overview
YN-700 series microcomputer comprehensive protection and measurement device is a high-performance microcomputer comprehensive protection and measurement device that integrates protection, measurement, metering, control, and communication. This series of protection and measurement devices uses an advanced 32-bit high-performance embedded controller as the main CPU, adopts fully isolated, high-speed and safe fieldbus technology, built-in operation circuit, and large screen Chinese character liquid display. Its functions, performance and technical indicators are at the leading level in China. All models of devices can be installed locally on switchgear with voltage levels of 35KV and below.
Technical Parameter
rated data |
Power consumption |
DC power supply: 220V soil 20% or 110V soil 20% |
DC circuit: ≤ 5W |
AC power supply: 85V to 265V |
AC voltage circuit:< 0.5VA/phase (at rated 220V) |
AC voltage: 100/V, 100V |
AC current circuit:< 0.5VA/phase (rated at 5A) |
AC current: 5A |
<0.1VA/phase (rated at 1A) |
Frequency: 50Hz |
|
|
|
work environment |
connectPoint capacity |
Environmental temperature: (-10 ° C~+55 ° C) to ensure normal operation |
Jumping and closing outlet (normally open contact): 5A, DC220V (suction) |
Relative humidity: 5~95% |
Signal outlet (normally open contact): 5A , DC220V (suction) |
Atmospheric pressure: 86~ 106KPa |
Switching input with empty contact input, conducting current<10mA |
|
|
Featured Features |
|
Display in both Chinese and English, easy to switch between |
measurement accuracy |
Frequency 45Hz-65Hz Self applicable |
P. Q, COS: Level 2 |
Programmable input and output |
Electricity integration accuracy: Level 2 |
|
Frequency: 0.02Hz |
thermal stability |
Remote signaling resolution:< 2ms |
2 times the rated current for continuous operation |
GPS timing accuracy:< 1ms |
10 times the rated current can run continuously for 10 seconds |
Voltage and current: Level 0.5 |
40 times the rated current can run continuously for 1 second |
|
anti-jamming performance |
Capable of withstanding the strict level IV electrostatic discharge test specified in GB/T14598.14-1998 (idt IE C255-22-2) standard. |
Can withstand the radiation electromagnetic field interference test of severity level Ill specified in GB/T14598.9-1995 (idt IEC255-22-3) standard. |
Capable of withstanding 1M Hz pulse group interference test with severity level Ill. as specified in GB/T14598.13-1998QdtlEC255-22-1) standard. |
Capable of withstanding the rapid transient interference test of severity level IV specified in GB/T14598.10-1996 (idt IE C255-22-4) standard. |
|
Mechanical properties |
Vibration:The device should be able to withstand the vibration durability test with a severity level of 1 as specified in GB/T11287. The device should be able to withstand the vibration response capability test with a severity level of 1 as specified in GB/T11287. |
to attack: The device should be able to withstand the impact durability test with a severity level of 1 as specified in GB/T14537. The device should be able to withstand the impact response capability test with a severity level of 1 as specified in GB/T14537. |
Collision: The device should be able to withstand a collision test with a severity level of 1 as specified in GB/T14537. |
Moisture and heat resistance performance: Can withstand the damp heat test specified in Chapter 21 of GB7261. |
|
Mainly following standards |
GB/T14598.13-1998 (idt IEC 255-22-1) Electrical interference tests for measuring relays and protective devices |
Chapter 1: 1MHz Pulse Group Interference Test |
GB/T14598.14-1998 (idt IEC 255-22-2) Electrical interference tests for measuring relays and protective devices |
Article 2: Electrostatic Discharge Test |
GB/T14598.9-2007 (idt IEC 255-22-3) Electrical interference tests for measuring relays and protective devices |
Article 3: Radiated Electromagnetic Field Interference Test |
GB/T14598.10-201 O (idt IEC 255-22-4) Electrical interference tests for relays and protective devices |
Article 4: Fast Transient Interference Test |
Other indicators meet the requirements of DL478-2008 "General Technical Conditions for Static Relay Protection and Safety Automatic Equipment" |
Appearance and opening size
Model Selection Table
Wiring diagram
YN-710 line protection and measurement device is suitable for directional line protection and measurement in non directly grounded systems or systems grounded through arc suppression coils (including low resistance grounding) with voltage levels of 35KV and below
(For wiring diagrams of other models, please refer to the instruction manual)