ZDLQ electronic three-way merging control valve and ZDLX electronic three-way diversion control valve are composed of PS series and 3610 series linear electric actuators and low flow resistance straight through single seat valves. (It can also be paired with other brands of direct travel actuators). The electric actuator is an electronic integrated structure with a servo amplifier inside. By inputting control signals (4-20mADC or 1-5VDC) and power supply, the valve opening can be controlled to adjust working parameters such as pressure, flow rate, liquid level, and temperature. It has the characteristics of sensitive action, simple connection, large flow rate, small volume, and high adjustment accuracy. The control accuracy and performance are significantly improved compared to the DKZ type.
The electronic electric three-way regulating valve has the advantages of high regulation accuracy, stable and reliable action. Confluence type is mainly used to mix two fluids into a third fluid; Split flow type is mainly used to divide one fluid into two fluids. This product can replace two single or double seat regulating valves that are mutually switchable, and is used for regulating and controlling media such as liquids, gases, and steam.
Equipped with 361L actuator, combined with PSL actuator, split flow
Main technical parameters and performance indicators
Main technical parameters of the regulating mechanism
Nominal diameter mm |
Confluence |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
shunt |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
|
Valve seat diameter mm |
26 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
|
Rated flow coefficient kv |
Confluence |
8.5 |
13 |
21 |
34 |
53 |
85 |
135 |
210 |
340 |
535 |
800 |
1260 |
shunt |
8.5 |
13 |
21 |
34 |
53 |
85 |
135 |
210 |
340 |
535 |
800 |
1260 |
|
Nominal pressure (MPa) |
0.6,1.6, 2.5, 4.0, six point four |
||||||||||||
Travel distance (mm) |
16 |
25 |
40 |
60 |
100 |
||||||||
Traffic characteristics |
straight line |
||||||||||||
Working temperature ℃ |
-40-230 ℃ (normal temperature type), heat sink 230-450 ℃ (medium temperature type), special order -100-600 ℃ |
||||||||||||
Flange size |
Compliant with JB78-59 and JB79-59 standards, can be ordered and produced according to JB/79.1-94, JB, ANSI, JIS, DIN and other standards |
||||||||||||
body material |
WCB(ZG230-450)、ZG1Cr18Ni9Ti、ZG0Cr18Ni12Mo2Ti CF8 CF8M |
||||||||||||
Valve core material |
1Cr18Ni9, SS304,0Cr18Ni12Mo2Ti,SS316,ZG1Cr18Ni9Ti |
||||||||||||
Valve type |
Three way double seat cast ball valve |
||||||||||||
Upper valve cover type |
Ordinary (room temperature), heat sink (medium temperature), long neck (low temperature) |
||||||||||||
Equipped with electric actuator |
PSL |
PSL-202 |
PSL-204 |
PSL-208 |
PSL-312 |
PSL325 |
|||||||
361L |
361LSA-20 |
361LSB-30 |
361LSB-50 |
361LSC-65 |
361LSC-99 |
||||||||
Explosion proof type |
361LXA-20 |
361LXB-30 |
361LXB-50 |
|
Note: 1. We can provide users with products that meet national flange standards such as ANSI, JPI, and JPI, with flange spacing determined according to user needs.
2. Products with working temperature, nominal pressure, and nominal diameter exceeding the listed range can be resolved through negotiation with our company
performance
1. Main technical parameters of the executing agency
model |
Rated output force N |
Speed mm/s |
technical parameter |
||||
PSL |
361L |
PSL |
361L |
PSL |
361L |
PSL |
361L |
201 |
361LSA-08 |
1000 |
800 |
0.25 |
4.2 |
Power Supply: AC220V 50Hz |
Power Supply: AC220V 50Hz |
202 |
361LSA-20 |
2000 |
2000 |
0.50 |
2.1 |
||
204 |
361LSB-30 |
4500 |
3000 |
0.50 |
3.5 |
||
208 |
361LSB-50 |
8000 |
5000 |
1.00 |
1.7 |
||
312 |
361LSC-65 |
12000 |
6500 |
0.60 |
2.8 |
||
325 |
361LSC-99 |
25000 |
10000 |
1.0 |
2.0 |
2. Performance indicators
project |
Indicator value |
||
Basic error% |
±2.5 |
||
Return difference% |
2.5 |
||
Dead zone% |
1.0 |
||
Constant point deviation% |
Electric opening |
Starting point |
±2.5 |
End |
±2.5 |
||
Electricity off |
Starting point |
±2.5 |
|
End |
±2.5 |
||
Adjustable range |
30:1 |
||
Rated travel deviation% |
2.5 |
||
Allowable discharge rate L/H |
Compliant with JB/T7387-94 Level IV, 10-4 below rated capacity |
3. Allow pressure difference
Nominal diameter mm |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
Allowable pressure difference (MPa) |
3.32 |
2.20 |
2.20 |
1.41 |
1.38 |
0.94 |
0.61 |
0.51 |
0.36 |
0.20 |
0.19 |
0.13 |
Note: The actual configuration needs to be determined based on specific process parameters. If the pressure difference is allowed to be clear or the maximum working pressure difference exceeds the list range, please contact us and take appropriate measures to solve it
Dimensions mm
Public diameter (mm) |
25 |
32 |
40 |
50 |
65 |
80 |
100 |
125 |
150 |
200 |
250 |
300 |
||
L(mm) |
PN1.6MPa |
185 |
200 |
220 |
250 |
275 |
300 |
350 |
410 |
450 |
550 |
640 |
740 |
|
PN4.0MPa |
190 |
210 |
230 |
255 |
285 |
310 |
355 |
425 |
460 |
560 |
660 |
760 |
||
PN6.4MPa |
200 |
210 |
235 |
265 |
295 |
320 |
370 |
440 |
475 |
570 |
670 |
770 |
||
H1(mm) |
PN1.6MPa |
140 |
150 |
160 |
180 |
200 |
220 |
220 |
256 |
278 |
322 |
465 |
580 |
|
PN4.0MPa |
150 |
160 |
170 |
190 |
220 |
232 |
256 |
295 |
313 |
372 |
474 |
585 |
||
PN6.4MPa |
160 |
170 |
180 |
200 |
220 |
242 |
266 |
300 |
318 |
382 |
474 |
585 |
||
Equipped with PSL |
H(mm) |
Ordinary type |
775 |
781 |
775 |
790 |
819 |
820 |
810 |
917 |
927 |
947 |
1252 |
1545 |
Heat sink type |
905 |
911 |
905 |
920 |
766 |
983 |
973 |
1116 |
1126 |
1144 |
1805 |
1825 |
||
D(mm) |
176 |
|||||||||||||
Weight (KG) |
61.5 |
64.5 |
69.5 |
76.5 |
109 |
132 |
164 |
207 |
267 |
395 |
430 |
480 |
||
Equipped with 361L |
H(mm) |
Ordinary type |
538 |
544 |
660 |
675 |
744 |
745 |
735 |
972 |
982 |
1027 |
1204 |
1265 |
Heat sink type |
668 |
674 |
790 |
805 |
691 |
908 |
898 |
1171 |
1181 |
1224 |
1440 |
1502 |
||
D(mm) |
225 |
310 |
||||||||||||
Weight (KG) |
69 |
72 |
85 |
92 |
124 |
147 |
179 |
260 |
320 |
448 |
627 |
780 |
Note: Diverter valves with a nominal diameter less than 80 shall be replaced by merging valves of the same diameter