The PD1351 installation type digital multifunctional power monitoring instrument is a power instrument that integrates measurement recording, large screen LCD display, and communication. It can measure the three-phase voltage, three-phase current, three-phase active power, three-phase reactive power, three-phase apparent power, three-phase power factor, and frequency of the power grid, and can also measure the total and phase separated reactive power. The RS485 communication interface supports the DL/T645-2007 communication protocol. The instrument has 2 switch inputs and 2 switch outputs, which can achieve local or remote switch signal monitoring and control output functions (i.e. "remote signaling" and "remote control" functions). Instruments are suitable for energy management systems, substation automation, distribution network automation, residential power monitoring, industrial automation, intelligent distribution panels and switchgear, including use in power plants, hydropower stations and other electrical management automation systems.
Product functional features
Real time measurement: voltage, current, power, power factor, frequency, voltage and current imbalance rate;
Save data records of extreme values and occurrence times of voltage, current, and power;
Time division measurement of forward and reverse active power and four quadrant reactive power, and the combination of active and reactive power can be set arbitrarily;
The maximum demand and occurrence time of forward and reverse active power and four quadrant reactive power for time-sharing metering;
Maximum 4 rates;
Up to 14 time zones and 8 daily time slots throughout the year, with a maximum of 14 time slots per day, supporting holidays and weekends;
Automatic settlement function (saving December historical records);
2-channel switch input, 2-channel electromagnetic relay output;
2-channel pulse output of electrical energy (active and reactive);
Rich programmable alarm output (electromagnetic relay output);
Support DL/T645-2007 protocol;
The operating parameters can be programmed and set through buttons;
Application scenarios
1. Power monitoring in intelligent buildings, intelligent distribution panels, and switchgear;
2. Power monitoring in the energy management and control systems of campuses, communities, and industrial parks.
technology project | parameter | ||
specifications |
Three-phase four-wire |
||
measure |
voltage |
Reference voltage Un |
AC220/380V |
measuring range |
0.7Un~1.3Un |
||
Limited voltage |
1.9Un |
||
power consumption |
<0.05VA (single-phase) |
||
impedance |
>2MΩ |
||
accuracy class |
0.2 ℅ |
||
electric current |
Rated current |
1.5A |
|
measuring range |
1.5(6)A |
||
power consumption |
<0.05VA (single channel rated current) |
||
accuracy class |
0.2 ℅ |
||
power |
Accuracy 0.5% |
||
grid frequency |
45-65Hz, accuracy 0.2 ℅ |
||
metering |
electric energy |
Active energy (accuracy level 0.5S) |
|
clock |
≤0.5s/d |
||
digit |
Electric pulse output |
2-channel optocoupler output |
|
Switching Output |
2-channel relay output |
||
Switching input |
2-channel optocoupler input |
||
+12V power output |
Rated current 50mA |
||
communication |
Interface and Communication Protocol |
RS485 interface: DL/T645-2007 protocol |
|
Communication address range |
6 bytes, each bit can be set from 0 to 9 |
||
Baud rate |
1200bps/2400bps/4800bps/9600bps |
||
environment |
operation temperature |
-25℃~+55℃ |
|
working temperature limit |
-35℃~+60℃ |
||
relative humidity |
≤ 95% (no condensation) |
||
Working power supply |
Dual purpose AC/DC power supply (range: 50V~420V), power consumption: ≤ 1W,2VA |
||
size |
Dimensions (mm): 96 × 96 × 95 Hole size (mm): 92 × 92 |
||
weight |
554g |