1、 Product Overview
The SNDEB-AI/AU series AC current transmitter converts AC signals from AC transformers into standard process signals for central monitoring of motors, pumps, or heating networks in DCS, monitoring power lines and their currents.
High reliability isolation of input, output, and power ports.
2、 Signal adjustment and explanation
When the product is working normally, the ON indicator light on the panel should be on.
There are two potentiometers on the product panel for signal adjustment
When conducting the following debugging, please power on and preheat the product for 30 minutes to achieve optimal stability.
1. Zero signal adjustment: When the input signal is zero, the output signal of the transmitter can be adjusted to the desired minimum value by adjusting the zero potentiometer.
2. Full scale signal adjustment: Input the signal to full scale (maximum value), and adjust the transmission signal to the required maximum range value through the range potentiometer.
3. Repeat operations 1 and 2 until they reach the desired value.
1、 Model meaning
2、 Product selection
▲SNDEB-AIXXX
Example: SNDEB-AI1B1, One in one out, AC current input 0-5A, output 4-20mA.
▲SNDEB-AUXXX
Example: SNDEB-AU1E1, One in one out, AC voltage input 0-300V, output is
4-20mA.
3、 Technical parameters
▲ Input terminal
Input current range: AC 0-20A
Input voltage range: AC 0-1000V
Frequency range: 40Hz-60Hz
▲ Output terminal
Output signal: 4-20mA; 0-20mA; 0-5V; 0-10V
Output load resistance: RL ≤ 500 Ω (when outputting as a current signal)
RL ≤ 10K Ω (when outputting as a voltage signal)
▲ Basic parameters
Power supply: AC85-265V or DC24V, ± 10%
Rated power consumption: ≤ 1W (one in one out, DC24V power supply, 20mA output)
≤ 1.5W (one in one out, AC220V power supply, 20mA output)
Basic accuracy: ≤ 0.5% F.S.
Temperature drift: 0.02% F.S./℃ (-20 ℃~+55 ℃)
Response time: ≤ 400mS(0-90%)(TYP)
Insulation strength: 2000V AC/1min (between input, output, and power supply)
Insulation resistance: ≥ 100M Ω (between input, output, and power supply)
Working temperature range:- 20℃~+55℃
Electromagnetic compatibility: Load GB/T18268.1 (IEC61326-1)