Jiangsu Huade Electric Power Technology Co., Ltd
Home>Products>Intelligent low-voltage reactive power compensation controller
Intelligent low-voltage reactive power compensation controller
The HD series intelligent low-voltage reactive power controller is a new generation product developed and produced by Jiangsu Huade Electric Power Tec
Product details

The HD series intelligent low-voltage reactive power controller is a new generation product developed and produced by Jiangsu Huade Electric Power Technology Co., Ltd. to meet the development needs of low-voltage reactive power automatic compensation, based on the absorption of domestic and foreign low-voltage reactive power automatic compensation technologies. The product has an RJ45 communication interface and can be used in conjunction with our company's anti harmonic low-voltage intelligent power capacitors. The wiring is simple and the operation is reliable. This product can replace one multifunctional meter, one transfer switch, and one low-voltage reactive power compensation controller on the existing low-voltage reactive power compensation cabinet. It is easy to use,

The product has obtained CQC product certification certificate and CQC logo certification test report

major function

1. Set Function

CT ratio setting

Protection setting

Delay time setting

Power factor setting

2. Control function

Automatic and manual control

Automatic switching control is performed based on controlled physical quantities (reactive power, reactive current, power factor, time period).

Capacitors with the same capacity are switched and controlled according to the principle of cyclic switching, while capacitors with different capacities are switched and controlled according to the reactive power deficit;

Before switching capacitors, predict the distribution reactive power and voltage changes caused by switching. If reverse operation is expected after switching, no switching control will be applied.

3. Measurement function

Measurement of distribution voltage, current, power factor, active power, reactive power, and harmonic content.

4. Signal function

Signal for capacitor commissioning and decommissioning;

Product or peripheral malfunction signal.

5. Protection function

Undervoltage and voltage loss protection.

Two level overvoltage acceleration protection;

Voltage over harmonic protection

Current over harmonic protection

Switching oscillation protection.

main features

The HD series low-voltage reactive power compensation controller is connected to other components using RJ45 communication, simplifying secondary wiring and reducing wiring workload and faults caused by wiring errors. The communication method requires the connected components to have the same communication interface and protocol. If they are different, necessary modifications must be made to one of them to achieve good communication between the two and enable information exchange. The wiring terminals on the rear cover of the HD-202 low-voltage reactive power compensation controller are electrically connected to the movement using a contact type, and the movement is integrated. In case of a malfunction, the external wiring can be removed and the rear cover can be replaced with the movement, and then the rear cover can be installed.

Specification

1. Environmental conditions

1) Environmental temperature:- 25℃~+55℃

2) Altitude: ≤ 4000m

2. Power supply conditions

1) Working voltage: 380V ± 30%

2) Voltage waveform: sine wave, total distortion rate not exceeding 10%

3) Power frequency: 50 ± 1.5Hz

4) Power consumption: ≤ 3VA

3. Measurement error

1) Voltage and current: ≤ 0.5%

2) Power: ≤ 1%

3) Active power consumption: ≤ 1%

4) Reactive power consumption: ≤ 2%

5) Harmonic voltage: ≤ 1.5%

6) Harmonic current: ≤ 2.5%

4. Protecting errors

1) Voltage: ≤ 0.5%

2) Current: ≤ 0.5%

3) Harmonic: ≤ 2.5%

4) Time: ≤ 0.1s

5. Reliability parameters

1) Control accuracy: 100%

2) Failure rate: ≤ 0.1% (year)

6. Security

The electrical clearance and creepage distance, insulation strength, safety protection, short-circuit strength, sampling and control circuit protection all comply with the corresponding requirements of the Chinese power industry standard GB/T22582-2008 "Power Capacitor Low Voltage Power Factor Compensation Device".

7. Control parameters

1) Control capacity: ≤ 33 units;

2) Control speed: ≤ 1S;

3) Control accuracy: minimum capacitor capacity ± 10%;

4) Control accuracy: 100%.

8. Mechanical parameters

1) Mass: 0.35kg

2) Dimensions: 120 (W) × 120 (H) × 96 (D) mm

3) Hole size: 111 (W) × 111 (H) mm


Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!