The DPG-200 series digital pressure gauge has a high accuracy of ± 0.25% of full scale.
Using a new oneThe DPG-200 series digital pressure gauge has a high accuracy of ± 0.25% of full scale. A four digit display will reduce potential errors in readings and eliminate parallax errors commonly caused by analog pressure gauges. The DPG-200 series uses a sturdy and durable aluminum shell to achieve NEMA 4X (IP66) protection. It is connected to a 12-24VDC/VAC power supply and comes with 2 alarm setpoints and a 4-20mA process output. The four key button is very easy to use. Other functions include background display light, maximum and minimum, calibration or auto zeroing, and pressure unit conversion.

application
• Liquid level control
• Pump control
• Process control
• Compressor control
technical indicators
Technical indicators for digital meters
Media: Compatible, non corrosive liquids and gases.
Material:316L stainless steel
Shell material: The front and back covers are made of black polycarbonate, embossed aluminum shell with grooves, polycarbonate surface, Buna-N O-ring, 316 stainless steel sensor structure
Accuracy: Full scale0.25% at 70 ° F (21 ° C) +/-Minimum Significant Number (including linearity, hysteresis, and repeatability)
Pressure range:2 times the pressure range for ranges within 1000 psi; 5000 psi for pressures within 3000 psi; 7500 psi for pressures within 5000 psi
Temperature range:0 to 158 ° F (-18 to 70 ° C)
Connector:1/4 ˝ MNPT external thread
Display:4-digit (. 425 ˝ H x. 234 ˝ W size)
Size:3.00 ˝ outer diameter x 1.90 ˝ depth (excluding cables)
Weight:8.84 oz(275 g)
Technical indicators of switches
Switch type:Two single blade double throw contacts with C
Electrical level:Impedance from 0.5A to 125VAC, 1A to 24VDC
Electrical connection:3ft (equivalent to 0.91m) cable
Installation location: Can be installed anywhere
Setpoint adjustment: via menu.
Technical specifications of the transmitter
Temperature range:0 to 158 ° F (-18 to 70 ° C)
Thermal effect:0.016%/° F between 70 and 158 ° F; 0.026%/° F between 0 and 70 ° F
Power requirements:12-24 VAC +/-20% 50-400 HZ,12-24 VDC+/-20%
Output signal:4-20mA
Loop resistance: maximum value is600ohms
Power consumption: maximum0.8W
Electrical connection:3ft (equivalent to 0.91m) cable
Protection indicators: Designed to meetNEMA 4X(IP66)
Institutional certification:CE