instrument for drawing circles check
speak bright
use
environment
ambient temperature
0~50
relative humidity
≤85RH Avoid strong corrosive gases
Supply Voltage
Conventional AC220V+10-15% (50Hz ± 2Hz)
Special type AC85~260V - Switching Power Supply DC24V ± 2V - Switching Power Supply
power consumption
≤6W
input
signal
analog quantity
Thermocouples: Standard thermocouples - B, S, K, E, J, T, WRe3-25, etc
Resistance: Standard thermistor - Pt10, Pt100.1, Cu50, Cu100 and other remote pressure resistors, etc
Current: 0~10mA, 4~20mA, 0~20mA, etc. - Input impedance ≤ 250 Ω
Voltage: 0~5V, 1~5V, mV, etc. - Input impedance ≥ 250K Ω
Switching quantity
Pulse signal: waveform - rectangular, sine or triangular wave
Radiance - greater than 4V (or as per user requirements)
Scope -0~10KHz (or as per user requirements)
Contact signal: electrical contact input signal
output
signal
analog output
DC 0~10mA (load resistance ≤ 750 Ω) DC 4~20mA (load resistance ≤ 500 Ω)
DC 0~5V (load resistance ≥ 250K Ω) DC 1~5V (load resistance ≥ 250K Ω)
Switching Output
Relay control output - relay ON/OFF return differential. AC 220V/3A DC 24V/5A (resistive load)
Controllable silicon control output - SCR (thyristor zero crossing trigger pulse) output, 0.5A/400V
Solid state relay output - SSR (Solid state relay control signal) output, 6~24V/30mA (voltage not adjustable)
Bidirectional thyristor output - SOT thyristor output, 5A/400V
Communication output
Interface Method - Standard Serial Bidirectional Communication Interface RS-485 RS-232 C, RS-422, etc
Baud rate -300~9600Bps instrument internal free setting
Feed output
DC 24V load ≤ 30mA
measurement accuracy
± 0.2% FS ± 1 word or ± 0.5% FS ± 1 word
resolution
± 1 word
measuring range
-1999~9999 words
Display mode
-1999~9999 word measurement value display -1999~9999 character setting value display, LED working status display
way
control/The alarm method is to bring back the upper or lower limit alarm of the difference (which can be freely set by the user)
Control accuracy
± 1 word
temperature compensation
0~50 ℃ digital temperature automatic compensation
Print Control
You can choose to directly connect various types of string printers(such as LQ-300K, TPuP series micro printers, etc.), with a printing interface of RS-232C
Printing accuracy
Same instrument accuracy
Parameter setting
Panel touch sensitive button settings, parameter settings permanently saved after power failure, parameter settings password locked
Protection method
Input circuit disconnection alarm(When thermocouple or resistor is input), LED indicator for output status of circuit breaker, input over/under range alarm
Power undervoltage automatic reset, abnormal operation automatic reset (Watch Dog)

SWP-LED series digital display manual operator type spectrograph

Model
code
explain
SWP-N
□□
-□
-□□
/□□
-□
-□
-□
New generation manual operator
Appearance characteristics
D
S
Horizontal display instrument
Vertical display instrument
External dimensions
4
7
8
9
96×48mm
72×72mm
160×80mm,80×160mm
96×96mm
Control function
35
Manual operator
Communication method
Refer to "Communication Methods"
Control output mode
Refer to "Control Output Mode"
Transmission output mode
Refer to "Transmission Output Method"
PVInput Type
□□
Refer to 'Input Types'
SVInput Type
□□
Refer to 'Input Types'
first
Alarm method
H
L
Upper limit alarm
Lower limit alarm
second
Alarm method
H
L
Upper limit alarm
Lower limit alarm
Feed output
P
DC24VFeed output
Power supply mode
W
T
DC24Vpower supply
AC85-260VPower Supply (Switching Power Supply)
AC220VPower supply (linear power supply, can be omitted)
SWP-LED Series Light Column Display Manual Operator Type Spectrograph

Model
code
explain
SWP-N
T
□□
-□
-□□
/□□
-□
-□
-□
-□
New generation manual operator
External dimensions
8
160×80mm, 80×160mm
Control function
35
Manual operator
Communication method
Refer to "Communication Methods"
Control output mode
Refer to "Control Output Mode"
Transmission output mode
Refer to "Transmission Output Method"
PVInput Type
□□
Refer to 'Input Types'
SVInput Type
□□
Refer to 'Input Types'
The first alarm method
H
L
Upper limit alarm
Lower limit alarm
Second alarm method
H
L
Upper limit alarm
Lower limit alarm
Feed output
P
DC24VFeed output
Power supply mode
W
T
DC24Vpower supply
AC85-260VPower Supply (Switching Power Supply)
AC220VPower supply (linear power supply, can be omitted)
Appearance characteristics
X
horizontal type
Vertical

★ Communication method:

code
0
2
3
4
8
9
Communication method
No communication
RS-232
lpt
RS-422
RS-485
Special specifications
★ Communication protocol: SWP communication protocol is used at the factory.
If the user has ordered a special communication protocol, please indicate it when placing the order.
When selecting instruments with printing ports, some instruments cannot meet the printing function. When ordering, choose instruments that can meet their requirements in terms of functionality.
★ Control output mode:

Selection code
0
1
2
3
4
5
6
7
8
9
Output
no-output
relay
4~20mA
0~10mA
1~5V
0~5V
SCR output
SSR output
Special specifications
SOT output
SCR thyristor zero crossing trigger pulse output SSR solid-state relay control output SOT bidirectional thyristor output
★ Transmission output mode:

Selection code
0
2
3
4
5
8
Output
no-output
4~20mA
0~10mA
1~5V
0~5V
Special specifications

★ Input type:

code
Input Type
measuring range
code
Input Type
measuring range
code
Input Type
measuring range
01
B
400~1800℃
09
Pt100.1
-199.9~320.0℃
17
30~350Ω
-1999~9999 d
02
S
0~1600℃
10
Cu50
-50.0~150.0℃
18
Special specifications
User to be determined
03
K
0~1300℃
11
Cu100
-50.0~150.0℃
19
4-20mA square meter
-1999~9999 d
04
E
0~1000℃
12
4~20mA
-1999~9999 d
20
0-10mA square root
-1999~9999 d
05
T
-199.9~320.0℃
13
0~10mA
-1999~9999 d
21
1~5V square root
-1999~9999 d
06
J
0~1200℃
14
1~5V
-1999~9999 d
22
0~5V square root
-1999~9999 d
07
WRe3~25
0~2300℃
15
0~5V
-1999~9999 d
23
Switchable input
08
Pt100
-200~650℃
16
0~20mA
-1999~9999 d

Due to the limited number of wiring terminals, ND435 and ND735 should be ordered according to the specific model (as close as possible to the selection catalog) and refer to the random wiring diagram.