Technical parameters: T968Y electric high pressure differential regulating valve Main technical parameters: working temperature ℃: -40~230 ℃ (room tem
Product details

The T968Y electric high-pressure differential regulating valve consists of a PS series or 3610 series linear electric actuator and a low flow resistance straight through single seat valve. (It can also be paired with other brands of direct travel actuators). The electric actuator is an electronic integrated structure with a servo amplifier inside. By inputting control signals (4-20mADC or 1-5VDC) and power supply, the valve opening can be controlled to adjust working parameters such as pressure, flow rate, liquid level, and temperature. It has the characteristics of sensitive action, simple connection, large flow rate, small volume, and high adjustment accuracy. The control accuracy and performance are significantly improved compared to the DKZ type.
Single seat valves are suitable for situations with strict requirements for leakage, low pressure difference before and after the valve, and a certain viscosity. Widely used in industries such as power, metallurgy, chemical, petroleum, environmental protection, light industry, equipment, etc.

Main technical parameters:

Nominal diameter mm G3/4” 20 25 32 40 50 65 80 100 125 150 200 250 300 350 400
Valve seat diameter mm 3 4 5 6 7 8 10 12 15 20 26 32 40 50 66 80 100 125 150 200 250 300 Can collaborate with our company
Negotiate production
Rated flow coefficient kv Linear type 0.08 0.12 0.20 0.32 0.5 0.8 1.8 2.8 4.4 6.9 11 17.6 27.5 44 69 110 176 275 440 690 1000 1600
Equal percentage





1.6 2.5 4 6.3 10 16 25 40 63 100 160 250 400 630 900 1440
Nominal pressure (MPa) 0.6,1.6,2.5,4.0,6.4
Travel distance (mm) 10 16 25 40 60 100
Traffic characteristics straight line Straight line, equal percentage, quick open
Working temperature ℃ -40-230 ℃ (normal temperature type), heat sink 230-450 ℃ (medium temperature type), special order -100-600 ℃
Flange size Compliant with JB78-59 and JB79-59 standards, can be ordered and produced according to JB/79.1-94, JB, ANSI, JIS, DIN and other standards
body material WCB(ZG230-450)、ZG1Cr18Ni9Ti、ZG0Cr18Ni12Mo2Ti CF8 CF8M
Valve core material 1Cr18Ni9,SS304,0Cr18Ni12Mo2Ti,SS316,ZG1Cr18Ni9Ti
Valve type Straight through single seat cast ball valve
Upper valve cover type Ordinary (room temperature), hot plate (medium temperature), long neck (low temperature)
Equipped with electric actuator model PSL PSL-201 PSL-202 PSL-204 PSL-208 PSL-312 PSL325
361L 361LSA-08
361LXA-08
361LSA-20 361LSB-30 361LSB-
50
361LSC-65 361LSC-99
Explosion proof type 361LXA-20 361LXB-30 361LXB-
50







Note:
1. We can provide users with products that meet national flange standards such as ANSI, JPI, and JPI, with flange spacing determined according to user needs.
2. Products with working temperature, nominal pressure, and nominal diameter exceeding the listed range can be resolved through negotiation with our company


Main technical parameters of the executing agency:

model Rated output force N Speed mm/s Technical Parameter
PSL 361L PSL 361L PSL 361L PSL 361L
201 361LSA-08
361LXA-08
1000 800
800
0.25 4.2
4.2
Power supply: AC220V 50Hz
Input signal: DC4-20mA
DC1-5V
(Shielded wire for signal line)
Output signal: DC4-20mA
Protection level: IP67
With handwheel
Power supply: AC220V 50Hz
Input signal: DC4-20mA
DC1-5V
(Shielded wire for signal line)
Output signal: DC4-20mA
Protection level: equivalent to IP55
Explosion proof mark: Exd Ⅱ BT4
With handle
202 361LSA-20
361LXA-20
2000 2000
2000
0.50 2.1
2.1
204 361LSB-30
361LXB-30
4500 3000
3000
0.50 3.5
3.5
208 361LSB-50
361LXB-50
8000 5000
5000
1.00 1.7
1.7
312 361LSC-65 12000 6500 0.60 2.8
325 361LSC-99 25000 10000 1.0 2.0

Performance indicators:

project Indicator value
Basic error% Equipped with 3610L ± 2.5; Equipped with locator ± 1.0
Return difference% Equipped with 361L ± 2.0; Equipped with PSL ± 1.0
Dead zone% 1.0
Constant point deviation% teletransmission Starting point ±2.5
End ±2.5
Electricity off Starting point ±2.5
End ±2.5
Adjustable range 50:1
Rated travel deviation% 2.5
Discharge rate L/H Compliant with JB/T7387-94 Level IV rated capacity of less than valve × 10-4

Allowable pressure difference:

Nominal diameter (mm) 20 25 40 50 65 80 100 150 200 250 300
Valve seat diameter (mm) 10 12 15 20 25 32 40 50 65 80 100 125 150 200 250 300
actuator Allowable pressure difference △ P (MPa)
Equipped with PSL PSL202 6.4 6.4 6.4 4.90 3.14 1.92 1.23 0.78







PSL204




4.31 2.76 1.76 1.04 0.69 0.44




PSL208







1.86 1.23 0.78 0.50 0.35 0.20

PSL320










1.26 0.87 0.49 0.32 0.22
Equipped with 361L 361LSA-20 6.4 6.4 6.4 4.90 3.14 1.92 1.23 0.78







361LSB-50




4.79 3.06 1.96 1.16 0.76 0.49




361LSC-65







1.51 0.99 0.64 0.41 0.28


361LSC-99










0.63 0.44 0.25 0.16 0.11