6Instruction manual for three-phase power collection module of circuit
XY-E6343-9D53
keywordThree phase four wire detection, multi-channel power detectionRS485CommunicationMODBUSProtocol, direct effective value measurement, multi loop power measurement
1、 Product Overview
This product is a real-time measurement and acquisition device6The comprehensive acquisition module for three-phase four wire power data in the circuit can be used for three-phase three wire or three-phase four wire,High precision current and voltage transformers are used to achieve isolation and sensing of each channel signal, and dedicated signal measurement is employed24The high-precision true RMS measurement chip can accurately measure various waveform parameters such as current, voltage, power, etc., with high accuracy and good stability; Adopting standardsRS-485busMODBUS-RTUagreement. Widely used in street lamp monitoring, production automation detection, computer room monitoring, enterprise energy consumption detection big data analysis, etc. This product has the following characteristics:
Ø 6Three phase circuit combination measurement, only need to be connected1The total incoming voltage and integration of the road are high in cost-effectiveness;
Ø 6Loop synchronous sampling is independent of each otherA/DThe fastest way is to60mSIt can be completed6Data collection of all electrical parameters on the road;
Ø High precision, using24positionA/DSampling, dynamic range1000:1The linear range of current can reach0.1%;
Ø Good stability, measurement accuracy is not affected by environmental temperature;
Ø have2Road switch input2Remote control output of road relay;
Ø Communication interface:RS232/RS485; Network port;
Ø Communication protocol:modbus RTU/TCP;
IIProduct model
XY-6343-9D53 6Circuit three-phase four wire electricity collector(9-30VPower Supply,RS485interface,belt4Road switch input+3Road relay output)
XY-6343-9D53Explanation:
6:6Circuit;
3:3Phase electric quantity;
4:4Road switch input;
3:3Road switch output;
9:RS232 +RS485+ TCP;
D5:Length of guide rail shell30CM;
3:working voltage9-30VDC;
3、 Performance indicators
Ø Accuracy level: Voltage, current:0.2%FSOther factors such as power:0.5%FS;
Ø Current range:0~5AAC (Optional external open type transformer method);
Ø Voltage range:0-500VAC
Ø Working temperature:-20℃~+60℃;
Ø Data update time:600mS(default);
Ø Isolation voltage resistance:>2500V DC;
Ø Auxiliary power supply: +24V DC(9V~30V);
Ø Rated power consumption:<5W;
Ø Output interface:RS232+RS485+TCP;
Ø Data output: voltage, current, active power of each phase, total active and reactive power, power factor, apparent power, forward power, reverse power, etc;
Ø Communication baud rate:1200、2400、4800、9600、19200、38400、115200 bps;
Ø Data format: no verification8A data bit1A stop position
Ø Communication protocol:MODBUS-RTU/MODBUS-TCPagreement;
Ø Lightning surge:2KV;
Default parameter: Communication address1Number, baud rate9600Without verification,8Data bits;
4、 Product appearance and size
Figure 1. Product Physical Image (Rail Installation)
Appearance dimensions:300X110X60mm
5、 Product wiring instructions
Figure 2. Product Wiring Reference Diagram
Table 1: Pin Definition
|
function |
label |
definition |
function |
label |
definition |
|
1Circuit three-phase current input |
IA1- |
1loopAPhase current outgoing line |
2Circuit three-phase current input |
IA2- |
2loopAPhase current outgoing line |
|
IA1+ |
1loopAPhase current incoming line |
IA2+ |
2loopAPhase current incoming line |
||
|
IB1- |
1loopBPhase current outgoing line |
IB2- |
2loopBPhase current outgoing line |
||
|
IB1+ |
1loopBPhase current incoming line |
IB2+ |
2loopBPhase current incoming line |
||
|
IC1- |
1loopCPhase current outgoing line |
IC2- |
2loopCPhase current outgoing line |
||
|
IC1+ |
1loopCPhase current incoming line |
IC2+ |
2loopCPhase current incoming line |
||
|
3Circuit three-phase current input |
IA3- |
3loopAPhase current outgoing line |
4Circuit three-phase current input |
IA4- |
4loopAPhase current outgoing line |
|
IA3+ |
3loopAPhase current incoming line |
IA4+ |
4loopAPhase current incoming line |
||
|
IB3- |
3loopBPhase current outgoing line |
IB4- |
4loopBPhase current outgoing line |
||
|
IB3+ |
3loopBPhase current incoming line |
IB4+ |
4loopBPhase current incoming line |
||
|
IC3- |
3loopCPhase current outgoing line |
IC4- |
4loopCPhase current outgoing line |
||
|
IC3+ |
3loopCPhase current incoming line |
IC4+ |
4loopCPhase current incoming line |
||
|
5Circuit three-phase current input |
IA5- |
5loopAPhase current outgoing line |
6Circuit three-phase current input |
IA6- |
6loopAPhase current outgoing line |
|
IA5+ |
5loopAPhase current incoming line |
IA6+ |
6loopAPhase current incoming line |
||
|
IB5- |
5loopBPhase current outgoing line |
IB6- |
6loopBPhase current outgoing line |
||
|
IB5+ |
5loopBPhase current incoming line |
IB6+ |
6loopBPhase current incoming line |
||
|
IC5- |
5loopCPhase current outgoing line |
IC6- |
6loopCPhase current outgoing line |
||
|
IC5+ |
5loopCPhase current incoming line |
IC6+ |
6loopCPhase current incoming line |
||
|
Switching input |
IN1 |
Switching input1 |
Relay |
COM1 |
relay1Common terminal |
|
IN2 |
Switching input2 |
NO1 |
relay1Output normally open contact |
||
|
IN3 |
Switching input3 |
COM2 |
relay2Common terminal |
||
|
IN4 |
Switching input4 |
NO2 |
relay2Output normally open contact |
||
|
VCC |
Switching input power supplyVCC |
COM3 |
relay3Common terminal |
||
|
GND |
Switch input common terminal |
NO3 |
relay3Output normally open contact |
||
|
Three phase total voltage input |
A |
APhase voltage input |
RS232communication |
Tx |
RS232Data sender |
|
B |
BPhase voltage input |
Rx |
RS232Data receiving end |
||
|
C |
CPhase voltage input |
GND |
RS232Communication grounding |
||
|
N |
Voltage center line |
TCPcommunication |
TCP |
Ethernet communication |
|
|
Auxiliary power supply |
VCC |
Positive pole of power supply |
485communication |
D+ |
RS485communicationD+ |
|
GND |
Negative pole of power supply |
D- |
RS485communicationD- |
VIregister table
function code3、4、6、16
|
Register address |
Register content |
quantity |
state |
describe |
|
|
public |
0000 |
Switching input1 |
2 |
read only |
Switch input status |
|
0002 |
Switching input2 |
2 |
read only |
Switch input status |
|
|
0004 |
Switching input3 |
2 |
read only |
Switch input status |
|
|
0006 |
Switching input4 |
2 |
read only |
Switch input status |
|
|
0008 |
Relay1 |
2 |
Reading and writing |
Relay output status |
|
|
0010 |
Relay2 |
2 |
Reading and writing |
Relay output status |
|
|
0012 |
Relay3 |
2 |
Reading and writing |
Relay output status |
|
|
0014 |
frequency |
2 |
read only |
grid frequency |