VIP member
Indoor VOC gas transmitter BYC100-VOC
Indoor VOC gas transmitter BYC100-VOC
Product details
1、 Introduction to indoor VOC gas transmitter
BYC100-VOC indoor VOC gas transmitter is a device developed and produced by Shenzhen Boyunchuang Environmental Technology Co., Ltd. for indoor air quality. It is mainly used to measure the content of VOC gases in indoor air, provide effective VOC concentration data, remind users to take safety measures, and drive functions such as fresh air system linkage, providing users with a comfortable home environment. The product adopts original imported metal oxide sensors and computing chips, which have the characteristics of high precision, high resolution, and good stability. Widely used in building HVAC, building energy conservation, smart homes, underground garages, airport stations and other places.
2、 Gas Introduction
VOC stands for volatile organic compounds. In the ordinary sense, VOC refers to volatile organic compounds; However, in terms of environmental protection, it refers to a type of volatile organic compound that is reactive and harmful. The objects that people come into contact with in their living environment emit this substance at all times. Working and living in buildings containing VOC substances, some people may experience headaches or blurred vision, known as' new house syndrome '. This has an impact on human health. Not only has the VOC issue of home decoration materials received attention, but in recent years people have also begun to pay attention to the VOC issue of electronic devices.
3、 Characteristics of indoor VOC gas transmitter
1. Stable and reliable communication, wide range power supply DC12-24V;
2. Complete anti reverse, overvoltage, overcurrent, and inter line protection capabilities;
3. Carefully designed circuit software and hardware, with low failure rate and short stability time;
4. Original imported sensors and professional grade signal processing chips ensure the accuracy of sensor data;
5. The structure considers aerodynamic principles, achieves automatic real-time sampling, and can be used for a long time;
6. The measurable environmental parameters cover a wide range and can meet various detection environment requirements;
7. Output 4-20mA, 0-10V, RS485 and other signals for easy use.
4、 Technical parameters of indoor VOC gas transmitter
4、 Technical parameters of indoor VOC gas transmitter
Technical Parameter | BYC100-VOC |
Detect gas | Organic volatile compounds (VOCs) |
Detection Principle | Principle of Metal Oxide Detection |
measuring range | 0~10ppm0~100ppm |
resolution | 0.1ppm(10ppm) ; 1ppm(100ppm) |
accuracy | ≤±5%F.S |
Warm-up time | 3 minutes |
sampling interval | 3S |
response time(T90) | <3 minutes |
service life | More than 3 years |
zero drift | <±1% |
Nonlinear | <1%F.S |
repeatability | ±2% |
Supply Voltage | DC 12~24V |
signal output | 4~20mA0~10VRS485 modbus RTU |
work environment | -10~50℃; 0-95% RH (no condensation) |
Environment | -30~60℃; 0-100% RH (no condensation) |
Shell material | Plastic ABS |
protection grade | IP30 |
Installation method | Wall mounted and ceiling mounted |
Weight/Size | 120g/ 110mm×70mm×38mm |
notes |
5、 Installation of indoor VOC gas transmitter size
1. First, fix the installation disk on the wall.
2. After connecting the equipment, fix it on the installation disk.
3. Do not connect the transmitter to a voltage higher than 24VDC. To prevent excessive voltage from burning out the sensor.
4. Install the transmitter at the location that needs to be tested, away from the heating element or steam source, and prevent direct sunlight.

Online inquiry