BOHG-106 Transformer Characteristics Comprehensive Tester
The BOHG-106 series fully functional transformer characteristic comprehensive tester is a multifunctional on-site testing instrument designed specific
Product details

功能描述

The BOHG-106 series fully functional transformer characteristic comprehensive tester is a multifunctional on-site testing instrument designed specifically for testing transformer characteristics such as volt ampere characteristics, transformation ratio, polarity, error curve, angle difference ratio, calculation of inflection point, and secondary side circuit inspection

During the experiment, only the test voltage/current value needs to be set, and the equipment can automatically boost/boost the current, and quickly display the voltage current characteristic curve or transformation ratio, polarity and other experimental results of the transformer. It supports data saving and on-site printing, which not only saves the tedious labor of manual voltage regulation, manual recording, and curve drawing, but also uploads the test data to the computer for editing, saving or printing through the USB interface Easy to operate and improve work efficiency, it is a high-tech product with high cost-effectiveness

产品别名
Transformer tester, transformer characteristic tester, multifunctional transformer tester, transformer characteristic comprehensive tester, transformer comprehensive tester, transformer comprehensive characteristic tester, transformer calibrator


仪器特点1. Safe and reliable

The first MBC power control technology in China, single-phase AC220V input power supply, and the working power supply shares the same input port with the power supply. The design is more scientific and reasonable, and the use is safer and more reliable

Note: Other similar products use separate input methods for working power and power supply, and also require the use of three-phase AC380V dual live input to meet experimental requirements, which poses a great safety hazard and can easily cause accidents such as electric shock and even injury to users

2. Complies with national maintenance regulations

The power output of the device is all true voltage and current values, and the waveform is a standard sine wave with a frequency of 50-60Hz; Can truly and effectively simulate the true state of transformers, in compliance with relevant national maintenance regulations

3. Large output capacity

The maximum voltage output of a single machine with 220V input is 0-1000V/2500V (depending on the model), and the maximum current output of a single machine is 0-600A/1000A (depending on the model), which is very suitable for on-site maintenance and use

4. Fully functional

It can detect the volt ampere characteristics, transformation ratio, polarity, 5% and 10% error curves, angular difference ratio, CT primary current and CT demagnetization of CT/PT, and easily achieve multi-purpose use of one machine

5. Simple wiring method

Adopting a single power input port; With only 8 test ports, all CT/PT testing projects can be completed. The wiring method is safe and simple, making it very suitable for on-site use. It can effectively reduce labor intensity and improve work efficiency

6. Large testing scope

For CT ratio measurement range of 15000A/5A, 3000A/1A, PT ratio testing range of 500kV: 100V

Note: Measurement range without the need for an external booster or an external current booster

7. Quick printing

Using a thermal printer to automatically screen and print typical report usage data, it is very suitable for on-site data comparison

8. Large capacity FLASH storage

Can save 1000 sets of experimental data, and can be saved for 10 years after power failure

9. USB interface

Convenient to connect to modern laptops

10. Small size, light weight

Convenient for on-site use

技术参数

1.1 BOHG-106

Equipped with CT/PT ratio and angle difference testing functions

Working power supply: AC220V

Output voltage: 0-1000V

Output current: 0-600A

1.2 BOHG-106A

Having all the functions of Type 106

Increase the output capacity of a single machine

Working power supply: AC220V

Output voltage: 0-2500V

Output current: 0-1000A

1.3 BOHG-106B

Having all the functions of the above models

And add CT/PT secondary actual load measurement

Working power supply: AC220V

Output voltage: 0-2500V

Output current: 0-1000A

1.4 BOHG-106C

Having all the functions of the above models

And add support for multiple groups to detect simultaneously

Working power supply: AC220V

Output voltage: 0-2500V

Output current: 0-1000A

1.5 BOHG-106D

Accuracy: ≤ 0.05, supporting detection of CT and PT (protection, metering, TP) steady-state and transient parameters

Working power supply: AC220V

Output voltage: 0-2500V

Resistance measurement: 0-300 Ω

Main testing functions

2.1 For current transformers (CT):

Voltage current characteristic test, transformation ratio test, polarity discrimination, 5% and 10% error curves, primary current test, demagnetization power frequency AC withstand voltage test, angle difference ratio difference test

2.2 For voltage transformers (PT):

Voltage current characteristic test, transformation ratio test, polarity discrimination, power frequency AC withstand voltage test, demagnetization, angle difference ratio test

3. Technical Parameter

Working power supply: AC220V (50~60Hz);

Volt ampere output voltage: 0~1000V;

Voltage current output: 0~15 A;

Variable ratio output current: 0~600 A;

Voltage current measurement accuracy: < 0.5%;

Variable ratio measurement accuracy: < 0.5%;

Angle difference test accuracy: 4 points;

Differential testing accuracy: 0.1 level;

Working temperature: -10~50℃;

Weight (Kg): 22;