Gas Solenoid Valve
EV/NC series gas safety solenoid valves are widely used for controlling and regulating gas heating equipment such as gas burners, atmospheric gas furnaces, industrial furnaces, incinerators, etc. Produced strictly in accordance with EN161 standards and CE testing rules, in compliance with European gas application standards 90/396/EC, 94/9/EC, 2004/108/EC, 2006/95/EC.
Product Features
Structural Analysis Diagram (1):

Structural Analysis Diagram (II):

Product parameters
| Maximum work pressure: | 200mbar or 360mbar |
| Grade: | Grade A (compliant with the European BS EN126 standard) |
| Safe voltage: | 24Vdc、24V/50HZ、110V/50HZ、230V/50-60HZ |
| Applicable medium: | Non corrosive gases such as urban gas, natural gas, liquefied petroleum gas, etc |
| Adapt to temperature: | -15℃—+60℃ |
| Connection method: | Threaded interface: (DN15-DN50) compliant with EN10226 standard Flange interface: (DN65-DN300) compliant with ISO 7005 standard |
| Opening/closing time: | <1 second (except=''evp13h=''>1>) |
installation
1. Before installation, confirm that the gas supply pressure must not exceed the working pressure indicated on the valve.
Before installation, remove the dust-proof plastic cover at the inlet and outlet of the valve.
3. Confirm whether the airflow direction is consistent with the arrow direction marked on the valve body.
4. There should be sufficient space (at least 30cm apart) between the wall and the ground to allow air to circulate freely.
5. Valves can be installed vertically with a tolerance of+/-90 degrees; The direction of the coil is 360 degrees in any direction.
6. Install in a location that is not affected by rainwater, splashes, or water droplets.
7. DN200 solenoid valves must be installed horizontally, while solenoid valves of other diameters can be installed horizontally or vertically in vertical pipes.