ZG5-1 type corrugated flame arrester
ZG5-1 type corrugated flame arrester
Product details

ZG5-1 typeRipple type flame arrester

Main purpose

ZGB-1 corrugated flame arrester is used to install important safety equipment on fixed top storage tanks for crude oil, gasoline, kerosene, diesel, aromatics, sulfur, and other fuels. Its function is to allow flammable and explosive gases to pass through, and to prevent suffocation of flames.

main features

1. This new type of flame arrester is a technological achievement designed by Beijing Design Institute of China Petroleum&Chemical Corporation in 1986. It has been tested and verified by Tianjin Fire Science Research Institute of the Ministry of Public Security and meets the requirements of the national standard GB5908-86.
2. The product has a reasonable structure and beautiful appearance. The shell is made of cast aluminum alloy, which is lightweight and easy to install. The fire-resistant layer core is made of stainless steel material, which has strong corrosion resistance and outstanding technical performance such as fire resistance and explosion resistance.
3. This flame arrester is usually used in conjunction with a breathing valve or separately, and can also be applied to the ventilation pipeline of an internal floating roof oil tank.

Please indicate the product name, model, and specifications when placing an order.

Structure diagram

Main appearance and flange connection dimensions
specifications
Weight
(Kg/set)
Weight
Installation size (millimeters)
D2
D
L
H
nר
DN50
6
Ø110
Ø140
220
235
4×14
DN80
17
Ø150
Ø185
280
270
4×18
DN100
20
Ø170
Ø205
325
275
4×18
DN150
25
Ø225
Ø260
425
290
8×18
DN200
35
Ø280
Ø315
495
305
8×18
DN250
46
Ø335
Ø370
595
320
12×18
Note: The connecting flange complies with the provisions of JB78-59 "Cast Iron Flanges"

Maintenance and repair

In order to ensure the safe use of flame arresters, they should be regularly inspected and maintained.
1. The flame arrester should be inspected every six months to check whether the flame arrester core is blocked, deformed, corroded, etc.
2. The blocked fire-resistant layer core should be cleaned thoroughly to ensure that each hole on the core is unobstructed, and any deformed or corroded fire-resistant layer should be replaced.
3. When reinstalling the fire-resistant layer core, it should be ensured that the joint surface is tight and there is no air leakage.