VIP member
ECA110A differential pressure transmitter
Summary: The ECA110A differential pressure transmitter is used to measure the liquid, gas, or vapor level, density, and pressure, and then convert it
Product details

summary
ECA110ADifferential pressure transmitters are used to measure the liquid, gas, or vapor level, density, and pressure, and then convert them into 4-20mADC current signals for output. ECA110A can also communicate with the HART275 handheld controller for setting, monitoring, and other purposes.
Functional specifications
output
2Wire system, 4-20mA DC output, digital communication, programmable linear or square root output mode, HART protocol loaded on 4-20mA DC signal.
supply voltage
10.5~42V DC (working state)
(10.5-30V DC intrinsic safety type)
16.4~42V DC (digital communication, BRAIN and HART protocols)
(16.4~30V DC intrinsic safety type)
load(When the output signal codes are D and E)
0-1335 Ω working state
250-600 Ω digital communication
HART
Communication Distance
Using multi-core twisted pair cables, the maximum communication distance can reach 1.5km, and the communication distance varies depending on the cable type.
ambient temperature
-40~85℃(-40~185°F)
-30-80 ℃ (-22-176 ° F) [with LCD meter head]
Liquid contact temperature
-40~120℃(-40~248°F)
Performance specifications
Reference accuracy for range adjustment
(Including linearity, hysteresis, and repeatability starting from zero)
±0.1%~±0.5%
Static pressure effect
LCapsule
± [0.07% range+0.052% range upper limit]/3.4MPa {500psi}
M. H and V membrane boxes
± [0.1% range+0.028% range upper limit]/6.9MPa {1000psi}
Overvoltage impact(M、 H and V membrane boxes)
± 0.03% upper range limit/6.9MPa {2000psi}
stability(M、 H and V membrane boxes)
± 0.1% range upper limit/60 months
Model and Specification Code Table
model
|
instrument for drawing circles check take the place of a sign or object indicating number
|
speak bright
|
||||||||
ECA110A
|
………………………………
|
differential pressure transmitter
|
||||||||
output signal
|
-E……………………………
-D……………………………
|
4~20mA, HART protocol digital communication
4~20mA
|
||||||||
Measurement range
(Membrane box)
|
L……………………………
M……………………………
H……………………………
V……………………………
|
0.5~10Kpa{50~1000mmH2O}
0.5~10Kpa{50~1000mmH2O}
0.5~10Kpa{50~1000mmH2O}
0.5~10Kpa{50~1000mmH2O}
|
||||||||
Material of the liquid receiving part
|
S…………………………
H…………………………
M…………………………
T…………………………
A…………………………
D…………………………
B…………………………
|
[Body][Membrane box[Exhaust screw
SCS14A SUS316L SUS316
SCS14AHastelloy C-276SUS316
SCS14AMonelSUS316
SCS14AtantalumSUS316
Hastelloy C-276 Hastelloy C-276 Hastelloy C-276
Hastelloy C-276 tantalum Hastelloy C-276
Monel Monel Monel
|
||||||||
pipe connection
|
0………………………
1………………………
2………………………
3………………………
4………………………
5………………………
|
No process joint (Rcl/4 internal thread on chamber flange)
Process connector with Rcl/4 internal thread
Process connector with Rcl/2 internal thread
Process connector with 1/4NPT internal thread
Process connector with 1/2NPT internal thread
No process joint (1/4NPT internal thread on the chamber flange)
|
||||||||
Material of bolts and nuts
|
A……………………
B……………………
C……………………
|
[Maximum working pressure
LCapsuleL、 M. H, V membrane box
SCM435 3.5Mpa 16Mpa
SUS630 3.5Mpa 16Mpa
SUH660 3.5Mpa 16Mpa
|
||||||||
Installation method
|
-2…………………
-3…………………
-6…………………
-7…………………
-8…………………
-9…………………
|
Vertical installation, high voltage on the right, process connector on top
Vertical installation, high voltage on the right, process connector at the bottom
Vertical installation, high voltage on the left, process connector on top
Vertical installation, high voltage on the left, process connector at the bottom
Horizontal installation, high voltage on the right side
Horizontal installation, high pressure on the left side
|
||||||||
electrical interface
|
0 ………………
2 ………………
3 ………………
4 ………………
5 ………………
7 ………………
8 ………………
9 ………………
|
G1/2Internal thread, 1 connection port
1/2NPTInternal thread, 2 connection ports
Pg13.5Internal thread, 2 connection ports
M20Internal thread, 2 connection ports
G1/2Internal thread, 2 connection ports with a blind plug
1/2NPTInternal thread, with two electrical interfaces and a blind plug
Pg13.5Internal thread, with two electrical interfaces and a blind plug
M20Internal thread, with two electrical interfaces and a blind plug
|
||||||||
Display header
|
D………………
E………………
N………………
|
Digital header
Digital header with setting button
(No header)
|
||||||||
2-inchPipe installation bracket
|
A……………
B……………
C……………
D……………
N……………
|
SECCFlat bracket
SUS304Flat bracket
SECC LType bracket
SUS304 LType bracket
No installation bracket
|
||||||||
Additional selection code
|
/□ Selection specifications
|
|||||||||
Example: ECA110A-DMS5A-92NN/□
|