1、 Technical parameters of BR0.1 plate cooler:
Model BR0.1
The effective area of a single piece is Active Area Per Plate 0.1 ㎡,
The depth of the ripple on the plate is nominal plate gap 3.8mm
Thickness of the board is 0.5mm
Plate corner hole size Port dim 50mm
Maximum flow rate: 65m ³/H
Connection diameter DN50
Working pressure 0.6MPa, 1.0MPa, 1.6MPa
2、 External dimensions of BR0.1 plate cooler equipment:
model |
Heat Exchange Area area(m2) |
Number of plates number of plates |
L | E | Weight Fweight(Kg) |
Traffic volume Flow rate(m3/H) |
BR0.1-A | 2 | 20 | 86 | 196 | 108 | 11 |
BR0.1-C | 12 | 120 | 516 | 626 | 187 | 65 |
A is the minimum assembly area, and C is the maximum assembly area.
Pressing size L (mm): L=(4.3 ± 0.2) x number of plates
The water flow rate is calculated based on a single process and a plate to plate flow rate of 0.4m/s
◆ We reserve the right to change the data. The above data is for reference only, and the actual product shall prevail