Changhui Automation System Co., Ltd
Home>Products>Thermocouple/thermal resistance isolated safety barrier
Thermocouple/thermal resistance isolated safety barrier
Thermocouple/thermal resistance isolated safety barrier
Product details

Specification parameters
explain
Number of channels
One in, two out
Explosion proof mark
[Exia]ⅡC
Adapt to the Place
Installed in a safe place, it can be connected to intrinsically safe instruments in Zone 0 hazardous areas with IIA, IIB, and IIC hazardous gases.
Supply Voltage
20~35VDC
power consumption
≤ 2.3W (24V power supply, 20mA output)
Dangerous zone signal
thermocouple
signal type
Range of measurement
B
500~1820℃
S
-50~1769℃
K
-50~1372℃
E
-50~1000℃
T
-200~320℃
J
-50~1200℃
WRe(3-25)
0~2300℃
thermal resistance
signal type
Range of measurement
CU50
-50.0~150.0℃
PT100
-199~850℃
PT100.1
-199.9~320.0℃
(Users need to specify the signal type and range when placing an order)
Safety zone signal
Current output: 4-20mADC
Load resistance: ≤ 800Ω
Voltage output: 1-5VDC
Load resistance: ≥ 10KΩ
(Users need to select current or voltage output when placing orders)
Power protection
Reverse power protection
output accuracy
0.3%F.S
temperature drift
0.01%F.S/℃
Instrument structure
Nylon plastic shell structure
weight
About 150g
Applicable on-site equipment
Two wire and three wire transmitters, current source signals

Thermocouple isolated safety barrier

Model specifications
Additional code
explain
SWP7081-Ex
/□
/□
/□
Thermocouple isolation safety barrier
Input Type
/B
B (Range: 500-1820 ℃)
/S
S (Range:- 50~1769℃)
/K
K (Range:- 50~1372℃)
/E
E (Range:- 50~1000℃)
/T
T (Range:- 200~320℃)
/J
J (Range:- 50~1200℃)
/W
WRe (3-25) (Range: 0-2300 ℃)
Channel 1 output type
/I
Channel 1: 4-20mA output (safe zone)
/V
Channel 1:1~5V output (safe zone)
Channel 2 output type
/I
Channel 2: 4-20mA output (safe zone)
/V
Channel 2:1 to 5V output (safe zone)
Thermal resistance isolated safety barrier

Model specifications
Additional code
explain
SWP7083-Ex
/□
/□
/□
Thermal resistance isolation safety barrier
Input Type
/CU50
Cu50 (range:- 50~150℃)
/Pt100
Pt100 (range:- 199~850℃)
/Pt100.1
Pt100.1 (Range:- 199.9~320.0℃)
Channel 1 output type
/I
Channel 1: 4-20mA output (safe zone)
/V
Channel 1:1~5V output (safe zone)
Channel 2 output type
/I
Channel 2: 4-20mA output (safe zone)
/V
Channel 2:1 to 5V output (safe zone)
Note: If the user does not specify the channel output type in the order, it will be produced and shipped according to the output type of 4-20mA.

Online inquiry
  • Contacts
  • Company
  • Telephone
  • Email
  • WeChat
  • Verification Code
  • Message Content

Successful operation!

Successful operation!

Successful operation!