Main functions and features of the system
(1) The instrument adopts infrared sensors
Infrared absorption principle, dual wavelength, with temperature compensation function
High reliability, high stability, sensor lifespan greater than10 Years
Digital and analog output
(2) Real time and quantitative detection of SF6gas concentration:
Accurately measure SF in the air within the range of 0-3000ppm6Gas content, full range quantitative display.
(3)SF6Gas concentration exceeding limit alarm
SF6Gas content exceeds the allowable thresholdAt 1000ppm, the system emits an audible and visual alarm.
(4) Real time oxygen concentration detection
The system can beAccurately measure the oxygen content in the air within the range of 0-35%.
Oxygen content below allowable thresholdAt 18%, the system emits an audible and visual alarm.
(5) Universal Power Protocol, seamlessly integrated with integrated automation systems
The system adopts485 communication mode, optional with 61850 or IED communication module, to achieve seamless integration with multiple domestic integrated automation manufacturers such as NARI, Nanzi, Xuji, Sifang, Dongfang Electronics and other systems.
(6) Multi parameter output
Through the power protocol, the system can integrate various collectorsSF6、O2Multiple parameters such as content, temperature and humidity values, alarm status, etc. are transmitted in real-time to the integrated automation system, truly achieving unmanned operation.
(7) Multi state output
The system can simultaneously provide alarm signals24V signal and constant on/off switch.
(8) Multiple fan control methods
The fan operates throughout the dayMultiple starting methods such as timed self start, forced start, and personnel induction start are available for 5 time periods to more effectively ensure personal safety.
Main technical characteristics of the system
(1) Equipment lifespan: Over 10 years
(2) Working environment
Temperature range: -30℃~+65 ℃
Humidity range:≤99%RH
Earthquake level:7 degrees
Atmospheric pressure:86kPa~106kPa
(3)SF6Measurement indicators
Measurement range:0~3000ppm
Reference error:±5%FS
(4) Oxygen measurement indicators
Detection concentration:0~35%
Oxygen concentration alarm point:18%
Oxygen measurement accuracy:<>2existAt 21%
(5) Other indicators
Working power supply:AC 220V
Switching output capacity:24V/48V/110V/220V
Fan output contact current: 45A (customizable according to user needs)
Fan ventilation time setting: adjustable, default15MIN/time
Communication method:RS-485 bus mode, universal power communication protocol
Insulation performance Between the casing and the power supply:>10MΩ
Electrical strength Between the casing and the power supply:>2000V
Electromagnetic compatibility characteristics: fast transient pulse trainGB/T17626.4-1999 Level 3
Lightning strike (surge)GB/T17626.5-1999 Level 3