X49H flat boiler water level gauge
The X49H flat water level gauge (also known as liquid level indicator) produced by Jiangsu Meiante Instrument is suitable for indicating liquid and wa
Product details

X49H Flat Plate Boiler Water Level Gauge Usage:

Flat water level gauge (also known as liquid level indicator) is suitable for indicating liquid and water level on industrial steam boilers, steam locomotive boilers, and reservoirs.

Common faults and troubleshooting methods:
Common fault locations
Reason for malfunction
processing method
Valve connection leakage
Poor sealing connection between the valve and the main body
Tighten the nut or seal the graphite ring with increased transparency
The graphite lining of the plug is worn out
Tighten the nut and replace the bushing with a new one if there is no effect
Leakage of the main sealing surface
The sealing gasket is broken or there are impurities on the sealing surface
Remove debris and replace with a new pressure pad
The sturdy components are not tightened
Moderately tighten
Display color code
Unclear light transmission
Due to pollution, immediately discharge the sewage or clean it by closing the steam and water valve and scrubbing it several times
When installing prisms (or glass plates), the pressure should be evenly applied, and the thread tightening should be done in a cross pattern in several times (see figure below) to achieve the desired torque20-39.4Nmuntil.

x49h锅炉平板水位计结构原理图x49h锅炉平板水位计结构原理图

Main technical parameters:

model
X49H DN25mm
nominal pressure
1.6MPa
2.5 MPa
4.0 MPa
test pressure
2.45 MPa
3.8 MPa
6.0 MPa
Baoli Time
3Min
3Min
3Min
medium temperature
t≤205
t≤225
t≤250
Installment Center Distance
300350440mm
Video height
165~195mm
Observation distance
15m
medium temperature
t≤250

Usage and maintenance:

1. When using the water level gauge, it should be preheated for 20-30 minutes first. After the glass plate has reached a certain temperature, the valves at both ends can be opened to allow water or other media to enter.

2. During use, it is required to regularly discharge pollutants to avoid blockage of channels due to erosion and false water levels.

3. When replacing the glass panel, the debris and iron filings on the sealing surface should be removed.

Boiler water level gauge/Boiler flat water level gauge/X49H-25/X49H-40