Used to monitor the density of SF6 gas in sealed containers and display the gas density on site. Alarm when the density value reaches the set value, s
Product details

Used for monitoring sealed containersSF6Density of gasCapable of displaying gas density on site.Alarm when the density value reaches the set value, suitable for monitoring high-voltage systems. We can provide various solutions such as supporting new substations and intelligent transformation of existing substations.



ZMJ100P型密度继电器




SF6Insulated composite electrical appliances(GIS

SF6Insulated Circuit Breaker

SF6Insulated pole switch

SF6insulating transformer

SF6Insulation Transformer

SF6Insulated busbar system


  1. Equipped with temperature compensation device for higher measurement accuracy

  2. Suitable for different installation needs indoors and outdoors

  3. selectAISI 304Stainless steel made sealed case

  4. selectAISI 316Stainless steel made pneumatic connection components

  5. The on-site display values and output signals are not affected by external factors such as altitude

  6. Electric contact switch design, achieving precise and stableSF6Gas density monitoring function

  7. at mostfourDocking point, multiple options such as overpressure alarm, dual alarm or dual locking can be implemented, making monitoring safer and more reliable


  1. Shell diameter:100mm

  2. Measurement range:-0.1 ~0.9MPa(Customizable)

  3. Measurement accuracy: (depends on the measurement range, andSF6For gaseous state

    20°C: 1.0level,perhaps1.5level

    -40°C~+60°C: 2.5level

  4. Protection level:IP65

  5. Working temperature:-40°C~ +60°C,relative humidity95%RH

  6. Leakage rate:1×10-9 Pa·m3/s (Helium leak detection)

  7. Interface size:M20×1.5(Can)Customized)

  8. Installation method: radial or axial

  9. Electrical connection: plug-in connectionM20×1.5Sealing head

    Cable size: recommended1.5mm2,maximum2.5mm2

  10. Insulation performance: Insulation resistance:>100 MW(DC 500V)

    Power frequency withstand voltage:2kV, 50/60 Hz, 1min

  11. Contact type: Magnetic assisted electric contact switch

    80%Silver20%Nickel,10µmgold-plating

  12. Impact level:50g (Oil filled type)30g(Non oil filled type)

  13. Contact electrical parameters:30W/50VA, 1A.(Maximum)

    220VDC/380V 50/60Hz(maximum)

  14. Table glass: multi-layer safety glass

  15. Weight: 1.0kg


Refillable oil

completerangeshowprice1.0level

power-frequency withstand voltage2.5kV,50/60 Hz,1min

A wider temperature range:-60°C~+60°C

measureQuantitative medium:SF6AirN2SF6+N2Waiting for gas