1、 Technical parameters of BR0.8 plate cooler:
Model BR0.8
The effective area of a single piece is Active Area Per Plate 0.81 ㎡,
The nominal plate gap is 4 0mm
Thickness of the board is 0.6mm
Plate corner hole size Port dim 200mm
Maximum flow rate: 408m ³/H
Connection diameter DN200
Working pressure 0.6MPa, 1.0MPa, 1.6MPa
2、 External dimensions of BR0.8 plate cooler equipment:
model |
Heat Exchange Area area(m2) |
Number of plates number of plates |
L | E | Weight Fweight(Kg) |
Traffic volume Flow rate(m3/H) |
BR0.8-A | 65 | 81 | 374 | 1300 | 1773 | 132 |
BR0.8-C | 200 | 251 | 1155 | 2100 | 1866 | 408 |
A is the minimum assembly area, and C is the maximum assembly area.
Pressing size L (mm): L=(4.6 ± 0.2) x number of plates
The water flow rate is calculated based on a single process and a plate to plate flow rate of 0.4m/s
◆ We reserve the right to change the data. The above data is for reference only, and the actual product shall prevail