1.1 Environmental conditions for product use
1.1.1 The altitude generally does not exceed 1000m, and for special types, it does not exceed 4000m.
1.1.2 The maximum ambient temperature shall not exceed+40 ℃, and the minimum shall not exceed -30 ℃
1.1.3 Wind speed not exceeding 35m/s
1.1.4 The seismic intensity shall not exceed 9 degrees.
1.1.5 The thickness of ice cover shall not exceed 10mm.
1.1.6 Pollution resistant products are suitable for areas with moderate pollution.
1.1.7 Not applicable to places with flammable substances, explosion hazards, chemical corrosion, and severe vibrations.
1.2 Main specifications and technical parameters
1.2.1 The main specifications and technical parameters of the isolation switch are shown in Table 1
Table 1
project |
Main specifications and technical parameters |
notes |
||
Rated voltage KV |
110 |
|
||
Maximum working voltage KV |
126 |
|
||
Rated current A |
630 |
1250 |
2000 (2500) |
|
Rated dynamic stability current (peak value) KA |
50 |
80 |
100 (104) |
Type I grounding switch dynamic stable current 20KA Type II grounding switch is the same as the isolation switch |
4S thermal stability current (effective value) KA |
20 |
31.5 |
40 (46) |
Type I grounding switch thermal stability current 8KA Type II grounding switch is the same as isolation switch |
Rated static tension of terminal N |
735 (980) |
|
||
Rated frequency Hz |
50 |
|
Continued Table 1
project |
Main specifications and technical parameters |
notes |
1-minute power frequency withstand voltage (Effective value) KV |
Ground 185 (230) |
|
Port 210 (520) |
||
Lightning impulse withstand voltage (Peak) KV |
Ground 450 (520) |
|
Port 520 (630) |
||
Product weight per unit (body) KG |
≈240 |
|
Supporting organization KG |
Isolation switch: manual mechanism 10 Or CJ6 motor mechanism Grounding switch: CS14G manual mechanism |
Supply according to order |
Institution weight KG |
CS14G manual mechanism 10 CJ6 motor mechanism 95 |
|
Grounding form |
Ungrounded, single grounded, or double grounded |
|
Crawling distance of pillar insulator mm |
Ordinary 1870 Pollution resistant 3050 |
Special orders can also be accepted |
Note: The data in parentheses represents the actual achieved value of the product
1.2.2 The main specifications and technical parameters of the CJ6 motor mechanism are shown in Table 2
project |
Technical Parameter |
notes |
|
electricity move machine |
Rated voltage V |
Three phase AC 380 |
|
Rated power KW |
0.6 |
|
|
Rated speed r/min |
1410 |
|
|
Starting current A |
Not greater than 5 |
|
|
Control voltage of switching coil V |
Exchange 380 or 220 |
Supply according to user requirements |
|
Current of the switching coil A |
Not greater than 5 |
|
|
Rated operating time s |
3.5 |
|
|
Rated output torque Nm |
500 |
|
|
Thermal relay action time s |
Motor short circuit overload 20-25 |
|