model |
SLB-2F |
SLB-3F |
SLB-3F |
|
control system |
PLCcontroller |
|||
Temperature control mode selection |
The material temperature control and equipment outlet temperature control modes can be freely selected |
|||
Temperature difference control |
The temperature difference between the equipment outlet temperature and the reaction material temperature can be controlled and set |
|||
Programming |
Can be compiled10Program, each program can be programmed40Step by Step |
|||
communication protocol |
MODBUS RTUagreementRS 485interface |
|||
Material temperature feedback |
PT100 |
|||
Temperature feedback |
Three temperature points: equipment inlet temperature, equipment outlet temperature, and reactor material temperature (external temperature sensor) |
|||
Temperature control accuracy of thermal conductive medium |
±0.5℃ |
|||
Temperature control accuracy of reaction materials |
±1℃ |
|||
compressor |
sanyo |
sanyo |
sanyo |
|
expansion valve |
danfoss/Emerson Thermal Expansion Valve |
|||
evaporator |
danfoss/Yalong Plate Heat Exchanger |
|||
operation panel |
7Inch color touch screen, temperature curve display and recording |
|||
safety protection |
Having self diagnostic function; Refrigerator overload protection; High pressure switch, overload relay, thermal protection device and other safety protection functions. |
|||
Closed circulation system |
The entire system is a fully enclosed system, which does not produce oil mist at high temperatures and does not absorb moisture from the air at low temperatures. The system does not increase pressure due to high temperatures during operation, and automatically replenishes the heat transfer medium at low temperatures. |
|||
refrigerant |
R-404A/R507C |
|||
interface size |
G1/2 |
G1/2 |
G1/2 |
|
External dimensionscm |
74*47*107 |
90*66*115 |
118*66*127 |
|
Standard weight |
88kg |
145kg |
182kg |
|
power supply |
AC 220V 50HZ(max) |
AC 220V 50HZ(max) |
AC380V 50HZ(max) |
|
Shell material |
SUS 304 |
SUS 304 |
SUS 304 |
|
Optional |
Positive pressure explosion-proof Add suffixPEX |
|||
Optional |
Optional Ethernet interface and computer operating software configuration |
|||
Optional |
Optional external touch screen controller, communication cable distance10M |
|||
Optional power supply |
100V 50HZsingle-phase,110V 60HZsingle-phase,230V 60HZsingle-phase,220V 60HZthree-phase,440V~460V 60HZthree-phase |