn11 |
2.2 | 2.0 | 130 | 110 | 100 | 600 |
4
4.5 |
55 |
|
2 | 50 | 2.0 | 1.8 | 170 | 150 | 130 | 870 |
top Oil temperature 55 coil 65 |
||||||
3 | 63 | 1.9 | 1.5 | 200 | 180 | 150 | 1049 | |||||||
4 | 80 | 1.7 | 1.2 | 250 | 200 | 180 | 1250 | |||||||
5 | 100 | 1.6 | 1.1 | 290 | 230 | 200 | 1500 | |||||||
6 | 125 | 1.5 | 1.0 | 340 | 270 | 240 | 1800 | |||||||
7 | 160 | 1.4 | 1.0 | 400 | 310 | 280 | 2200 | |||||||
8 | 200 | 1.4 | 0.8 | 480 | 380 | 340 | 2600 | |||||||
9 | 250 | 1.2 | 0.8 | 560 | 460 | 400 | 3050 | |||||||
10 | 315 | 1.1 | 0.7 | 670 | 540 | 480 | 3650 | |||||||
11 | 400 | 1.0 | 0.7 | 800 | 650 | 570 | 4300 | |||||||
12 | 500 | 1.0 | 0.6 | 960 | 780 | 680 | 5150 | |||||||
13 | 630 | 0.9 | 0.6 | 1200 | 920 | 810 | 6200 | |||||||
14 | 800 | 0.8 | 0.6 | 1400 | 1120 | 980 | 7500 | |||||||
15 | 1000 | 0.7 | 0.5 | 1700 | 1320 | 1150 | 10300 | |||||||
16 | 1250 | 0.6 | 0.5 | 1950 | 1560 | 1360 | 12000 | |||||||
17 | 1600 | 0.6 | 0.5 | 2400 | 1880 | 1640 | 14500 |
9、 Ordering Notice
The parameters in this plan are the standard configuration provided by our company. If the customer has no specific requirements, the company will supply according to the standard configuration. If it exceeds the requirements of this plan, please explain separately.