Used for monitoring sealed containersSF6The density of gas can be displayed on site, and an alarm will be triggered when the density value reaches the set value, with real-time remote transmissionSF6Gas density data, realizing online remote monitoring function. Suitable for monitoring high-voltage systems. We can provide various solutions such as supporting new substations and intelligent transformation of existing substations.
SF6Insulated composite electrical appliances(GIS)
SF6Insulated Circuit Breaker
SF6Insulated pole switch
SF6insulating transformer
SF6Insulation Transformer
SF6Insulated busbar system
1. Equipped with temperature compensation device for higher measurement accuracy
2. The perfect combination of mechanics and electronics, on-site indication and control of instruments. Adopting precision mechanical structure and possessing real-time remote transmission function of electronic signals
3. RS485Bus interface, easy system expansion, convenient for implementing telemetry and remote control functions. Strong ability to resist electromagnetic interference
4. Suitable for different installation needs indoors and outdoors
5. selectAISI 304Stainless steel made sealed case
6. selectAISI 316Stainless steel made pneumatic connection components
7. The on-site display values and output signals are not affected by external factors such as altitude
8. at mostfourDocking point, multiple options such as overpressure alarm, dual alarm or dual locking can be implemented, making monitoring safer and more reliable
1. Shell diameter:100mm
2. Measurement range:-0.1 ~ 0.9MPa(Customizable)
3. Measurement accuracy: (depends on the measurement range, andSF6For gaseous state)
a)20°C: 1.0level,perhaps1.5level
b)-40°C ~ +60°C: 2.5level
4. Protection level:IP65
5. Working temperature: -40°C~ +60°C,relative humidity≤ 95%RH
6. Leakage rate:≤1×10-9Pa·m3/s (Helium leak detection)
7. Interface size:M20×1.5(Can)Customized)
8. Installation method: radial or axial
9. Electrical connection: plug-in connectionM20×1.5Sealing head
Cable size: recommended1.5mm2,maximum2.5mm2
10. Insulation performance: Insulation resistance:>100 MW(DC 500V)
Power frequency withstand voltage:2kV,50/ 60 Hz 1min
11. Contact type: Magnetic assisted electric contact switch
80%Silver20%Nickel,10µmgold-plating
12. Impact level:50g (Oil filled type), 30g(Non oil filled type)
13. Contact electrical parameters:30W/ 50VA, 1A.(Maximum)
220VDC/ 380V 50/ 60Hz(maximum)
14. Table glass: multi-layer safety glass
15. Weight: 1.2kg
16. Pressure sensing component: imported Burton tube
Main electrical performance indicators and specifications for remote transmission
lWorking voltage:DC 24V
lpower waste:<>
lCommunication method:RS485
lCommunication protocol:ModBus RTU
lTransmission speed:9600bps
lanti-electromagnetic interferenceIEC61000-4-2:4level(15kV)
IEC61000-4-3:3level(10V/m)
IEC61000-4-4:4level(4kV)
IEC61000-4-5:3Grade(+/-2kV)
IEC61000-4-6:3Grade(10V)
IEC61000-4-8:5Grade(100A/m)
power-frequency withstand voltage2.5kV 50/60 Hz 1min
Refillable oil
Measurement medium:SF6、Air、N2、SF6+N2Waiting for gas