1) Air cooled ice water machines are particularly suitable for situations with poor water quality or frequent need for movement, without the need for a cooling tower, which saves pipeline installation costs and is easy to move.
2) The air-cooled cooling air is drawn in from the side of the body and discharged from the top, resulting in better performance.
3) Adopting a large area condensing coil and a special blade type cooling fan, the heat transfer efficiency is strong.
4) Adopting a brand new imported Japanese "Daikin" compressor, it has a large cooling capacity, energy saving and durability.
5) Built in stainless steel insulated water tank and circulating chilled water pump.
The basic principle of industrial chiller refrigeration system:
After absorbing the heat of the cooled object in the evaporator, the liquid refrigerant vaporizes into low-temperature and low-pressure steam, is sucked in by the compressor, compressed into high-pressure and high-temperature steam, and discharged into the condenser. It releases heat to the cooling medium (water or air) in the condenser and condenses into high-pressure liquidThe refrigerant is throttled by a throttle valve to low pressure and low temperature, and then enters the evaporator again to absorb heat and vaporize, achieving the purpose of circulating refrigeration. In this way, the refrigerant completes a refrigeration cycle in the system through four basic processes: evaporation, compression, condensation, and throttling.
Project Ltem \ Model Model
|
TYPA-001S
|
TYPA-002S
|
TYPA-003S
|
TYPA-005S
|
TYPA-007.5S
|
TYPA-010D
|
TYPA-015T
|
TYPA-020D
|
TYPA-025D
|
TYPA-030T1
|
||
Power Supply
|
1∮220V/50HZ
|
|||||||||||
Nominal Capacity REFTIGERATION CONSUMPTION
|
kw
|
2.8`
|
5.76
|
8.58
|
14.1
|
22.8
|
28.8
|
43.5
|
58.2
|
66
|
81
|
|
Kcal/Hr
|
12,478
|
4,956
|
7,380
|
12.126
|
19.644
|
24,780
|
37,427
|
50,075
|
66,786
|
69,692
|
||
Input power consumption
|
kw
|
1.1
|
2.0
|
3.76
|
6.41
|
8.96
|
10.7
|
16.48
|
23.48
|
28.32
|
31.44
|
|
Compressor type
|
Fully enclosed Hermetic Scroll
|
|||||||||||
Refrigerant refrigerant
|
Category Type
|
|
R-22
|
|||||||||
Control Method: Control
|
|
Wool tube/temperature sensitive pressure equalization expansion valve Thermostaic expansion valve
|
||||||||||
evaporator
Chiller
|
Type Type
|
|
Cisstem type water tank
|
Shell and tube
|
||||||||
Cold water flow rate
|
㎡/Hr
|
0.5
|
1
|
1.5
|
2.5
|
3.9
|
5
|
7
|
10
|
12
|
15
|
|
Pipe diameter
|
inch
|
PT1″
|
PT1-1/2″
|
PT2″
|
PT2-1/2″
|
|||||||
Condenser
|
Type Type
|
|
Fin type Drye expansion evaporator
|
|||||||||
Ice water pump
Pump
|
Power Supply
|
kw
|
0.37
|
0.75
|
1.5
|
|
|
|
||||
Head of external lift
|
m
|
12
|
15
|
17
|
|
|
|
|||||
Built in Water Tank Capacity
|
l
|
40
|
40
|
90
|
90
|
165
|
165
|
140
|
|
|
|
|
External dimensions
Dimension
|
Length
|
mm
|
750
|
1200
|
1400
|
1740
|
2200
|
2200
|
2300
|
|||
width
|
mm
|
500
|
650
|
750
|
780
|
1100
|
1200
|
1300
|
||||
height
|
mm
|
990
|
1250
|
1720
|
1720
|
1900
|
1900
|
1900
|
||||
Unit weight Net weight
|
kg
|
130
|
150
|
155
|
165
|
280
|
300
|
600
|
820
|
1200
|
1400
|
|
Fan power
|
w
|
150wx1
|
150wx1
|
150wx2
|
495wx2
|
550wx2
|
550wx2
|
780wx2
|
780wx3
|
780wx3
|
600wx4
|
|
Protection device
|
High and low voltage switches, antifreeze switches, thrombolytic devices, overload protection devices, coil overheat protectors, temperature automatic switches.
High/low pressure switch, chilled water low temo switch ,fusible plug,thermal overload,compressor intermal thermostat, thermostat
|