Oil pipe flame arresterModel:GZW-I
|
Valve body material |
Carbon steel, stainless steel 304, 316, 316L aluminum alloy |
|
Fire retardant core material |
Stainless steel fire-resistant corrugated plate |
|
Sealing ring material |
Polytetrafluoroethylene |
|
pressure rating |
0.6-2.5MPa |
|
Nominal diameter |
DN50-500 |
|
Environmental temperature ℃ |
-30~+60 |
|
Explosion proof level |
BS 5501:IIA、IIB、IIC |
|
connection method |
flange connection |
Oil pipe flame arresterIt is to prevent external flames from entering equipment or pipelines containing flammable and explosive gases, or to prevent flames from spreading between equipment and pipelines. A flame arrester is a device that uses flames to pass through narrow pores in a thermal conductor
From time to timeDesign and manufacture based on the principle of extinguishing due to heat loss. The fire-resistant layer structure of flame arresters includes gravel type, wire mesh type, or corrugated type. Suitable for combustible gas pipelines, such as gasoline, kerosene, light diesel
Stupid, stupidStorage and flare systems for crude oil and other oil products, gas purification and chemical systems, gas analysis systems, coal mine gas emission systems, fuel gas pipelines for heating furnaces, and can also be used for acetyleneoxygen
Gas, nitrogen, naturalGas pipeline supplies. This valve can be used in conjunction with a breathing valve,It can also be used separately.
Main performance:
1Qualified explosion resistance performance,continuous13The secondary explosion resistance performance test can block fire every time.
2Qualified fire resistance performance, fire resistance test1There is no tempering phenomenon within hours.
3The shell water pressure test is qualified. This product has a reasonable structure, light weight, and corrosion resistance. Easy to maintain and install. The flame arrester core is made of stainless steel material,Corrosion resistant and easy to clean.
flame arresterworking principleMost flame arresters are composed of solid materials with many small, uniform, or non-uniform channels or pores that can pass through gas, and these channels or pores are required as much as possible
The small,Small enough to pass through flames. In this way, the flame enters the flame arrester and is divided into many small flame streams that are extinguished. The mechanism by which flames can be extinguished is through heat transfer and wall effect.
flame arresterstandard: Flange standard:GBTheHGTheSHTheHGJTheJBTheANSLTheJISWaiting for standards. (User specified, please indicate pressure level) Execution standard:GB13347-92Petroleum Gas
Pipeline obstructionfireFire resistance performance and test methods of flame arrestersSH/T3413-99Selection, Inspection, and Acceptance of Fire Arresters for Petrochemical Petroleum Gas PipelineHG/T20570.19-95The setting of flame arresters. block
Firearms production and inspectionInspection and acceptance criteria:SY/T0512-1996Fire arresters for oil storage tanks, testing basis:GB5908-86Performance and experimental methods of flame arresters for oil storage tanks.
YouTubeflame arresterMain purpose:
1On pipelines transporting flammable gases.
2Torch system.
3Oil and gas recovery system.
4The pipe network for heating furnace fuel gas.
5Gas purification and chemical system.
6Gas analysis system.
7Coal mine gas emission system.
8Hydraulic pressure test2.4MPaNo leakage.
flame arrestersize:
|
Specifications and Dimensions DN(mm) |
External dimensions(mm) |
||||
|
L |
H |
D |
K |
n*d |
|
|
50 |
190 |
200 |
165 |
125 |
4*18 |
|
65 |
205 |
210 |
180 |
145 |
8*18 |
|
80 |
220 |
220 |
200 |
160 |
8*18 |
|
100 |
240 |
240 |
220 |
180 |
8*18 |
|
125 |
280 |
260 |
245 |
210 |
8*18 |
|
150 |
330 |
285 |
285 |
240 |
8*22 |
|
200 |
380 |
325 |
340 |
295 |
12*22 |
|
250 |
450 |
365 |
405 |
355 |
12*26 |
|
300 |
520 |
400 |
460 |
410 |
12*26 |
|
350 |
595 |
420 |
520 |
470 |
16*26 |
|
400 |
645 |
450 |
580 |
525 |
16*30 |
|
450 |
710 |
480 |
640 |
585 |
20*30 |
|
500 |
780 |
520 |
715 |
650 |
20*33 |
Oil pipe flame arresterRegular inspection and maintenance should be carried out:
1The flame arrester should be inspected every six months to check whether the flame arrester core is blocked, deformed, corroded, etc.
2The blocked fire-resistant layer core should be cleaned thoroughly to ensure that each hole on the core is unobstructed, and any deformed or corroded fire-resistant layer should be replaced.
3When reinstalling the fire-resistant layer core, it should be ensured that the joint surface is tight and there is no air leakage.
Shanghai Nanshi is a professionalflame arresterManufacturer, products produced by the company: breathing valve, flame arrester, flame retardant breathable cap, fireproof vacuum pressure cap, aluminum alloy ball valve, aluminum alloy single
A series of supporting accessories including flange ball valves, oil discharge ports, double door bottom valves, and oil measuring holes.
Welcome to visit our website【http://www.shhxfcj.com】,If you have any questions.You can call us,We will do our best to provide you with high-quality service.
Telephone:.