Installation of KJH41X hydraulic control valve:
1. Gate valves should be installed at both ends of the KJH41X hydraulic control valve. It is strictly prohibited to set butterfly valves.
2. The control pipe of KJH41X hydraulic control on-off valve is connected to the water outlet pipeline and located between the water pump outlet and the check valve. Do not install it on the pipeline connected to the check valve outlet, otherwise the valve will not function.
3. Do not bring any debris into the joint of this valve.
4. Before installing this valve and on the control pipeline, install a dirt remover and filter. Otherwise, debris may support the valve disc and cause leakage.
5. This valve can be used in conjunction with an automatic reversing check valve.
Operation of KJH41X hydraulic control valve:
1. After the installation of this valve, the exhaust valve should be opened after the pipeline is filled with water, and then closed when the exhaust valve is discharged.
2. If you want to extend the service life of this valve, you can connect a pipeline between the water supply and return pipelines on the basis of the original installation system, and install a check valve on this pipeline
Valve (B), so that when the pump is running, the check valve (B) is closed and the system is running normally. When the pump stops, the on-off valve begins to close. If the return water pressure increases,
The stop valve (B) will be opened to reduce the impact force on the opening and closing valve, thereby extending its service life.
Troubleshooting of KJH41X Hydraulic Control Valve:
1. The on-off valve cannot be opened. Carefully observe whether the installation of this valve is reasonable, whether the operation is correct, and whether the control pipe valve is open.
2. Stop the pump and check if the boiler overflow operation is incorrect, and check if the check valve is leaking water.
Maintenance and upkeep of KJH41X hydraulic control valve:
Due to material reasons, maintenance and upkeep should be carried out after shutdown. Open the upper and lower cover bolts, remove the valve stem nuts separately, then remove the piston and clean the cylinder piston
Clean, apply butter, and install as is.
Main technical parameters of KJH41X hydraulic control valve:
Product model: KJH41X
Nominal pressure: 1.0-2.5Mpa
Nominal diameter: 50-350mm
Applicable media: water, oil, seawater, sewage
Operating temperature: 0-80 degrees Celsius
Flange standard: GB/T17241.6GB/9113
Test standard: GB/T13927AP1598
Zhengzhou KJH41X hydraulic control valve Shijiazhuang KJH41X hydraulic control valve