Yongnuo Electric Co., Ltd
Home>Products>YN-700 microcomputer comprehensive protection and measurement device
YN-700 microcomputer comprehensive protection and measurement device
overview
Product details


overview

YN-700 series microcomputer comprehensive protection and measurement device is a high-performance microcomputer comprehensive protection and measurement device that integrates protection, measurement, metering, control, and communication. This series of protection and measurement devices uses an advanced 32-bit high-performance embedded controller as the main CPU, adopts fully isolated, high-speed and safe fieldbus technology, built-in operation circuit, and large screen Chinese character liquid display. Its functions, performance and technical indicators are at the leading level in China. All models of devices can be installed locally on switchgear with voltage levels of 35KV and below.

FEATURES
The design concept of the basic hierarchical distributed electrical monitoring and management system is that one component (one interval) corresponds to one device, each interval has independent functions, and each device is connected through a networkState flexibility greatly improves the reliability of the entire system, and any device failure does not affect the normal operation of other devices and systems.
Adopting advanced 32-bit high-performance embedded processors as the main CPU, the protection module is completely separated from other modules (telemetry, remote control, remote signaling) in software design: the protection function does not rely on communicationThe communication function does not affect the normal operation of protection even if the network is paralyzed.
Due to the use of safe and reliable fieldbus technology, large data can be transmitted through a communication interface, and the information of each device can be shared at the communication layer, saving control cables and simplifying secondary wiring.
High speed RS485 network, supporting dual networks, with an actual transmission rate of up to 115.2Kbps.
Built in operation circuit and anti bounce circuit, further simplifying the design and wiring of the switchgear, and improving reliability.
Adopting a fully enclosed back plug-in structure, with internal strong and weak electrical separation, and carefully designed anti-interference circuits, the device's anti electromagnetic interference and seismic resistance are greatly improved, fully meeting various EMC tests specified in IEC255 and GB/T14598.
The device adopts a fully localized large screen LCD display, with a user-friendly human-machine interface and easy operation through a small keyboard. The tree shaped menu, remote signaling, telemetry, trip reports, alarm reports, and other internal information of the device can be displayed in Chinese on the LCD, making debugging, operation, and maintenance convenient.

Technical Parameter

rated data
Power consumption
DC power supply: 220V soil 20% or 110V soil 20%
DC circuit: ≤ 5W
AC power supply: 85V to 265V
AC voltage circuit:< 0.5VA/phase (at rated 220V)
AC voltage: 100/V, 100V
AC current circuit:< 0.5VA/phase (rated at 5A)
AC current: 5A
<0.1VA/phase (rated at 1A)
Frequency: 50Hz


work environment
connectPoint capacity
Environmental temperature: (-10 ° C~+55 ° C) to ensure normal operation
Jumping and closing outlet (normally open contact): 5A, DC220V (suction)
Relative humidity: 5~95%
Signal outlet (normally open contact): 5A , DC220V (suction)
Atmospheric pressure: 86~ 106KPa
Switching input with empty contact input, conducting current<10mA


Featured Features
Display in both Chinese and English, easy to switch between

measurement accuracy

Frequency 45Hz-65Hz Self applicable
P. Q, COS: Level 2
Programmable input and output
Electricity integration accuracy: Level 2

Frequency: 0.02Hz
thermal stability Remote signaling resolution:< 2ms
2 times the rated current for continuous operation
GPS timing accuracy:< 1ms

10 times the rated current can run continuously for 10 seconds

Voltage and current: Level 0.5

40 times the rated current can run continuously for 1 second

anti-jamming performance
Capable of withstanding the strict level IV electrostatic discharge test specified in GB/T14598.14-1998 (idt IE C255-22-2) standard.
Can withstand the radiation electromagnetic field interference test of severity level Ill specified in GB/T14598.9-1995 (idt IEC255-22-3) standard.
Capable of withstanding 1M Hz pulse group interference test with severity level Ill. as specified in GB/T14598.13-1998QdtlEC255-22-1) standard.
Capable of withstanding the rapid transient interference test of severity level IV specified in GB/T14598.10-1996 (idt IE C255-22-4) standard.

Mechanical properties

Vibration:The device should be able to withstand the vibration durability test with a severity level of 1 as specified in GB/T11287.

The device should be able to withstand the vibration response capability test with a severity level of 1 as specified in GB/T11287.

to attack: The device should be able to withstand the impact durability test with a severity level of 1 as specified in GB/T14537.

The device should be able to withstand the impact response capability test with a severity level of 1 as specified in GB/T14537.

Collision: The device should be able to withstand a collision test with a severity level of 1 as specified in GB/T14537.
Moisture and heat resistance performance: Can withstand the damp heat test specified in Chapter 21 of GB7261.

Mainly following standards
GB/T14598.13-1998 (idt IEC 255-22-1) Electrical interference tests for measuring relays and protective devices
Chapter 1: 1MHz Pulse Group Interference Test
GB/T14598.14-1998 (idt IEC 255-22-2) Electrical interference tests for measuring relays and protective devices
Article 2: Electrostatic Discharge Test
GB/T14598.9-2007 (idt IEC 255-22-3) Electrical interference tests for measuring relays and protective devices
Article 3: Radiated Electromagnetic Field Interference Test
GB/T14598.10-201 O (idt IEC 255-22-4) Electrical interference tests for relays and protective devices
Article 4: Fast Transient Interference Test
Other indicators meet the requirements of DL478-2008 "General Technical Conditions for Static Relay Protection and Safety Automatic Equipment"

Appearance and opening size

Model Selection Table

Wiring diagram

YN-710 line protection and measurement device is suitable for directional line protection and measurement in non directly grounded systems or systems grounded through arc suppression coils (including low resistance grounding) with voltage levels of 35KV and below

(For wiring diagrams of other models, please refer to the instruction manual)