product details
1. The "Iron Tower Brand" series of AC parameter voltage regulators integrates ultra wide voltage regulation, high precision, high reliability, fast response, and bidirectional anti-interference. There is no need for standby, and the load can be connected and used immediately upon startup.
2. Strong bidirectional anti-interference ability! It can effectively filter out various frequencies of positive and negative pulses and surge voltages generated by the power grid and loads, and has strong lightning resistance, high safety, reliability, and stability.
3. The voltage stabilization range is particularly wide, especially suitable for situations with large voltage fluctuations.
4. Has strong overload capacity.
5. It has automatic protection features. When the load is short circuited or internal components are damaged, the output voltage automatically drops to 0 volts. Never experience overvoltage output, ensuring the safe operation of user devices.
6. High quality raw materials and power components are selected, and there are no active components inside the machine, resulting in a low failure rate, particularly long lifespan, and more reliable operation. It can be considered as a "semi permanent equipment".
Technical Parameters
1. Power supply voltage nominal value: 220V (AC)
2. Power supply voltage frequency: 50Hz
3. Rated output voltage: 220V ± 2% (or specified by the user)
4. Power supply voltage range: 154V~264V
5. The short-term working range is up to 120V~300V.
6. Stable output voltage accuracy:
① When inputting 220V ± 10%, output 220V ± 1.5%;
② When inputting 220V ± 20%, output 220V ± 2.5%;
③ When inputting 220V ± 20%~30%, output 220V ± 3%~4%;
7. Power factor: COS Φ ≥ 0.95 (full load).
8. Efficiency
Below 500VA ≥ 80%
Above 1000VA ≥ 83%~92%
9. Relative harmonic content of output voltage
1000VA, 2KVA, 3KVA, 5KVA, 7.5KVA ≤ 3%
300VA, 500VA, 10KVA or above ≤ 3.5%
10. Transient total recovery time: 10-40ms
11. Audio noise: ≤ 60dB (A), 10KVA or above ≤ 70dB (A)
12. Overload capacity: When inputting 220V, it is allowed to overload 1.2 times the rated output current for a short period of time.
13. Working environment: -25 ℃ to+45 ℃, relative humidity ≤ 95%, altitude below 4 kilometers
14. Temperature rise: ≤ 65 ℃ (B-class insulation)
15. Source frequency effect: ≤ 6% (Source frequency nominal value ± 2%)
16. Output short circuit characteristic: When the output short circuit occurs, the source current is less than 2.5 times the rated input current. After the short circuit disappears, it can automatically resume operation. However, the voltage regulator does not allow the output terminal to operate in a long-term short circuit state
17. Cooling method: Natural cooling below 1KVA, air cooling or natural cooling above 2KVA
18. Anti interference performance:
① Peak suppression: Constant input 2. KV peak signal, output ≤ 40Vp
② Frequent noise suppression: ≥ 40dB
19. Working mode: continuous
20. Reliability index: Mean Time Between Failures (MTBF) ≥ 30000 hours
21. Safety standards:
① Insulation resistance ≥ 20M Ω
② The insulation test voltage is 1.5KV/min without any flashover or breakdown phenomenon
③ Leakage current: ≤ 3.5mA (effective value)
④ Safety category: Class I safety equipment
⑤ Protection level: IP20 class
Product parameters