Function Description of SGK Fire Machinery Emergency Start Device

SGK消防机械应急启动装置,消防机械应急启动柜
SGK Fire Machinery Emergency Start Device, Fire Machinery Emergency Start Cabinet

  SGK Fire Machinery Emergency Start DeviceAlso known as the emergency starting cabinet for firefighting machinery, it is used to forcibly start the fire pump during fire fighting, ensuring timely control and extinguishing of the fire. In some special occasions, the configuration of the emergency starting device for firefighting machinery is necessary. The specific requirements and functions are as follows.


1、 According to Article 11.0.12 of the Technical Specification for Fire Water Supply and Hydrant Systems GB50974-2014, "The fire water pump control cabinet should be equipped with a manual mechanical pump start function, and should ensure that personnel with management authority can start the fire water pump in emergency situations when the control circuit inside the control cabinet fails. When manually operated, the fire water pump should work normally within 5 minutes of the alarm

This article is a mandatory provision (in bold). Pressure start, remote start, and hard wire start are all achieved through relays to automatically start the pump. If the relay and weak current signal fail and the fire pump cannot be started automatically, the "emergency start device for fire machinery" set in the fire pump control cabinet should be relied on to directly start the fire pump. When the weak current signal and hard wire start relay fail and the secondary circuit and electrical faults in the fire pump control cabinet cannot make the fire pump start automatically or manually, in case of a fire emergency, this article stipulates that as long as the control circuit in the fire pump control cabinet is damaged under normal power supply, the pump can be forcibly started directly to ensure timely firefighting. This "emergency start device for fire machinery" is The mechanical interlocking device is directly driven, To achieve the device of directly starting the fire pump, Shenyang Shengong SGK Fire Machinery Emergency Start Device has been developed and launched.

This device can be configured with two methods: star delta start and voltage reduction start. The starting handle of the "Fire Machinery Emergency Start Device" is usually in a stopped state (with a lock), and must be operated by authorized management personnel in case of emergency fire (the mechanical emergency start device is locked and is usually kept by authorized personnel, and the time from alarm to normal water supply of the fire pump is not more than 5 minutes, including the time for management personnel to travel from the control room to the pump room and the time from forced start of the fire pump to normal water supply).


II SGK fire machinery emergency start device function (product configuration can be implemented according to several user situations)


1. The fire and sprinkler pump control cabinets have been installed, and an independent fire machinery emergency start control cabinet can be added in front of the fire pump and sprinkler pump control cabinets. The power supply is led from the dual power cabinet, and the output of the "SGK fire machinery emergency start device" is connected to the output terminal inside the original control cabinet to achieve direct emergency start of the fire pump.


2. When the control cabinets of the fire pump and sprinkler pump adopt the star delta starting mode, two sets of "SGK fire machinery emergency starting devices" are used to start pump 1 # and pump 2 # respectively. In case of a fire alarm, either pump 1 # or pump 2 # can be started; When starting, press the handle 90 °. After starting, wait for the actual situation of the fire and have someone with management authority manually stop the pump (automatic pump stop or manual pump stop in case of fire alarm is not allowed).


3. When the control cabinets of the fire pump and sprinkler pump are in the depressurization starting mode, a set of "SGK fire machinery emergency starting devices" will start the 1 # and 2 # pumps respectively. In case of a fire alarm, either pump 1 # or 2 # can be started. When starting, pressing the handle 90 ° to the left will start the 1 # pump, and pressing it 90 ° to the right will start the 2 # pump, both of which are forced starts. After starting, the pump must be manually stopped by a person with management authority based on the actual situation of the fire (automatic pump stop or manual pump stop in case of a fire alarm is not allowed).


4. If both the user and the owner purchase our company's fire pump and sprinkler pump control cabinet, that is, the integrated fire and sprinkler pump control cabinet (with "SGK fire machinery emergency start device") has the same function as above, in order to meet the requirements of the new regulations and standards, our company's products will ensure passing the fire inspection.


Since the national introduction of the GB50974-2014 Technical Specification for Fire Water Supply and Hydrant Systems, the company has focused all personnel on learning the new specifications and requirements. In response to the new specifications and requirements, the R&D department of the company has concentrated all its efforts and, after several months of trial and error, researched and developed a high-level fire water tank flow switch (i.e., a fire pressure stabilizing equipment flow switch control direct start fire pump device) and a SGK fire machinery emergency start device.


The flow switch of the high-level fire water tank is installed on the water pipe of the high-level fire water tank. When the water level of the high-level fire water tank drops, the flow switch on the outlet pipe of the water tank senses the flow of water and converts it into an electrical signal, directly starting the fire water pump. This ensures the reliability of the fire water supply in case of a fire alarm.

SGK fire machinery emergency starting device, which has two starting modes: star delta and self coupling voltage reduction. When the control circuit inside the fire pump control cabinet malfunctions and cannot automatically start the fire pump, immediate repair will encounter limitations in personnel quality and time. Fire alarm is also an emergency situation. This device can ensure that under normal power supply conditions, regardless of the circuit, it can be forcibly started, ensuring the timeliness of fire extinguishing. The above two devices play a dual insurance role in our fire water supply system in case of sudden fire. These two new products have been successfully developed and recognized by the fire department. We welcome new and old customers to inquire and visit us.

沈阳申工消防机械应急启动装置
Shenyang Shengong Fire Machinery Emergency Start Device

 
消防机械应急启动柜面板
Fire machinery emergency start cabinet panel


 
消防机械应急启动柜控制手柄
Control handle for emergency start-up cabinet of fire-fighting machinery