JUMO 404366 dTRANS p30 pressure transmitter
JUMO 404366 dTRANS p30 pressure transmitter is used for gauge and absolute pressure measurement of gases or liquids. It uses piezoresistive or thin-fi
Product details

JUMO 404366 dTRANS p30 pressure transmitter
sketch
Used for measuring gauge pressure and absolute pressure of gases or liquids
Using piezoresistive or thin-film strain gauge measuring elements

JUMO 404366 dTRANS p30 pressure transmitter

technical data
Reference conditions
DIN 16 086 and IEC 770/5.3
measuring range
Refer to the selection instructions
Overload capacity
measuring range
0 25 bar 3 x full range
measuring range
0 40 to 0 250 bar 2 x full range
measuring range
0 400 to 0 600 bar 1.5 X full range
fracturing pressure
Measurement range 0 40 bar ≤ 4 x full scale
measuring range
0 60 to 0 100 bar 8 x full scale
measuring range
0 160 to 0 400 bar 5 x full scale
measuring range
0 600 bar 3 x full range
Liquid receiving material
Standard: Stainless steel Mat. Ref. 1.4571/1.4435
Range ≥ 60 bar, Mat. Ref. 1.4571/1.4542
output
0 20 mA 3-wire system with load capacity ≤ (UB-12 V)/0.02A
4 — 20 mA
2-wire system with load capacity ≤ (UB-10 V)/0.02A 4-20 mA 3-wire system with load capacity ≤ (UB-12 V)/0.02A
0.5-4.5 V load capacity ≥ 50 k Ω
1-6 V carrying capacity ≥ 10 k Ω
0-10V load capacity ≥ 10 k Ω
loading error
0.5% max.
drift
≤ 0.3%
Thermal hysteresis ± 0.5% Max. F.S
(Within the temperature compensation range)
± 1% max.F.S. for 0-250 mbar
0 - 400 mbar
0 - 600 mbar
Temperature drift
Temperature range 0-+100 ° C
(Temperature compensation range)
Range of 250 and 400 mbar
Zero point: ≤ 0.03%/℃ C typical
≤ 0.05%/℃ maximum
Range: ≤ 0.02%/℃ Typical
≤ 0.04%/℃ maximum
Range greater than 600 mbar
Zero point: ≤ 0.02%/℃ Typical
≤ 0.04%/℃ maximum
Range: ≤ 0.02%/℃ Typical
≤ 0.04%/℃ maximum
accuracy
≤ 0.5% F.S.
(Adjustment of restriction points)
return difference
≤ 0.1% full scale
repeatability
≤ 0.05% full scale
response time
Current output (output 402, 405 or 406):
≤ 3 msec
Voltage output (output 412, 415, 418 or 420):
≤10 msec
Annual stability
≤ 0.5% F.S.
power supply
10-30 V DC (output 4 20 mA and 1-6V)
5V DC (output 0.5-4.5V)
11.5-30 V DC (output -10 V)
11.5-30 V DC (output 0 (4-20 mA))
The power fluctuation cannot exceed the above range
Maximum current consumption: approximately 25 mA
Power supply error
≤ 0.02%/V (standard voltage 24 V DC) proportional to the power supply 5 V DC (± 0.5 V)
ambient temperature
-20 - +100°C
storage temperature
-40 - +125°C
medium temperature
-30 - +120°C
electromagnetic compatibility
EN 61326
Electromagnetic interference: Class B
Anti interference capability: meets industrial requirements
Fully compliant with EN 50082-2 standard (CE mark)
Used in industrial settings
mechanical shock
( IEC 68-2-27) 100 g/1 msec
Mechanical Shock
( IEC 68-2-6) 20g max., Based on 15-2000 Hz
protection grade
Junction box type
IP65, EN 60 529 standard
(Cable outer diameter, 5-7 mm)
Cable type
IP67, EN 60 529 standard
casing
stainless steel, Mat. Ref. 1.4301
Polycarbonate GF

Online inquiry