6-circuit three-phase power acquisition module
This product is a comprehensive acquisition module for real-time measurement and collection of 6-circuit three-phase four wire power data. It can be t
Product details

6Instruction manual for three-phase power collection module of circuit

XY-E6343-9D53

keywordThree phase four wire detection, multi-channel power detectionRS485CommunicationMODBUSProtocol, direct effective value measurement, multi loop power measurement

1、 Product Overview

This product is a real-time measurement and acquisition device6The comprehensive acquisition module for three-phase four wire power data in the circuit can be used for three-phase three wire or three-phase four wire,High precision current and voltage transformers are used to achieve isolation and sensing of each channel signal, and dedicated signal measurement is employed24The high-precision true RMS measurement chip can accurately measure various waveform parameters such as current, voltage, power, etc., with high accuracy and good stability; Adopting standardsRS-485busMODBUS-RTUagreement. Widely used in street lamp monitoring, production automation detection, computer room monitoring, enterprise energy consumption detection big data analysis, etc. This product has the following characteristics:

Ø 6Three phase circuit combination measurement, only need to be connected1The total incoming voltage and integration of the road are high in cost-effectiveness;

Ø 6Loop synchronous sampling is independent of each otherA/DThe fastest way is to60mSIt can be completed6Data collection of all electrical parameters on the road;

Ø High precision, using24positionA/DSampling, dynamic range10001The linear range of current can reach0.1%

Ø Good stability, measurement accuracy is not affected by environmental temperature;

Ø have2Road switch input2Remote control output of road relay;

Ø Communication interface:RS232/RS485; Network port;

Ø Communication protocol:modbus RTU/TCP

IIProduct model

XY-6343-9D53 6Circuit three-phase four wire electricity collector(9-30VPower Supply,RS485interface,belt4Road switch input+3Road relay output)

XY-6343-9D53Explanation:

66Circuit;

33Phase electric quantity;

44Road switch input;

33Road switch output;

9RS232 +RS485+ TCP

D5Length of guide rail shell30CM

3working voltage9-30VDC

3、 Performance indicators

Ø Accuracy level: Voltage, current:0.2%FSOther factors such as power:0.5%FS

Ø Current range:0~5AAC (Optional external open type transformer method)

Ø Voltage range:0-500VAC

Ø Working temperature:-20℃+60℃

Ø Data update time:600mS(default);

Ø Isolation voltage resistance:>2500V DC

Ø Auxiliary power supply: +24V DC(9V~30V)

Ø Rated power consumption:<5W

Ø Output interface:RS232+RS485+TCP

Ø Data output: voltage, current, active power of each phase, total active and reactive power, power factor, apparent power, forward power, reverse power, etc;

Ø Communication baud rate:12002400480096001920038400115200 bps

Ø Data format: no verification8A data bit1A stop position

Ø Communication protocol:MODBUS-RTU/MODBUS-TCPagreement;

Ø Lightning surge:2KV

Default parameter: Communication address1Number, baud rate9600Without verification,8Data bits;

4、 Product appearance and size

Figure 1. Product Physical Image (Rail Installation)

Appearance dimensions:300X110X60mm

5、 Product wiring instructions

Figure 2. Product Wiring Reference Diagram

Table 1: Pin Definition

function

label

definition

function

label

definition

1Circuit three-phase current input

IA1-

1loopAPhase current outgoing line

2Circuit three-phase current input

IA2-

2loopAPhase current outgoing line

IA1+

1loopAPhase current incoming line

IA2+

2loopAPhase current incoming line

IB1-

1loopBPhase current outgoing line

IB2-

2loopBPhase current outgoing line

IB1+

1loopBPhase current incoming line

IB2+

2loopBPhase current incoming line

IC1-

1loopCPhase current outgoing line

IC2-

2loopCPhase current outgoing line

IC1+

1loopCPhase current incoming line

IC2+

2loopCPhase current incoming line

3Circuit three-phase current input

IA3-

3loopAPhase current outgoing line

4Circuit three-phase current input

IA4-

4loopAPhase current outgoing line

IA3+

3loopAPhase current incoming line

IA4+

4loopAPhase current incoming line

IB3-

3loopBPhase current outgoing line

IB4-

4loopBPhase current outgoing line

IB3+

3loopBPhase current incoming line

IB4+

4loopBPhase current incoming line

IC3-

3loopCPhase current outgoing line

IC4-

4loopCPhase current outgoing line

IC3+

3loopCPhase current incoming line

IC4+

4loopCPhase current incoming line

5Circuit three-phase current input

IA5-

5loopAPhase current outgoing line

6Circuit three-phase current input

IA6-

6loopAPhase current outgoing line

IA5+

5loopAPhase current incoming line

IA6+

6loopAPhase current incoming line

IB5-

5loopBPhase current outgoing line

IB6-

6loopBPhase current outgoing line

IB5+

5loopBPhase current incoming line

IB6+

6loopBPhase current incoming line

IC5-

5loopCPhase current outgoing line

IC6-

6loopCPhase current outgoing line

IC5+

5loopCPhase current incoming line

IC6+

6loopCPhase current incoming line

Switching input

IN1

Switching input1

Relay

COM1

relay1Common terminal

IN2

Switching input2

NO1

relay1Output normally open contact

IN3

Switching input3

COM2

relay2Common terminal

IN4

Switching input4

NO2

relay2Output normally open contact

VCC

Switching input power supplyVCC

COM3

relay3Common terminal

GND

Switch input common terminal

NO3

relay3Output normally open contact

Three phase total voltage input

A

APhase voltage input

RS232communication

Tx

RS232Data sender

B

BPhase voltage input

Rx

RS232Data receiving end

C

CPhase voltage input

GND

RS232Communication grounding

N

Voltage center line

TCPcommunication

TCP

Ethernet communication

Auxiliary power supply

VCC

Positive pole of power supply

485communication

D+

RS485communicationD+

GND

Negative pole of power supply

D-

RS485communicationD-

VIregister table

function code34616

Register address

Register content

quantity

state

describe

public

0000

Switching input1

2

read only

Switch input status

0002

Switching input2

2

read only

Switch input status

0004

Switching input3

2

read only

Switch input status

0006

Switching input4

2

read only

Switch input status

0008

Relay1

2

Reading and writing

Relay output status

0010

Relay2

2

Reading and writing

Relay output status

0012

Relay3

2

Reading and writing

Relay output status

0014

frequency

2

read only

grid frequency

Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!