This gateway is a MODBUS/232/485 to PROFINET gateway, which is a type of serial PROFINET gateway. The gateway on the PROFINET side is a PROFINET IO slave, and on the serial port side, there are two physical interfaces: RS-485 or -232. It supports MODBUS/RTU master or slave protocols (selected by a DIP).
When the MODBUS side of this gateway is used as the main station, it can be used for one to many integrated MODBUS/485 or one-to-one integrated MODBUS/232 devices, forming a MODBUS subnet and connecting to PROFINET to meet the technical requirements of PROFINET controller monitoring MODBUS devices. When the gateway MODBUS side serves as a slave station, it can be used to transmit data from other MODBUS master stations (such as PLC/DCS) and their slave stations to the PROFINET controller. The principle of this gateway technology is memory sharing, which does not require programming of the main station PLC/DCS. Simply configure the gateway MODBUS message in the main station configuration (such as STEP7) to achieve the automatic sending function of the gateway MODBUS main station.
General technical indicators:
1. Power Supply Voltage: Supports dual redundant power supply, wide voltage range: 19.2~28.8VDC
2. 12. Dimensions: (width) 45mm × (height) 125mm × (thickness) 118mm
3. 13. Installation method: 35mm guide rail
4. 14. Protection level: IP20
5. Working temperature: -20 ℃~+55 ℃, working relative humidity: 95% (no condensation)
6. Transportation temperature:- 30℃~+70℃
PROFINET interface technical specifications
1 2XRJ45 Ethernet interface, supporting 100BASE-TX, full duplex communication, MDI/MDIX self detection;
2. Integrated Ethernet switch, making it convenient to form a daisy chain of PROFINET devices;
3. Compliant with PROFINET Class C standards and supports PROFINET version 2.3;
4. So the total input and output data of Slot/subSlot does not exceed 340 bytes;
5. Maximum number of slots that can be inserted: 43;
6. Integrate GSML files.
MODBUS/RTU485/232Technical indicators:
1, SupportMODBUS/RTUagreement,support01H、02H、03H、04H 、05H、06H、0FH、10HFunction code;
2Baud rate:300、600、1200、2400、4800、9600、19.2K、38.4K、57.6KOptional; check bit(8No verification for the position1Stop position8Bit even verification1Stop position8Bit Oddity Verification1Stop position8No verification for the position2stop bit)Optional.
3Bus bridge control words can be flexibly controlledMODBUSMessage transmission: timed transmission (between transmissions)partitionWaiting interval optional), event triggered sending. Can be strictly controlledMODBUSWrite it(05H、0FH、10H)Command sending, optional: write command enable/Prohibition, data change enable/Prohibited functions;
4The bus bridge status word can comprehensively reflect the gatewayMODBUSCommunication status and serial communication status;
5Maximum input/Output data volume:Input Bytes + Output Bytes ≤340 Bytes;Max Input Bytes ≤252Bytes;Max Output Bytes ≤252Bytes
6Bus bridge is a memory sharing gateway that can be configured through the main station without programmingMODBUSMessage configuration and providePROFIBUS I/QarriveMODBUSSite storage area(0、1、3、4Corresponding relationship of data in the region.
PROFINET Physical Interface
Appearance layout
Product dimensions